6ES5 927-3SA11

Siemens 6ES5 927-3SA11 – S5-150S / S5-150U Central Processor Board 927

Siemens 6ES5 927-3SA11 is the 927 board used in the SIMATIC S5-150S and S5-150U central processor assembly. The Siemens spare-parts list identifies it as central board 4. When sourcing parts for Siemens S5 and SIMATIC S5 systems, check the complete 3SA11 code alongside the installed assembly.

The other central boards are listed as 6ES5 924-3SA11, 6ES5 925-3SA11 and 6ES5 926-3SA11. Record their labels and revisions as part of the maintenance file. Assessment of an individual board requires knowledge of the central controller and connections in which it operates.

Br. 1 Jumper and Timer Updating

The manufacturer’s jumper table states that timers are updated with Br. 1 fitted and are not updated with Br. 1 open. Check this setting when investigating timing behavior. Photograph the installed jumper position and compare it with the application records before replacing the board.

Keep the jumper functions of nearby boards such as 6ES5 926-3SA12 distinct from those of the 927. Other suffixes, including 6ES5 927-3KA13, 6ES5 927-5BA12 and 6ES5 927-5BA13, require separate assessment when sourcing a spare. Verify wiring and jumper settings against documentation for the complete order number.

S5-150S and S5-150U Rack Positions

The manufacturer’s S5-150S layout shows 927-3SA11 in position 75. The S5-150U manual places boards 924/925/926/927 in positions 35/43/51/59, respectively. Check the installed S5 rack and chassis and S5 power supply against the layout drawing for the actual central controller.

When assessing the bus arrangement, also record the position of the 6ES5 756-0AA11 jumpering and routing board and installed S5 memory modules. Documenting module positions, jumpers and memory together makes removal and reinstallation easier to control.

Programmer Connection and System Checks

Assess programmer access through the central controller’s PG connection arrangement. When reviewing S5 cables and connectors, S5 interface modules and S5 communication modules, document the roles of the processor boards and external connections separately. Inspect rear connectors for corrosion, bent contacts and locking problems.

Back up the STEP 5 program and system data before PLC programming or debugging. Investigate timer-related faults by checking program conditions, the Br. 1 position and system operating state together. See the Siemens S5 PLC overview for background on the legacy system.

Editor’s Note

Read the complete 3SA11 label before selecting a spare. Record the order numbers of the other three central boards as well.

If timers stop progressing, check the Br. 1 position before changing the program. Compare the jumper table with the installed application and photograph the existing arrangement before removal.

Use the layout for the actual rack. The documented 150S and 150U positions differ, so verify the housing label and its drawings.

Bench inspection of one board cannot establish the health of the complete processor assembly. Where possible, assess it in a suitable central controller using the application’s timing functions.

Preserve the program, memory arrangement and details of the fault before replacing hardware. A poor connector or supply problem can otherwise lead to unnecessary board replacement.

Documentation and PDF Archive

Browse further S5 documents in our S5-115 PDF archive. Consult the manufacturer references below for S5-150S and S5-150U layouts and the board’s jumper functions.

Related Topics and Nearby References

6ES5 924-3SA11 · 6ES5 925-3SA11 · 6ES5 926-3SA11 · 6ES5 927-3KA13. These links support comparison of assembly components and different references; they do not establish direct interchangeability.

Siemens S5 Navigation

Used Siemens products · Siemens S5 main page · S5 function modules · Racks and chassis · Memory modules · Interface modules

External References

Siemens Zentralgerät 150 S – C79000-B8500-C246-3, German: §1.2.1 layout; §3.2.3 Br. 1 function; §4.4 exact central-board order numbers.

Siemens S5-150U Handbuch, German: B85346/3, §1.2 / PDF 15 layout; §3.3.1 / PDF 37–38 jumpers; PDF 47 spare-parts list.