Gd10 fault codes 2

INVT GD10 Fault Codes 2 - Troubleshooting Guide

This section continues the INVT Goodrive10 (GD10) fault-code guide with the most common current, voltage, overload, temperature, communication and feedback faults. The displayed code should be treated as the starting point of the diagnosis rather than simply cleared with a reset command.

For recurring faults, compare the code with the motor load, supply condition, wiring and the operating data stored in the GD10 fault history before restarting the machine.

OC1 - Overcurrent During Acceleration

Likely causes:
The acceleration time may be too short. Supply voltage may be low, the drive may be undersized for the application, or the motor and mechanical load may require more current than expected. A short circuit, ground fault or abnormal condition in the motor or output wiring can also produce OC1.

Checks:
Increase the ACC time. Check the incoming supply, motor wiring and mechanical load. Confirm that the motor rotates freely and that the GD10 has sufficient current and power capacity for the application. Also investigate strong electrical interference if no power-circuit problem is found.

OC2 - Overcurrent During Deceleration

Likely causes:
The drive may be subjected to abnormal current while the motor is slowing down. Low supply voltage, insufficient drive capacity, sudden load changes, a short circuit or a grounding problem may be involved.

Checks:
Check the incoming power supply, motor wiring and mechanical load. Inspect the output circuit for short circuits or ground faults and confirm that the load is able to decelerate normally.

OC3 - Overcurrent at Constant Speed

Likely causes:
A sudden increase in mechanical load, abnormal motor operation, output phase loss or a wiring problem may cause excessive current while the drive is running at a steady frequency.

Checks:
Inspect the mechanical load and motor current. Check the U, V and W output wiring for phase loss, poor connections or short circuits. External electrical interference should also be considered.

OV1 - Overvoltage During Acceleration

Likely causes:
The incoming voltage may be abnormally high, or the mechanical system may be returning energy to the drive. The motor may already be rotating when the GD10 is started, and some applications may require additional braking capability.

Checks:
Check the mains voltage and the condition of the mechanical load. Review the acceleration and deceleration settings. If the machine produces significant regenerative energy, evaluate the braking arrangement used with the drive.

OV2 - Overvoltage During Deceleration

Likely causes:
Regenerative energy returned by the motor can raise the DC-bus voltage during deceleration. A very short deceleration time can make this condition more severe.

Checks:
Check the incoming voltage and increase the DEC time where appropriate. Inspect the machine for high-inertia or overhauling loads and verify that the braking arrangement is suitable for the application.

OV3 - Overvoltage at Constant Speed

Likely causes:
The supply voltage may be excessive, or the load may be driving the motor and feeding regenerative energy back into the DC bus while operating at constant speed.

Checks:
Measure the incoming supply and examine the mechanical load. Check that any required braking components are functioning correctly.

UV - DC-Bus Undervoltage

Likely cause:
The incoming power-supply voltage has fallen below the level required for normal GD10 operation.

Checks:
Check the mains voltage, input wiring, protective devices and power connections to the drive.

OL1 - Motor Overload

Likely causes:
Supply voltage may be too low. The configured motor rated current may not match the motor nameplate. The motor may also be stalled, overloaded or subjected to sudden changes in mechanical load.

Checks:
Verify the incoming supply and compare the programmed motor rated current with the nameplate value. Check the motor and machine for excessive load, jamming or abnormal torque demand.

OL2 - VFD Overload

Likely causes:
Acceleration may be too fast, the load may be too heavy, the incoming voltage may be low, or the selected drive may not have sufficient capacity. Improper restart of a motor that is still rotating can also contribute to overload conditions.

Checks:
Increase the ACC time, check the mains supply and inspect the mechanical load. Confirm that both the motor and GD10 are correctly sized for the application and review the restart conditions.

OL3 - Electronic Overload

The GD10 can generate an overload pre-alarm according to the configured overload threshold.

Checks:
Check the actual machine load and verify that the overload pre-alarm setting is suitable for the application.

OH1 - Rectifier Module Overtemperature

Likely causes:
The cooling path may be blocked, the cooling fan may be faulty, ambient temperature may be too high, or the drive may have been operating under excessive load for an extended period.

Checks:
Clean the cooling path and inspect the fan. Reduce the ambient temperature where necessary. Check motor current and drive loading, and inspect the main electrical connections. Persistent OH1 faults may require inspection of the power section or control hardware.

OH2 - Inverter Module Overtemperature

Likely causes:
The inverter power stage is overheating because of insufficient cooling, high ambient temperature or sustained high load.

Checks:
Check the cooling fan, ventilation path and panel temperature. Review motor current and machine load and make sure all power connections are secure.

EF - External Fault

Meaning:
A digital input assigned to the external-fault function has been activated.

Checks:
Inspect the external device, sensor, relay or control circuit connected to the fault input and confirm that the digital-input logic is correct.

CE - RS485 Communication Fault

Likely causes:
The baud rate or device address may be incorrect. The RS485 connection may be open, reversed or poorly terminated, or the communication cable may be affected by electromagnetic interference.

Checks:
Verify the baud rate and communication address. Inspect the RS485 wiring and shielding. Where possible, keep communication wiring away from motor and power cables.

EEP - EEPROM Fault

Meaning:
The GD10 has detected a problem while reading or writing parameter data, or the EEPROM memory itself may be faulty.

Checks:
Try resetting the drive with STOP/RST. If EEP returns, the main control board may require technical inspection or replacement.

PIDE - PID Feedback Fault

Meaning:
The PID feedback signal has been lost or the configured feedback source is no longer available.

Checks:
Inspect the PID feedback signal, wiring and the connected sensor or transmitter. Confirm that the feedback source is operating normally.

END - Operating-Time Limit Reached

Meaning:
The accumulated operating time of the GD10 has reached or exceeded the configured running-time limit.

Checks:
Review the relevant operating-time parameter and, where required, consult the supplier or service provider before changing the setting.

LL - Electronic Underload Fault

Meaning:
The drive has detected a load condition below the configured underload threshold.

Checks:
Inspect the mechanical load and verify that the underload pre-alarm setting is appropriate for normal machine operation.

Note: Repeated OC, OV, OL and OH trips should be investigated rather than repeatedly reset. Review the motor, mechanical load, incoming supply, drive capacity, ACC/DEC times, cooling and power wiring together.