Gemo DT104A-230VAC-R Temperature Controller
Gemo control products have been sold by our company since 2013.
Gemo DT104A is a 48x48 mm panel temperature controller with Auto-tune PID control. Sensor input is selectable for J, K, T, S and R type thermocouples or Pt100.
Front size: 48x48 mm
Panel cut-out: 45.5x45.5 mm
Supply: 100..240VAC, 50-60Hz
Power consumption: < 8VA
24VDC/AC supply and SSR output versions must be specified when ordering.
Outputs
Control output: Relay, NO + NC, 250VAC, 2A resistive load
Alarm output: Relay, NO only, 250VAC, 2A resistive load
Related switching products can be found in our relay and socket section.
Control Settings
Control mode: ON-OFF, P, PI, PD or PID selectable.
Heating hysteresis (H.Hys): 0 .. 50 °C, or 0.0 .. 5.0 °C with Pt.0 input. When H.Hys is set to 0, PID control is active.
Alarm hysteresis (A.Hys): 1 .. 50 °C, or 0.1 .. 5.0 °C with Pt.0 input.
Control period (Ct): 4 .. 200 sec. A value between 4 and 10 seconds is normally suitable for PID operation.
Proportional band (Pb.C): 1 .. 130 °C
Integral time (Ti): 0 .. 30.0 min.
Derivative time (Td): 0 .. 10.0 min.
If Ti is set to 0, the integral part is disabled and control operates as P or PD. If Td is set to 0, the derivative part is disabled and control operates as P or PI.
Heating / Cooling: Selectable. Cooling uses ON-OFF control only. An ON-delay can also be set for the cooling output.
The controller includes Auto-tune, anti-windup and automatic overshoot reduction in PID mode.
Sensor Inputs and Measuring Ranges
J type thermocouple: -100 .. 600 °C
K type thermocouple: -100 .. 1300 °C
T type thermocouple: -100 .. 400 °C
S type thermocouple: 0 .. 1750 °C
R type thermocouple: 0 .. 1750 °C
Pt100: -100 .. 600 °C
Pt100 (Pt.0): -99.9 .. 600.0 °C
Resolution: 1 °C or 0.1 °C
Accuracy: ±0.3% of full scale
For compatible sensors, see our temperature sensor section or our K type thermocouples.
Pt100 line compensation: 10 Ohm max. with a 3-wire Pt100.
For sensor selection, see our short Pt100 vs Thermocouple comparison.
Sensor Failure
If the sensor is disconnected, the measurement is outside the selected range or the input cannot be measured, the display shows FAIL.
During a FAIL condition the alarm output remains OFF. The control output works according to the P.Err and Ct settings. If P.Err is 0, the OUT output also remains OFF.
Other Specifications
Display: 4-digit PV + 4-digit SV, 7 segment
Offset: -100 .. +100 °C, or -10.0 .. +10.0 °C with Pt.0
Protection: IP20
Operating temperature: 0 .. 50 °C
Storage temperature: -10 .. 60 °C
Altitude: < 2000 m
Weight: < 0.5 kg
Settings are password protected and stored in EEPROM memory when the power is switched off.
When a 2-wire Pt100 is used, terminals 10 and 11 must be bridged for the compensation connection.
Gemo DT104A User Manual (PDF)
Installation
DT104A is intended for permanent panel mounting. Installation and wiring must be carried out by qualified technical personnel with the power disconnected.
Gemo specifies a 1A / 250VAC external fuse for the supply line and a separate 2A / 250VAC fuse for each relay output.
For product or ordering information, use our Gemo contact page or email gemo@otomasyonavm.com.
```Gemo DT104A
- Mağaza: Efes Otomasyon
- Store: Efes Automation
- Brands GEMO
- Product Code: Gemo DT104A-230VAC-R
- Availability: 12
-
51.00USD
- Ex Tax: 51.00USD
Related Products
DESA-44R-A Analog Temperature Controller, 220V
▪︎ DERELL DESA-44R-A >> 220V Power Supply, Relay Output, 48x48 mm Panel Type Temperature Contr..
127.00USD Ex Tax: 127.00USD
DGS-44R-A Advanced Temperature Controller (220V)
— Next-generation temperature compensation with high precision DGS-44R-A >> 220V pow..
130.00USD Ex Tax: 130.00USD
DGS-44T-A – Advanced Serial Type with SSR Output – 220V
— Next-generation temperature compensation with high precision DGS-44T-A >> 220V pow..
135.00USD Ex Tax: 135.00USD
DGS-44R-B Advanced Temperature Controller (24VAC/DC)
— Next-generation temperature compensation with high precision DGS-44R-B >> 24VDC/AC..
201.00USD Ex Tax: 201.00USD