IC694MDL734

IC694MDL734 DC Positive/Negative Logic Output Module: High Voltage and Flexible Control

The IC694MDL734 is a 125 Volt DC output module with the ability to provide six isolated output points, each with a separate common terminal. This versatile module can be configured for either positive or negative logic. In positive logic mode, the module sources current to loads from the user’s common or positive power bus, while in negative logic mode, it sinks current from the loads to the user’s common or negative power bus. Compatible with a wide range of load devices, such as motor starters, solenoids, and indicators, this module is suitable for various industrial applications. Power to operate the field devices must be supplied by the user, and external fusing is recommended for safety.

For applications requiring more power, two Amp loads can be driven by wiring two outputs in parallel. Individual numbered LEDs display the ON/OFF status of each output point, while the red bands on the label indicate that this is a high-voltage module. There are no built-in fuses, so external fuses should be considered. This module can be installed in any I/O slot of an RX3i system.
Technical Specifications and Performance

    Rated Voltage: 125 Volts DC
    Output Voltage Range: +10.8 to +150 Volts DC
    Number of Outputs: 6 isolated outputs
    Isolation: 250 Volts AC continuous, tested up to 1500 Volts AC
    Output Current: Maximum 1 Amp per point
    Inrush Current Capacity: 15.89 Amps for 10 ms
    Power Consumption: 90 mA (with all outputs on) from the 5-volt bus on the backplane
    Output Voltage Drop: 1 Volt maximum
    Off-State Leakage Current: 1 mA maximum
    On Response Time: 7 ms maximum
    Off Response Time: 5 ms maximum

Wiring Connections

The terminal connections depend on whether you configure the module for positive or negative logic. Here’s the connection breakdown:

    Positive Logic Connection:
        Terminal 1: Output 1
        Terminal 2: Output 1 return (DC+)
        Terminal 3: Output 2
        Terminal 4: Output 2 return (DC+)
        Terminal 7: Output 3
        Terminal 8: Output 3 return (DC+)
        Terminal 9: Output 4
        Terminal 10: Output 4 return (DC+)
        Terminal 13: Output 5
        Terminal 14: Output 5 return (DC+)
        Terminal 15: Output 6
        Terminal 16: Output 6 return (DC+)

    Negative Logic Connection:
        Terminal 1: Output 1 return (DC+)
        Terminal 2: Output 1
        Terminal 3: Output 2 return (DC+)
        Terminal 4: Output 2
        Terminal 7: Output 3 return (DC+)
        Terminal 8: Output 3
        Terminal 9: Output 4 return (DC+)
        Terminal 10: Output 4
        Terminal 13: Output 5 return (DC+)
        Terminal 14: Output 5
        Terminal 15: Output 6 return (DC+)
        Terminal 16: Output 6

Recommendations and Advice

The IC694MDL734 is a highly flexible and reliable module for high-voltage applications, offering both positive and negative logic configurations to suit a wide range of devices. It is suitable for controlling motor starters, solenoids, and other industrial devices requiring 125V DC. External fusing is strongly recommended to ensure safe operation, as the module does not include built-in fuses. For higher current loads, wiring two outputs in parallel can handle up to 2 Amps.

With its isolated outputs, fast response times, and high inrush current capacity, the IC694MDL734 is well-suited for demanding environments where reliable, high-voltage DC control is needed. This module is a strong choice for long-term use in industrial automation systems.


>> IC694MDL734 Output modules User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC694MDL734 Output modules and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."