IC694MDL931
IC694MDL931 Isolated Relay Output Module: High-Current Capacity and Flexible Control
The IC694MDL931 is an 8 Amp isolated relay output module that provides four normally-closed (N.C.) and four Form C relay circuits for controlling user-supplied output loads. Each circuit has a switching capacity of 8 Amps. Every relay is isolated from the others, and each relay has its own common power output terminal. This module can control a wide range of devices, including motor starters, solenoids, and indicators. The AC or DC power required to operate the connected field devices must be supplied by the user.
Each output point has a numbered LED to indicate its ON/OFF status. There are no fuses on the module. The red bands on the label signify that the MDL931 is a high-voltage module. This module can be installed in any I/O slot within an RX3i system.
Technical Specifications
Rated Voltage: 24V DC, 120/240V AC, 50/60 Hz (nominal, see table below for exceptions)
Output Voltage Range: 5 to 30V DC, 5 to 250V AC, 50/60 Hz
Outputs per Module: 8 isolated outputs
Isolation:
250 VAC continuous (Field to Backplane and Frame Ground)
1500 VAC for 1 minute (Field to Backplane and Frame Ground)
250 VAC continuous (Point to Point); 1500 VAC for 1 minute
Maximum Load:
8 Amps resistive load per output
Maximum of 20 Amps per module for UL installations
Maximum load depends on ambient temperature
Minimum Load: 10 mA
Inrush Current: 8 Amps (maximum for one cycle)
On/Off Response Time: Maximum 15 ms for both ON and OFF
Output Leakage Current: Maximum 1 mA at 250V AC (at 25°C)
Power Consumption:
6 mA from the 5V bus on the backplane (all outputs ON)
110 mA from the 24V relay bus on the backplane (all outputs ON)
Load Current vs. Temperature
Maximum load current capacity is affected by the ambient temperature. For example:
At 10°C, total load current is 32 Amps
At 35°C, each point can handle 6 Amps
At 45°C, each point can handle 4 Amps
Field Wiring
The terminal connections for the IC694MDL931 module are as follows:
Terminals 1-2: Output 1 and common
Terminals 3-4: Output 2 and common
Terminals 5-6: Output 3 and common
Terminals 7-8: Output 4 and common
Terminals 9-11: Normally-closed Output 5 (N.C.), common, and normally-open Output 5 (N.O.)
Terminals 12-14: Normally-closed Output 6 (N.C.), common, and normally-open Output 6 (N.O.)
Terminals 15-17: Normally-closed Output 7 (N.C.), common, and normally-open Output 7 (N.O.)
Terminals 18-20: Normally-closed Output 8 (N.C.), common, and normally-open Output 8 (N.O.)
Recommendations
The IC694MDL931 module offers a high-current capacity and flexible control solution, capable of handling up to 8 Amps per output. It is ideal for controlling various devices in industrial automation systems, such as motor starters, solenoids, and indicators. The combination of normally-closed (N.C.) and Form C relay circuits provides flexibility for different circuit requirements. This module is a reliable choice for high-voltage applications, offering robust and isolated output control.
>> IC694MDL931 Output modules User manual (pdf)
----------
+ Ge-Fanuc Contact (for Automation Mall)