Gd20 Fault Codes 1

INVT GD20 Fault Codes 1

This section covers the first group of INVT Goodrive20 (GD20) drive faults, including IGBT output-stage faults, overcurrent, overvoltage, DC-bus undervoltage and overload conditions.

Before resetting the drive, note the fault code and check the machine condition at the moment of the trip. Motor wiring, mechanical load, mains voltage and acceleration/deceleration settings should be considered together during troubleshooting.

OUt1 - IGBT U-Phase Fault

Possible causes:
Acceleration may be too fast. The IGBT power module may be faulty. Motor or drive power wiring may be loose or incorrectly connected. A ground fault or strong electrical interference from nearby equipment may also cause the trip.

Checks and corrective actions:
Increase the acceleration time. Inspect the power stage and IGBT module. Check the drive-to-motor wiring and grounding. Investigate strong electromagnetic interference from surrounding equipment.

OUt2 - IGBT V-Phase Fault

Possible causes:
Electrical interference may cause incorrect triggering, or a problem may exist in the V-phase output circuit or motor connection.

Checks and corrective actions:
Inspect the drive and motor cables. Check for loose connections and determine whether external equipment is producing strong electrical noise.

OUt3 - IGBT W-Phase Fault

Possible causes:
The W-phase connection may be poor, the motor cable may have a ground fault, or external interference may be affecting the output stage.

Checks and corrective actions:
Inspect the U, V and W output wiring and check the motor cable for a short circuit to ground. Check nearby equipment for possible interference sources.

OC1 - Overcurrent During Acceleration

Possible causes:
Acceleration time may be too short. Mains voltage may be low, or the drive may be undersized for the connected load. Sudden load changes, mechanical jamming, ground faults, phase-to-phase short circuits or output phase loss can also produce excessive current.

Checks and corrective actions:
Increase the acceleration time and check the input supply. Confirm that the GD20 has sufficient current and power capacity for the motor. Inspect the motor, mechanical load and U-V-W wiring for jamming, short circuits or phase loss.

OC2 - Overcurrent During Deceleration

Possible causes:
Deceleration may be too fast for the mechanical system. The drive may be undersized, the load may change abruptly, or a motor/output wiring fault may be present.

Checks and corrective actions:
Increase the deceleration time. Check the incoming supply and inspect the motor and mechanical load for abnormal resistance, jamming or short circuits. Verify the drive output wiring.

OC3 - Overcurrent at Constant Speed

Possible causes:
The mechanical load may increase suddenly during operation. A motor or output-cable problem may be present, strong external interference may exist, or related protection parameters may be incorrectly configured.

Checks and corrective actions:
Check motor current and mechanical load. Inspect the U-V-W connections and reduce external interference. Review the related GD20 protection and control parameters.

OV1 - Overvoltage During Acceleration

Possible causes:
The incoming supply voltage may be too high or abnormal. The motor may already be rotating when the drive is started, or regenerative energy may be returning to the DC bus. The application may also require a braking circuit that has not been installed or configured.

Checks and corrective actions:
Check the mains voltage and motor operating condition. Review the acceleration/deceleration settings and braking requirements. Where required, use the appropriate braking unit and resistor and verify the related function parameters.

OV2 - Overvoltage During Deceleration

Possible causes:
Regenerative energy returned from the motor may be too high. Deceleration time may be too short, or the braking resistor and braking circuit may not have sufficient capacity.

Checks and corrective actions:
Increase the deceleration time. Check the braking circuit and confirm that the braking resistor is suitable for the machine inertia, stopping time and braking duty.

OV3 - Overvoltage at Constant Speed

Possible causes:
Mains voltage may be excessive, or the driven machine may be feeding regenerative energy back into the DC bus. Overvoltage or braking-related parameters may also be incorrectly configured.

Checks and corrective actions:
Check the incoming supply and the behaviour of the mechanical load. Inspect the braking system and verify the relevant drive parameters.

UV - DC Bus Undervoltage

Possible cause:
The mains supply or DC-bus voltage has fallen below the level required for normal GD20 operation.

Checks and corrective actions:
Check the mains voltage, incoming fuses, contactor, power cables and terminal connections.

OL1 - Motor Overload

Possible causes:
Supply voltage may be low. The configured motor rated current may be incorrect. The motor may be overloaded, stalled or subjected to rapid load changes.

Checks and corrective actions:
Check the mains supply. Verify the rated motor current against the motor nameplate. Inspect the mechanical load and review the motor-control and torque settings.

OL2 - VFD Overload

Possible causes:
Acceleration may be too fast. The drive may be attempting to start a motor that is still rotating. Mains voltage may be low, the mechanical load may be too heavy, or the selected drive/motor combination may not match the application.

Checks and corrective actions:
Increase the acceleration time. Avoid restarting a rotating motor unless the appropriate restart function is being used. Check the mains supply and mechanical load. If required, select a drive and motor with sufficient current, power and torque capacity.

OL3 - Electrical Overload

The GD20 generates an overload pre-alarm according to the configured electrical overload threshold.

Checks and corrective actions:
Check the actual motor load and verify that the configured overload pre-alarm level is appropriate for the application.