6ES5 752-0AA53

Siemens 6ES5 752-0AA53 — PG Interface Submodule for CPU 928B / CPU 948

The Siemens 6ES5 752-0AA53 is a PG/OP interface submodule installed in the SI2 receptacle of a CPU 928B or CPU 948 in SIMATIC S5 systems. It uses a 20 mA current loop, a fixed 9600 bit/s PG transmission rate and a 15-pin female Sub-D connector. Within the S5 interface module range, it provides a second programming-device or compatible operator-panel connection.

The submodule equips SI2 on the Siemens S5 PLC for PG access. It can provide a second PG connection alongside SI1 or connect a suitable OP. The PG supplies the loop current; the submodule transmitter and receiver operate according to that current-loop arrangement.

20 mA PG connection and signal pins

For PLC programming, use the appropriate S5 PG cable and interface hardware. The main signal pins are 9 = +RxD, 2 = −RxD, 6 = +TxD and 7 = −TxD; housing/shield connections use pins 1 and 8. When selecting S5 cables and connectors, retain the other connections required by the manufacturer’s diagram. A 15-pin connector alone does not establish RS232 or RS422 compatibility.

PG communication operates at a fixed 9600 bit/s. Siemens specifies up to 1000 metres under the standard cable and connection conditions. Assess the actual cable and PG hardware together rather than applying that distance to an arbitrary converter or cable.

CPU compatibility and related 752 variants

Check the complete CPU number and hardware revision: CPU 928B examples include the 6ES5 928-3UB11, 6ES5 928-3UB12 and 6ES5 928-3UB21; CPU 948 examples include the 6ES5 948-3UA11 and 6ES5 948-3UA21. Match the PG submodule’s J1 processor selection to the CPU 928B/948 setting in the manual.

Other family members serve different interfaces: the 752-0AA12 is TTY, the 752-0AA23 is V.24/V.28, the 752-0AA43 is RS422/485, and the 752-0AA62 is SINEC L1. The 0AA53 is the PG/OP submodule; do not transfer those interface functions between part numbers.

If replacing a 752-0AA52, review its revision and CPU requirements. The 752-0LA12 TTY, 752-0LA52 PG and 752-0LA62 SINEC L1 are catalogued for CPU 945 applications. Consider the complete part number and processor selection together rather than deciding from connector appearance.

SI2 operating mode and DX2

SI2 supports different communication tasks according to the installed submodule and CPU configuration. A DX2 configured for a computer link can conflict with the intended PG function when a PG submodule is installed. When reviewing S5 communications modules, check the physical interface, selected port and software task together.

Installation and mechanical connection

To replace the submodule, switch off the PLC supply, remove the CPU from the rack and secure the submodule with its two screws. These screws also contribute to the CPU’s shielding/ground connection. Inspect the J1 jumper, front connector pins and internal CPU connection before installation. The submodule receives its supply through the CPU.

Diagnosing a connection problem

During PLC troubleshooting, assess SI1 and SI2 separately. An SI2 LED going out after startup does not by itself confirm successful communication; that can also happen in certain cases with no submodule installed. Check the module type, PG cable, PG interface setting and existing DX2 together.

Editor’s note

If the PG will not connect, start by checking the cable and PG interface on a known working connection. A reliable starting point makes it much easier to decide whether this small submodule needs attention.

The 0AA53 suffix matters. Before trying another 752 submodule of the same size, establish its interface function. Matching the label to the intended task can save a great deal of time with the wrong cable.

A working SI1 and a non-working SI2 give you a useful comparison. Start with the second port’s submodule, configuration and cable path. Deleting the working program or performing an overall reset should not be the opening step in a communications diagnosis.

Inspect a used unit’s front pins, securing screws and internal connector closely. Bent pins or a loose fit can look like an electronic failure. Establish a sound connection before drawing a firm conclusion about the board.

Where possible, assess a spare through a real PG session on a suitable CPU and observe communication stability. The useful evidence is the connection it maintains, as well as the part number on its label.

OtomasyonAVM resources and PDFs

+ S5 interface modules · S5 communications modules · S5 cables and connectors. Review the submodule together with the CPU and connecting cable.

+ OtomasyonAVM S5 PDF archive and system manuals. Consult section 5.11.2 of the S5-135U/155U manual for pins and J1 selection, and the CPU 928B/948 communication manual for port behavior.

Related topics

+ 752-0AA52 PG submodule · 752-0AA12 TTY · 752-0AA43 RS422/485 · 752-0AA62 SINEC L1.

Browse SIMATIC S5

+ S5 interface modules · SIMATIC S5 · Siemens S5 PLCs · Siemens second-hand main page.

Siemens and external references

+ Siemens S5-135U/155U system manual — English; 5.11.2, 5-95–5-98; specifications 5-122 and ordering table A-4.

+ Siemens CPU 928B/CPU 948 communication manual — English; SI2 functions, LED diagnostics and installation.

+ Siemens 6ES5752-0AA53 data sheet — German; 11 December 2020, third-party archive copy.

+ Siemens ST 50, 1998 — English; 3/24, 4/26 and 4/29; third-party archive copy.