Simatic S5 Positioning Modules
Siemens SIMATIC S5 Positioning, Encoder and Motion Control Modules
Siemens SIMATIC S5 positioning modules perform tasks such as encoder evaluation, pulse counting, positioning, stepper motor command generation and electronic cam processing. This section covers hardware and a configuration package associated with the IP 240, IP 241, IP 246, IP 247, IP 263, IP 265, IP 266, IP 267 and IP 288 families.
Identify the control task, encoder interface, drive command and complete order number before selecting a replacement. Incremental encoders, parallel absolute encoders and SSI require different interfaces. An axis using an analog speed reference also needs different control hardware from a pulse/direction stepper axis.

IP 240: counting, position sensing and positioning
6ES5 240-1AA12 and 6ES5 240-1AA21 are IP 240 hardware modules. Counting, position sensing and positioning functions are configured for the application. Check the encoder signal, channel settings, standard function blocks and CPU data exchange together. Replacement between 1AA12 and 1AA21 requires the applicable supplementary product information.
6ES5 240-5AA11 is the German-language IP 240 configuration package. Check its contents, standard STEP 5 blocks, software environment, original media and licence separately from the hardware. An order number alone does not establish that a usable software installation is available.
IP 241: basic modules and encoder matching modules
6ES5 241-1AA11 and 6ES5 241-1AA12 are IP 241 basic modules, completed by the appropriate encoder matching module. The 1AA12 supports 16 cam tracks per channel in two-channel operation, or 32 tracks in single-channel operation. These functions provide position-dependent switching; a separate power stage supplies the motor.
6ES5 241-1AB11 belongs to the incremental encoder matching group; 6ES5 241-1AC11 to parallel Excess-3 Gray; 6ES5 241-1AD12 to parallel BCD/binary; and 6ES5 241-1AF12 to synchronous serial SSI. Match the encoder’s electrical interface and data code to the selected matching module.
The MIR variant 6ES5 241-3CA12 requires separate assessment. Use the existing measuring system and exact model documentation to establish its connections and settings, rather than transferring information from a digital IP 241 basic module or another encoder adapter.
IP 246: incremental and absolute feedback
6ES5 246-4UA31 and 6ES5 246-4UA41 are IP 246I incremental versions; 6ES5 246-4UB11 and 6ES5 246-4UB21 are IP 246A absolute versions. The family provides two-axis positioning with an analog speed reference to the drive. Compare encoder type, machine data, referencing and COM 246 settings for the exact replacement version.
IP 247: stepper motor positioning
6ES5 247-4UA11, 6ES5 247-4UA21, 6ES5 247-4UA31 and 6ES5 247-4UA41 belong to the IP 247 stepper motor positioning family. The module sends movement commands to a suitable drive; the motor requires a separate power stage. The 4UA31 requires forced ventilation, while the 4UA41 uses natural cooling. Check width, adapter casing and cooling requirements for the complete order number.
IP 263: rapid-traverse and creep-speed positioning
6ES5 263-8MA11, 6ES5 263-8MA12 and 6ES5 263-8MA13 belong to the IP 263 family. Its basic positioning method uses rapid-traverse, creep-speed and direction commands for two axes. Confirm incremental or SSI feedback requirements against the exact version’s connections and parameters; retain the distinction between 8MA11, 8MA12 and 8MA13.
IP 265, IP 266 and IP 267: different control tasks
The IP 265 6ES5 265-8MA01 is a high-speed sub-control module. Its application depends on the loaded program and memory contents. When purchasing used equipment, identify the software and application function as well as checking that the board powers up.
The IP 266 6ES5 266-8MA11 supports positioning with encoder feedback and a ±10 V analog reference to the drive. The IP 267 6ES5 267-8MA11 is a separate controller generating pulse/direction commands for a stepper drive. Select the module to suit the drive’s command input.
IP 288: three axes and electronic cams
The IP 288 6ES5 288-4UA11 provides three-axis positioning and electronic cam functions. Machine data, target positions and cam tables form part of the application. Check COM 288 data and PLC data exchange when replacing the hardware.
Testing a used positioning module
Compare the complete model, quantity, working/faulty condition, nameplate photographs and price. Establish the conditions used to test encoder inputs, drive command outputs, digital enables and parameter retention. Illuminated LEDs alone do not establish that axis control has been tested.
Editor’s note
Start with the actual control task. Reading an encoder, generating cam outputs, sending an analog speed reference and producing stepper pulses require different hardware. Similar front panels are insufficient grounds for choosing a replacement.
Before removal from a working machine, back up machine data, reference settings, targets and PLC blocks. These parameters may be harder to replace than the board itself. A blank replacement cannot automatically recover the machine’s previous configuration.
Distinguish 5 V RS-422, 24 V incremental, parallel absolute and SSI connections. Record the encoder nameplate, cabling and switch/jumper positions together. A sound encoder connected to the wrong interface will not provide reliable position data.
During initial controlled movement checks, verify direction, reference sensor, limits and drive enables. Resolve reversed or inconsistent position readings before automatic operation. Mechanical play in couplings or the screw assembly can also affect positioning.
Distinguish an IP 241 basic module from its encoder matching module, and IP 240 hardware from the 5AA11 configuration package. For IP 247, check cooling and adapter requirements as part of the replacement.
Agree the test scope and included items before buying used equipment. Workshop testing is possible, with the method determined by the module and available equipment. All sales require an invoice; returns are not accepted. To offer an S5 module for sale, send the model, quantity, condition, nameplate photographs and asking price to otomasyonavm@gmail.com.
OtomasyonAVM resources and PDFs
For system background, see About Siemens S5 PLCs, the SIMATIC S5 main page and S5 CPU models. Review central units and expansion racks when checking module installation.
Use the S5 system manuals and PDF files archive for connection, commissioning and parameter information. Compare the complete order number, hardware version and document edition as well as the family name. Configuration software, documentation and hardware are separate delivery items.
Related topics
Review S5 cables and connectors, S5 interface modules, S5 power supplies and S5 racks and mounting frames when planning connections and installation. The S5 module groups section provides routes to other system modules.
Browse SIMATIC S5
+ SIMATIC S5 | Siemens S5 PLCs | S5 module groups | Used Siemens equipment | All used equipment
Siemens and external references
+ IP 240 Counter/Positioning/Position Decoder Module Manual — EWA 4NEB 811 6120-02b; Edition 03; English.
+ IP 241 Digital Position Decoder Manual — 6ES5 998-0KD21; Release 02; English.
+ IP 246 Positioning Module Manual — 6ES5 998-5SA23; Release 04; English.
+ IP 247 Positioning Module for Stepper Motors Manual — 6ES5 998-5SB22; Release 02; English.
+ S5-100U System Manual — Function Modules — EWA 4NEB 812 6120-02b; English.
+ IP 265 High Speed Sub Control Manual — EWA 4NEB 812 6130-02a; English.
+ IP 267 Stepper Motor Controller Manual — EWA 4NEB 812 6061-02a; English.
+ IP 288 Manual — 6ES5 998-5SF21; Release 01; English.
+ Siemens SIMATIC S5 Catalog ST 50 — ST 50, 1998; English; Siemens catalogue, external archive copy.