Gd10 user manual

INVT GD10 User Manual and Commissioning Reference
The INVT Goodrive10 (GD10) user manual is the main technical reference for installation, wiring, parameter setup, commissioning and troubleshooting of the drive. It is useful both during initial machine setup and later when a GD10 is being replaced, reconfigured or serviced.
Before changing parameters, confirm the complete GD10 model number and check the motor nameplate data. Rated voltage, current, frequency, power and speed should match the values entered in the drive. Incorrect motor data can affect control performance and protection functions.

What the GD10 Manual Covers
- Mechanical installation and cooling requirements
- Main power and motor wiring
- Control-terminal functions
- Motor nameplate parameters
- Frequency-reference selection
- Acceleration and deceleration settings
- Programmable digital inputs
- Analog input and output configuration
- PID functions
- RS485 / Modbus communication
- Protection functions and fault codes
Download the INVT GD10 User Manual
+ INVT GD10 User Manual (English PDF)
Checks Before First Start
- Verify that the incoming supply matches the voltage class of the GD10.
- Check the U, V and W motor connections.
- Confirm protective grounding.
- Compare the programmed motor data with the motor nameplate.
- Select the correct run-command source.
- Select the required frequency-reference source.
- Check digital and analog input assignments.
- Set acceleration and deceleration times according to the machine.
- Make sure the mechanical system is safe before issuing the first RUN command.
If a GD10 is being installed as a replacement for another drive, do not copy old parameters blindly. Check that the previous settings are still suitable for the connected motor, machine load and control circuit.
Using the Manual for Fault Diagnosis
When the drive trips, record the displayed fault code before resetting it. The GD10 P07 fault-history parameters can provide useful information about the operating condition at the moment of the trip, including frequency, current, DC-bus voltage, temperature and terminal status.
Repeated faults should be investigated together with the motor load, mains supply, wiring and relevant drive parameters rather than cleared repeatedly with STOP/RST.