invt DA200 servo fault codes 5
INVT DA200 Servo Fault Codes 5
This section covers INVT DA200 servo drive faults related to external fault inputs, emergency stop inputs, RS485 communication, DSP software, digital and analog input assignments, pulse input frequency, main-circuit voltage and control-circuit undervoltage.
When one of these faults occurs, check the related input signals, communication wiring, parameter assignments and supply voltages before repeatedly resetting the servo drive.
Er10-3 - External Input Fault
Cause:
A digital input terminal assigned to the external fault input function has become active.
Solution:
Check why the external fault input is active and remove the fault condition. Activate the fault-reset function and, if necessary, power the servo drive off and on again.
Er10-4 - Emergency Stop Fault
Cause:
A digital input assigned to the emergency-stop function has become active.
Solution:
Check the emergency-stop input, pushbutton and related wiring. Remove the emergency-stop condition, perform the fault-reset procedure and, if required, restart the servo drive.
Er10-5 - RS485 Communication Fault
Cause:
Strong electromagnetic interference (EMI) on the RS485 communication circuit may cause serial communication errors in the servo drive.
Solution:
Use twisted, shielded pair cable for RS485 communication. Route communication cables separately from servo motor and other power cables to reduce electrical interference.
Er11-0 - Motor Control Task Reentry
Possible causes:
The CPU load may be too high or an error may exist in the DSP software.
Solution:
Reduce unnecessary software functions to lower CPU load. If the fault remains, obtain technical support for the DSP software or servo-drive firmware.
Er11-1 - Loop Task Reentry
Cause:
A cyclic software task may have been entered again incorrectly or repeatedly.
Solution:
Reduce unnecessary software functions and lower the processor load. If the fault continues, the DSP software may require inspection or replacement.
Er11-2 - Forbidden Operation Fault
Cause:
The DSP software may be attempting an operation that is not permitted.
Solution:
Check the software and operating conditions. If the fault is related to the DSP software, obtain technical support.
Er12-0 - Duplicate Digital Input Assignment
Cause:
Two or more digital input terminals may have been assigned to the same function.
Solution:
Check parameters P3.00–P3.09. Remove duplicate assignments and make sure each digital input is assigned to the required function only once.
Er12-1 - Duplicate Analog Input Assignment
Cause:
In the standard drive configuration, analog input 3 may already be assigned to the speed command, causing a conflict with another analog-input function.
Solution:
Check P3.70 and select another suitable value to remove the duplicate analog-input assignment.
Er12-2 - Pulse Input Frequency Too High
Possible causes:
The pulse input frequency detected by the drive may exceed the permitted value. The drive's internal pulse-frequency detection circuit may also be faulty.
Solution:
Reduce the external pulse input frequency and make sure the signal remains within the range accepted by the drive. If the external signal is normal and the fault remains, the internal input circuit may require inspection or the drive may need replacement.
Er13-0 - Main Circuit Overvoltage Fault
Possible causes:
The main-circuit DC voltage may be above the permitted level. The mains input voltage may be too high. The braking resistor or braking circuit may be missing, incorrectly connected or faulty. The DEC deceleration time may be too short. The internal DC-voltage detection circuit may also be faulty.
Solution:
Measure the mains input voltage and confirm that it is within the permitted range. Check the braking resistor and braking-circuit connections. Increase the DEC time to reduce regenerative overvoltage.
With the drive disabled, monitor R0.07. If the displayed DC voltage does not correspond with the actual mains and DC-bus conditions, the internal voltage-detection circuit may be faulty and the drive should be inspected.
Er13-1 - Main Circuit Undervoltage Fault
Possible causes:
The main-circuit DC voltage may be below the permitted level. Mains voltage may be too low, the buffer relay may not have activated, or the drive power demand may be too high for the available supply. The internal DC-voltage detection circuit may also be faulty.
Solution:
Check the mains input voltage. Power the drive on again and listen for the buffer relay operating.
With the drive disabled, monitor R0.07. If the displayed value does not correspond with the actual supply and DC-bus conditions, the voltage-detection circuit may require inspection or the drive may need replacement.
Er14-0 - Control Circuit Undervoltage Fault
Possible causes:
The DC voltage of the control circuit may be below the permitted level. The mains supply may be too low or the internal control-power DC-voltage detection circuit may be faulty.
Solution:
Check the mains input voltage. With the drive disabled, monitor R0.08. If the displayed control-circuit voltage does not correspond with the actual supply conditions, inspect or replace the servo drive.