Siemens 6ES5 341-3AA11 – AS 341 External Memory Interface
6ES5 341-3AA11 is the AS 341 interface that manages data exchange between main memory and 340/350 external memory boards in the S5-150S system of the Siemens SIMATIC S5 family. The external memory arrangement supports addressing of up to 64K words; this is not the AS 341 board's own storage capacity.
This S5 interface module supports external storage of data and text. Within the SIMATIC S5 system, 341 manages transfers, 340/350 store the data, and an optional 342 board provides parity monitoring.
System, rack and memory arrangement
The manufacturer manual places the AS 341 in position 67 of the S5-150S central expansion rack, 6ES5 150-3SB31. Check this arrangement when selecting PLC racks and slots; the memory boards occupy positions 35–59 in the documented system.
When assessing S5 memory boards, check the 340/350 order number, capacity and address configuration together. Physical resemblance alone does not establish that a used memory board can perform the same role.
The relevant unit in these memory specifications is the word. 64K words does not mean 64 KB. The AS 341 accesses a selected external memory section through a 2K-word addressing window.
The external RAM and EPROM areas require different preparation. The manual specifies word-mode operation for the memory boards. Understanding ROM types helps, but verify the actual address and jumper settings against the installed board's own manual.
Data transfers with FB 190 and FB 191
In the PLC program, FB 190 – EX:URLAD performs initial loading of external memory and builds the data-block address list. FB 191 – EX:TRADB transfers data blocks between main and external memory.
FB 191 transfers up to 1024 data words per call. Distinguish memory capacity from transfer size: this is the limit for one function-block call, rather than the total capacity of external memory.
During PLC troubleshooting, check block parameters, source/destination areas and returned status together. For arrangements using AS 512 C, the manual also describes direct access; review the existing application before assuming the same transfer method applies everywhere.
Battery, address list and red LED
The front-mounted lithium Mignon cell backs up the address list on the AS 341 during a power failure. Among available battery types, matching physical size alone is insufficient: the specified cell is a non-rechargeable primary lithium battery. Check the lithium battery characteristics and suitability together.
The red LED indicates a battery/backup problem. Its monitoring function can be affected by jumper settings, so an unlit LED alone does not prove that the battery is healthy. When investigating memory data loss, assess the battery, holder, address list and the memory boards' own backup arrangement separately.
Electrical and mechanical specifications
The module operates from the rack's internal 5 V DC ±5% supply, with current consumption of up to 1.5 A. Check the power supply and rack supply with the module installed and under load.
The operating temperature range is 0 to +55 °C; storage and transport are specified at −40 to +70 °C. Dimensions are 20 × 244 × 195 mm (W × H × D), with an approximate weight of 0.3 kg.
Inspect S5 connection components and the board contacts in the rack. Assessing memory reliability requires more than a successful first start: verify address-list and external-data retention after a planned power interruption.
What should be checked on a used module?
When selecting used Siemens equipment, inspect the 6ES5 341-3AA11 label, battery holder, corrosion, jumpers and board-edge connections. Test address-list generation and bidirectional data transfer with the intended PLC CPU and 340/350 boards.
Confirm the S5 system architecture against the actual installation. A category name or a similar order number does not establish compatibility with every S5 CPU and rack.
Editor’s note
Before removing this board, back up the program, external data blocks and address configuration. The manual warns that withdrawing the board interrupts buffering and RAM data can be lost. Give yourself a reliable way back before starting the job.
Insert or withdraw the board only with power switched off. Replacing the front battery and removing the whole board are separate procedures in the manual. Take a moment to distinguish them, so a battery task does not become an unexpected reload.
A red LED is a reason to investigate before condemning the board. Check the battery, its contacts and the monitoring jumpers first. Silencing the indicator does not preserve the address list; verify that the data actually survives.
Before changing 340/350 jumpers, photograph their original positions and write down the addresses. Keep track of which board holds each area. A small record now makes the next service visit much easier.
If a transfer fails, first confirm that FB 190 has built the address list, then check FB 191 parameters. Remember the 1024-word limit per call. Work through the sequence before replacing components that may still be sound.
For the final check, look beyond the CPU reaching RUN. Read and write the external data, then verify retention after a power interruption using an appropriate backup and shutdown plan. That gives you a sound basis for handing the machine back.
OtomasyonAVM resources and PDFs
Start with About Siemens S5 PLC, S5 memory boards and S5 interface modules.
The OtomasyonAVM Siemens S5 PDF archive collects our available S5 documents. Details for this model are based on the German Siemens AS 341 manual below. It appears within a compilation titled S5-150U, but its component section describes the S5-150S external memory system.
Related topics
+ How RAM works and EPROM characteristics.
+ Causes of memory data loss and lithium battery information.
+ PLC programming and PLC troubleshooting.
Browse SIMATIC S5
S5 interface modules · S5 memory boards · SIMATIC S5 systems · Used Siemens equipment
Siemens and external references
+ Siemens AS 341 External Memory Interface Operating Instructions – C79000-B8500-C248-03, German: section beginning on page 64 of the combined PDF; §1.1 system and slots, §1.3 addressing and function blocks, §1.5 specifications, §2 installation, §3 battery monitoring, §4.1 FB 190/191.