Siemens 6ES5 926-3SA11 – S5-150S / S5-150U Central Processor Board

Siemens 6ES5 926-3SA11 is the 926 central board used in the processor assembly of S5-150S and S5-150U central controllers in the SIMATIC S5 family. Siemens lists it as Zentralbaugruppe 3, or central module 3. Its front panel carries BETRIEB, STOP and NEUSTART ERFORDERLICH indicators, a BETR./STOP selector and a WIEDERANLAUF pushbutton. In the S5-150U arrangement, its fixed location is slot 51.

In this Siemens S5 PLC architecture, the central processor consists of 6ES5 924-3SA11, 6ES5 925-3SA11, 926 and 6ES5 927-3SA11 boards. The 926 is therefore a component of the processor assembly rather than a complete standalone PLC containing all processing and user-memory functions. Replacement requires assessing the four boards, memory arrangement and central rack together.

Installation, supply and memory arrangement

The S5-150U manual assigns the 924/925/926/927 boards to slots 35/43/51/59, respectively. Preserve this fixed order when examining an S5-150U central controller; do not automatically apply these slot numbers to S5-150S. The internal system supply is 5 V ±5%. The mains or 24 V input rating on an S5 power supply must not be treated as a voltage to apply directly to the 926 board.

User-program storage must be assessed through the system's separate memory boards, such as the 340/350, and their suitable submodules. When selecting S5 memory modules, check capacity, RAM/EPROM type and address jumpers. Arrangements using external memory also require checking the 341 external-memory interface. The complete system's memory capacity must not be presented as onboard program memory belonging to the 926.

Operating indicators and restart behaviour

Green BETRIEB indicates cyclic program execution; red STOP indicates the stop loop; yellow NEUSTART ERFORDERLICH indicates that a fresh start is required. The BETR./STOP selector and WIEDERANLAUF pushbutton are associated with different startup behaviours. Check the application data and process conditions before operating these controls.

In STOP, the BASP signal inhibits peripheral output commands. Investigate digital input, digital output and analog module conditions through the appropriate expansion and interface arrangement. Slots reserved for the central processor are not general-purpose I/O positions.

Programming access, jumpers and model differences

PG access uses a separate 6ES5 511-5AA12 programming interface. The S5-150U manual specifies 20 mA passive current-loop communication at 9600 baud for this interface; these specifications do not establish an independent RS232 or Ethernet port on the 926. Match S5 cables and connectors and interface modules by their complete codes and the installed rack configuration.

The 926 board's A-B-C jumpers select a periodic interrupt setting of 10 ms, 100 ms or no periodic interrupt. Other jumpers can affect diagnostic and test behaviour. Do not assume automatic interchangeability with 6ES5 926-3SA12. 6ES5 926-3KA12 belongs to S5-150K, while 6ES5 926-5AA12 belongs to S5-150A; sharing the number 926 does not establish the same system compatibility.

Editor's Note

When buying used Siemens equipment, look beyond a description saying “926 CPU.” Ask for the 3SA11 order code, board revision and clear front-panel photographs. Record the neighbouring 924, 925 and 927 boards too; this makes identification much more reliable.

Photograph the original jumper positions before removing the board. A different A-B-C periodic-interrupt setting on the replacement can change program behaviour. Moving jumpers at random is a poor way to investigate a fault.

Back up the program and memory boards separately. Replacing a processor board does not resolve memory data loss; check the RAM backup supply and battery condition as well. A healthy 926 cannot automatically recover a missing user program.

If the yellow NEUSTART ERFORDERLICH indicator is lit, record the PG diagnostics and the machine's last operating state first. Do not press WIEDERANLAUF out of habit; a fresh start and a restart may have different consequences for the process.

Arrange testing in a suitable, known-good central rack. Check the 5 V supply, fans, connectors and other processor boards together. Illuminated LEDs alone are insufficient: confirm program access and stable cyclic execution. Remove or insert the board with power switched off.

OtomasyonAVM resources and PDFs

See About Siemens S5 PLC for the general architecture and our S5 PDF files section for available documents. Technical checks for this model use the C79000-B8500-C346-04 central-controller section in the Siemens AG S5-150U Handbuch, 6ES5 998-0AL11, Edition 11, together with the ST 53 / 1985 ordering tables. These documents are in German.

Related topics

924-3SA11 central board · 925-3SA11 central board · 927-3SA11 central board · 511-5AA12 PG interface. These links describe the processor assembly and connection arrangement; the listed components are not substitutes for the 926.

Browse SIMATIC S5: 6ES5 926-3SA11 main page · S5-150U central controller · SIMATIC S5 · Siemens S5 PLC · Used Siemens models.