6ES5 941-7UB11
Siemens 6ES5 941-7UB11 CPU 941B — S5-115U, 2 KB RAM
Siemens 6ES5 941-7UB11 is the CPU 941B central processing unit for the S5-115U, with 2 KB of internal RAM and one TTY programming connection. It executes the STEP 5 program in a SIMATIC S5 system. Distinguish this S5 CPU’s internal RAM from the total capacity available with a memory submodule.
941-7UA11 is an A-series model; 942-7UB11 and 943-7UB11 are different CPU options. Physical resemblance or a generic “S5-115U CPU” description is insufficient for spare selection. Compare the complete order code, program requirements and fitted memory equipment together.
2 KB internal RAM and 18 KB total capacity
The manual specifies 2 KB of internal program memory and up to 18 KB total with a suitable 16 KB memory submodule. This does not mean 18 KB of internal CPU RAM. Identify the submodule type: the 375-1LA21 16 KB EPROM and 375-0LD21 16 KB RAM have different operating and retention requirements.
The CPU 941 can execute the program directly from the memory submodule. Data blocks stored in E(E)PROM cannot be changed by the user program. When investigating recipe or operating-value changes, establish whether the relevant blocks reside in RAM or E(E)PROM before attributing an unsuccessful write to a CPU fault.
Supply requirements and power-supply checks
Siemens’ exact-code table specifies consumption of 0.16 A from the internal 5 V rail. Consumption from 24 V is 0.04 A without a programmer and 0.06 A with one connected. Include the rack and additional equipment when assessing total load on the PS 951 power supply; these figures are not mains input currents.
Approximate module weight is 0.8 kg. Inspect connectors, seating and power-supply indicators when checking used equipment. Preserve the program, data blocks and backup status before removing power. Establish RAM retention independently of whether a memory submodule is present.
TTY connection and DB1 parameters
The CPU’s single serial interface serves PG/OP and SINEC L1 applications. Select the PG cable for the TTY electrical interface. A similar connector does not make an ordinary RS-232 cable suitable. Photograph the installed communication arrangement and connected device before disconnecting anything.
Siemens’ COM DB1 manual lists 6ES5 941-7UB11 from revision A01 among supported CPUs. Back up the existing DB1 first; parameterization support does not add functions absent from the hardware. Keep program and parameter changes separate so their effects remain traceable.
Timers, counters and I/O acceptance testing
The CPU 941 provides 128 timers and 128 counters. Compare program states with field signals when checking digital inputs and digital outputs. Record retention settings and battery condition. Reaching RUN once does not demonstrate that operating values will survive a power interruption.
Record addressing, data format and scaling for analog modules, and the FB versions used by function modules. If a problem appears after CPU replacement, compare the program, memory submodule and peripheral arrangement with the original records.
For an older Siemens S5 system, perform acceptance testing with a known working rack, power supply and suitable PG connection. Identify the fitted memory, program read and functions actually checked. Treat visual inspection, program access and an operating test on the system as separate results.
Editor’s note
This CPU has 2 KB of internal RAM. If an offer says “18 KB”, ask which memory submodule is included. Quoting expanded system capacity for a bare CPU can leave the replacement unable to hold the intended program.
If a recipe value will not change, check the block location first. On the CPU 941, the user program cannot write to a data block stored in E(E)PROM. Establish which value the application is trying to change before condemning the module.
Back up a system showing a battery warning before shutting it down. An EPROM does not establish protection of current operating data in RAM. Record the memory code and preserve current data blocks separately.
For a failed PG connection, try a suitable TTY converter and a known working cable. Also inspect bent contacts and connector condition before setting aside an otherwise working CPU.
Ask for photographs of the CPU label and memory receptacle. The offer should identify included memory and the rack used to read the program. A useful test description explains what “working” actually covers.
OtomasyonAVM resources and PDFs
+ 6ES5 941-7UB11 product and information page, S5 CPU series pages and Siemens S5 models.
+ OtomasyonAVM SIMATIC S5 PDF archive. Use the English S5-115U manual explicitly covering 941-7UB11 for this order code.
Related topics
+ 375-1LA21 EPROM, 375-0LD21 RAM, CPU 942-7UB11, CPU 943-7UB11 and S5 programming cables.
Browse SIMATIC S5
S5 CPU | SIMATIC S5 | S5 memory submodules | Siemens second-hand homepage
Siemens and external references
+ Siemens 6ES5941-7UB11 data sheet, 30 June 2020, German — third-party archive copy: exact code, CPU 941, S5-115U and 2 KB RAM.
+ Siemens S5-115U Manual, 6ES5 998-0UF23, Edition 04, English — printed page 15-14 / PDF page 542: exact-code technical table; section 2.7.2 / PDF page 58: memory submodules; section 4.2.2 / PDF pages 117–119: program transfer and data blocks.
+ Siemens COM DB1 Parameterization Software Manual, EWA 4NEB 812 6113-02b, English — section 1.2, table 1-1, printed page 1-4 / PDF page 15: exact CPU code and revision A01 requirement.