6ES5 900-7AD11

Siemens 6ES5 900-7AD11 – SIMATIC S5-110A CPU 900

Siemens 6ES5 900-7AD11 is the CPU 900 central processor module for SIMATIC S5-110A. Its CMOS bit processor provides program addressing for up to 4092 statements and an execution time of 20 µs per statement. When maintaining Siemens, Siemens S5 and SIMATIC S5 equipment, check the complete order number alongside the installed program memory.

910 EPROM Program Memory

The program is stored in a 910 EPROM memory submodule fitted to the CPU. The manufacturer specifies 1020 statements for 910-0AA21, 2044 for 910-0AA31 and 4092 for 910-0AA41. Preserve the label and contents of the installed S5 memory submodule and identify the memory required when selecting a spare CPU.

R/NR Selection and Retentive Flags

The CPU contains 511 F flag bits and 384 non-retentive free Q bits. The R setting retains the F area with a suitable NiCd backup battery; NR resets the F area during initialization. Selecting R does not keep the physical outputs energized. Check the S5 power supply, battery and selector position together.

The manual specifies CPU consumption of 120 mA including the memory submodule and power losses below 1 W. Inspect the S5-110A internal 5 V supply arrangement and rear connector contacts. Consider the 300 ms scan-time monitor when investigating program execution problems.

Rack Coding and I/O Addresses

Verify the installed S5 rack and chassis coding against the drawings for mounting arrangements such as 6ES5 710-0SA11 and 6ES5 710-0SA41. Compare program addresses for the digital input modules and digital output modules with their physical positions. Photograph the module order and bus connections before dismantling.

Programming and Test Connection

The S5-110A manual lists the 6ES5 500-7AA12 programmer interface for online program testing. This arrangement uses a parallel interface. When selecting S5 interface modules and S5 cables/connectors, verify the programmer type and wiring diagram. The 6ES5 330-7AB11 test module supports single-step and program-section examination with the appropriate connections.

Nearby CPU References and Maintenance Records

6ES5 900-7AB11, 6ES5 900-7AB21 and 6ES5 900-7AC21 are separate order numbers. Compare memory compatibility, R/NR functionality and hardware revision before replacement. During PLC programming and debugging, preserve the EPROM backup, selector positions and observed fault symptoms. Consult the Siemens S5 PLC overview for further system background.

Editor’s Note

Identify the 910 EPROM submodule first. Establish whether it is supplied with the CPU and which program it contains. Preserve a backup before using the machine’s only EPROM for testing.

Photograph the installed R/NR setting. If the machine loses its sequence state after power-off, assess the battery and use of F flags together; R alone does not establish healthy backup.

Inspect an old NiCd battery for leakage, corrosion and board damage. The EPROM program and battery-backed operating information serve different purposes.

A red STOP indication does not identify the CPU as the failed component. Check supply dips, a weak battery in R mode and scan-time monitoring. Record whether the fault occurs at power-up or during operation.

Remember the 500 parallel programmer interface arrangement. Verify the cable, memory label and test connections together before attempting programmer access.

Documentation and PDF Archive

Browse further S5 documents in our S5-115 PDF archive. For CPU 900, consult the relevant sections of the manufacturer’s S5-110A manual below.

Related Topics and Nearby References

6ES5 900-7AB11 · 6ES5 900-7AB21 · 6ES5 900-7AC21 · 6ES5 500-7AA12 · 6ES5 330-7AB11. The CPU versions, programmer interface and test module have different roles; these links do not establish direct interchangeability.

Siemens S5 Navigation

Used Siemens products · Siemens S5 main page · S5 function modules · Memory cards · Racks and chassis · Cables and connectors

External References

Siemens SIMATIC S5-110A Operating Instructions – GWA 4NEB 807 0690-02, English manufacturer document: §1.3.2 CPU and R/NR functions; §1.3.3 memory; §1.3.9–1.3.10 programming/testing; §1.4 technical table, printed page 1.11; §6 spare parts.