invt DA200 servo fault codes 3
INVT DA200 Servo Fault Codes 3
This section covers INVT DA200 servo drive faults related to encoder temperature, encoder EEPROM data, current sensing, system initialization, motor model selection and software limit settings.
When one of these faults occurs, do not rely only on resetting the drive. Check the relevant wiring and parameter settings. For encoder EEPROM and motor-model faults, parameters such as P0.00, P4.97 and P4.98 are especially important.
Er02-a - Encoder Overtemperature Fault
Possible cause:
The temperature of the feedback encoder has exceeded the configured overtemperature protection level.
Checks and solutions:
Check the configured overtemperature protection value and make sure the temperature limit is appropriate. Stop the motor and allow the encoder temperature to return to its normal operating range.
Er02-b - Encoder EEPROM Write Error
Possible cause:
When a motor with a communication encoder is used, a transmission or data verification error may occur while the drive is attempting to write data to the encoder EEPROM.
Checks and solutions:
Check the encoder connection and reduce electrical interference on the communication line. Retry the EEPROM write operation. If the fault continues, the motor or encoder system may require further inspection or replacement.
Er02-c - No Data in Encoder EEPROM
Possible cause:
When power is applied to a motor using a communication encoder, the drive may be unable to read motor data from the encoder EEPROM.
Checks and solutions:
Select the correct motor model using P0.00. Then use P4.97 to attempt writing the required data to the encoder EEPROM.
If required, use P4.98 to block the fault and then perform the necessary initialization using the motor parameters stored in the EEPROM.
Er02-d - Encoder EEPROM Data Check Error
Possible cause:
A data verification error may occur while reading information from the encoder EEPROM after power is applied to a motor with a communication encoder.
Checks and solutions:
Check the encoder connection and reduce communication interference. Select the correct motor model with P0.00 and retry writing data to the EEPROM using P4.97.
Er03-0 - U-Phase Current Sensor Error
Possible causes:
The current sensor or current detection circuit may be faulty. Power may also have been applied while the motor shaft was still moving.
Checks and solutions:
Make sure the motor shaft is completely stationary and power the system on again. If the fault remains, the servo drive may require inspection or replacement.
Er03-1 - V-Phase Current Sensor Error
Possible causes:
The same conditions as the U-phase current sensor fault may apply: a faulty current sensor or detection circuit, or power being applied while the motor shaft is moving.
Checks and solutions:
Ensure the motor is completely stationary and power the system on again. If the fault persists, inspect or replace the servo drive.
Er03-2 - W-Phase Current Sensor Error
Possible causes:
The current sensor or detection circuit may be faulty, or power may have been applied while the motor shaft was still moving.
Checks and solutions:
Power the system on again only after the motor shaft has stopped completely. If the fault continues, the servo drive may require inspection or replacement.
Er04-0 - System Initialization Error
Possible cause:
The servo drive detected an error during its self-check and initialization sequence after power-up.
Checks and solutions:
Power the system on again. If the fault continues after several attempts, the servo drive may need to be inspected or replaced.
Er05-1 - Motor Model Not Found
Possible cause:
The P0.00 motor-model parameter may be set incorrectly.
Checks and solutions:
Select the correct motor model in P0.00. Verify that the motor parameters and motor power rating are compatible with the servo drive power class.
Er05-2 - Motor and Drive Model Mismatch
Possible cause:
The selected servo motor and servo drive models may not be compatible.
Checks and solutions:
Check the full motor and drive model numbers and make sure they are a compatible combination.
Er05-3 - Software Limit Setting Error
Possible cause:
The software limit parameters are set incorrectly. According to the source information, P0.35 must not be less than or equal to P0.36.
Checks and solutions:
Check and adjust P0.35 and P0.36. P0.35 should be set to a value greater than P0.36.
INVT DA200 Fault Code Document
+ INVT DA200 Servo Fault Codes (PDF)