6ES5 942-7UA11

Siemens 6ES5 942-7UA11 – S5-115U CPU 942 Processor Module

Siemens 6ES5 942-7UA11 is a SIMATIC S5-115U CPU 942 processor module with 10 KB of internal RAM and one TTY serial interface. This Siemens automation processor executes the Siemens S5 PLC program and manages data exchange with peripheral modules in the SIMATIC S5 system. Its front memory slot accepts a suitable memory submodule with a capacity of up to 32 KB.

Typical duties include machine sequencing, interlocks, timing and process control. Sensor signals are handled through digital input modules, control signals through digital output modules, and measurement or reference values through analog modules. The CPU has no onboard field I/O channels; field voltage, signal type and output ratings depend on the installed I/O modules.

Memory and program retention

The 10 KB internal RAM and the 32 KB memory-slot limit are separate specifications. Siemens' CPU 942 A-family comparison specifies a maximum total program memory of 42 KB with a suitable memory configuration. RAM, EPROM and EEPROM have different loading and retention behaviour; select an S5 memory submodule against the CPU revision and the program requirements.

When considering EPROM models such as 6ES5 375-0LA21 and 6ES5 375-0LA41, compare the complete order number and the manufacturer's memory table as well as capacity. A 32 KB slot rating does not establish compatibility with every 32 KB module. RAM retention during a power interruption also depends on the system's backup battery and retention arrangement.

TTY connection and programming

The CPU 942's 15-pin TTY connection uses a 20 mA current loop. With the appropriate equipment, it supports a PG programmer, an OP operator panel or a SINEC L1 slave connection. When choosing S5 cables and connectors, check the pin assignment, active/passive current-loop arrangement and converter specifications. A standard RS-232 cable must not be connected directly to the TTY port.

For servicing with an PG 615 or PG 685, check which functions the selected programmer supports. PC access requires suitable STEP 5 software and an S5 TTY interface. Plan programmer access, panel operation and communication around the CPU's single-port arrangement.

Addressing, timers and rack configuration

Siemens' A-CPU comparison gives CPU 942 digital address ranges of E 0.0–E 127.7 and A 0.0–A 127.7, using German STEP 5 notation, and an analog peripheral word range of PW 128–PW 254. These are CPU address limits; the channels actually available depend on the rack, I/O modules and expansion configuration. The CPU is not assigned an I/O start address in the same way as an input or output module.

The CPU 942 A family provides 128 timers, 128 counters and 2048 flag bits. The timer range is 0.01–9990 seconds; software counters operate over 0–999. Check cyclic, interrupt-driven and time-controlled execution, together with retentive areas, against the installed CPU revision.

Review the S5 rack, the selected CR 700-2 rack model and any S5 interface modules together. Confirm mechanical compatibility, backplane connections and the power-supply budget before approving a replacement configuration.

Differences between similar order numbers

6ES5 941-7UA11, 6ES5 943-7UA11 and the dual-interface 6ES5 943-7UA22 belong to the S5-115U family but differ in memory and connection features. 6ES5 942-7UA12, 6ES5 942-7UA13 and 6ES5 942-7UB11 are also different order numbers from 6ES5 942-7UA11. Compare the operating system, hardware revision, special-function modules and program functions before substitution.

Editor's Note

Start with a clear photograph of the complete label and revision markings. A CPU 942 nameplate is only part of the identification; compare the 7UA11 suffix with the original unit too.

Before removing a working CPU, back up the program and data blocks, and record the fitted memory module. Avoid OR/overall reset until a usable backup is available, because this operation can erase program contents.

If the programmer cannot connect, check the TTY cable, converter and port settings before condemning the CPU. On an older installation, the connection equipment deserves a careful check as well.

If the program disappears after power is removed, inspect the battery connection, battery condition and memory type together. Successful powered operation does not prove that RAM contents survive a power interruption.

A RUN indicator is a useful first check, but also assess program upload, controlled RUN/STOP operation, fault indicators and I/O response under safe test conditions. The Siemens S5 maintenance information provides background; judge a used unit by its own test record.

OtomasyonAVM resources

6ES5 942-7UA11 main page · Used Siemens S5 models · S5-115U PDF files and manuals

Related topics

CPU 941-7UA11 · CPU 942-7UA13 · CPU 943-7UA11 · CPU 943-7UA22

These links support comparison and do not establish direct interchangeability.

Navigation

Siemens · Siemens S5 · SIMATIC S5 models · Memory submodules · Racks and connections

External references

Siemens – 6ES5 942-7UA11 product record
Siemens S5-115U A-CPU manual – German PDF