Gd20 Fault Codes 3
INVT GD20 Fault Codes 3 - STO and Safety Circuit Faults
This section covers the Safe Torque Off (STO) function and related safety-channel faults on the INVT Goodrive20 (GD20), together with the low-load warning and PoFF power-supply condition.
Important: An STO indication does not automatically mean that the drive has failed. When the STO inputs request the safety function, the GD20 disables torque-producing output as intended. STL1, STL2, STL3 and CrCE, however, indicate abnormal conditions associated with the safety circuit.
STO wiring and safety-channel diagnostics should only be carried out by qualified personnel. Do not bypass, bridge or defeat the STO channels to force the drive to run.
STL1 - Safety Channel H1 Abnormal
Possible cause:
An abnormal condition may exist on the H1 safety channel, or an internal hardware fault may be present in the STO safety circuit.
Checks and corrective actions:
Inspect the H1 STO input, wiring and associated safety switching device. According to the source instructions, replace the STO switching device if necessary. If STL1 remains active, the internal safety circuit should be inspected by the manufacturer or an authorized service provider.
STL2 - Safety Channel H2 Abnormal
Possible cause:
The H2 safety channel may be abnormal, or the internal STO hardware circuit may have developed a fault.
Checks and corrective actions:
Check the H2 STO input, external safety wiring and switching device. Replace the STO switching device if required by the application. If the alarm remains, contact the manufacturer or authorized service.
STL3 - Both Safety Channels Abnormal
Possible cause:
Both H1 and H2 channels may be abnormal at the same time, or a fault may exist in the internal safety hardware.
Checks and corrective actions:
Inspect both STO channels and their external wiring. If the external safety circuit is normal and STL3 remains active, contact the manufacturer or authorized service.
CrCE - Safety Code FLASH CRC Check Fault
Possible cause:
The drive has detected a FLASH CRC check error in the STO safety code.
Corrective action:
This condition is related to the internal safety system. Contact the manufacturer or authorized service rather than attempting to bypass or modify the safety circuit.
LL - Electronic Low-Load Fault
The GD20 can generate a low-load pre-alarm according to the configured detection level.
Checks and corrective actions:
Check the actual mechanical load and confirm that the configured low-load alarm threshold is suitable for the application.
STO - Safe Torque Off
When STO is active, the GD20 enters its safety state and disables motor output torque. In this condition, the STO function itself is operating as intended.
P11.16 and STO Alarm Behaviour
When the hundreds digit of P11.16 is set to 0:
The STO alarm operates as a latched alarm. When both H1 and H2 signals are OFF and the safety function is requested, the GD20 enters safety mode and stops its output.
The STO indication remains active until a valid reset operation is performed. The external run command must then be released and applied again before the drive can accept a new run command.
When the hundreds digit of P11.16 is set to 1:
The STO alarm operates in a non-latching mode. When the H1 and H2 safety signals return to their normal state, the STO indication clears automatically and no separate fault reset is required.
The external run command must still be released and reapplied before the drive resumes operation.
STL1 Safety-Channel Behaviour
STL1 is generated when safety hardware channel 1 is abnormal while the H2 channel remains normal. The GD20 enters safety mode and stops its output.
The STL1 alarm remains latched. A normal reset command alone will not return the drive to operation. The actual H1 safety-channel fault must first be corrected.
STL2 Safety-Channel Behaviour
STL2 is generated when safety hardware channel 2 is abnormal while the H1 channel remains normal. The drive enters safety mode and disables its output.
The STL2 alarm remains latched. Resetting the drive does not by itself restore operation; the H2 safety-channel fault must be found and corrected.
PoFF - System Power Off / Low DC Voltage
Possible cause:
The incoming supply may be switched off, or the DC-bus voltage may have fallen below the level required for normal operation.
Checks and corrective actions:
Check the incoming mains supply, input voltage, fuses, contactor and power connections.