IC694ALG392

Analog Output Module, Current/Voltage, 8 Channel: IC694ALG392

The IC694ALG392 is an 8-Channel Analog Output module capable of providing single-ended current loop and/or voltage outputs. Each output channel can be configured to operate within one of the following ranges:

   0 to +10 volts (unipolar)
   -10 to +10 volts (bipolar)
   0 to 20 milliamps
   4 to 20 milliamps

Each output converts 15 to 16 bits of binary data to an analog output signal, depending on the range. All eight channels are updated every 12 milliseconds.

In current mode, the module reports an Open Wire fault for each channel to the CPU. It can also retain its last state or reset to zero if system power is interrupted, as long as external power is maintained.

This module is compatible with any I/O slot in the RX3i system.

Power Supply

The module requires 24 VDC power from an external source. If installed in an RX3i Universal Backplane, the power can be connected via the TB1 connector or directly to the module's terminal block. In an Expansion Backplane, the external power source must be connected to the module’s terminal block.

LED Indicators

   Module OK LED: Shows the status of the module.
       ON: Module is OK and configured.
       Flashing: Module is OK but not configured.
       OFF: No power or defective module.
   User Supply LED: Indicates whether the external 24 VDC power is present and above the minimum required level.

Specifications: IC694ALG392

   Number of Output Channels: 1 to 8, selectable, single-ended.
   Output Current Range: 4 to 20 mA and 0 to 20 mA.
   Output Voltage Range: 0 to +10 V and -10 to +10 V.
   Calibration: Factory calibrated to 0.625 μA for 0 to 20 mA, 0.5 μA for 4 to 20 mA, and 0.3125 mV for voltage per count.
   External Supply Voltage: 20 to 30 VDC.
   Update Rate: Approximately 8 milliseconds for all eight channels.
   Resolution:
        4 to 20 mA: 0.5 μA
        0 to 20 mA: 0.625 μA
        0 to 10 V: 0.3125 mV
        -10 to +10 V: 0.3125 mV

Absolute Accuracy:
       Current Mode: ±0.1% FS at 25°C (77°F), ±0.5% FS over operating temperature.
       Voltage Mode: ±0.25% FS at 25°C, ±1.0% FS over operating temperature.

Compliance Voltage: VUSER -3 V to VUSER (maximum).
User Load (Current Mode): 0 to 850 Ω (VUSER = 20 V), 1350 Ω (VUSER = 30 V).
Isolation: 250 VAC continuous, 1500 VAC for 1 minute.
Power Consumption: 110 mA from +5 VDC backplane supply, 315 mA from +24 VDC user supply.

Data Format

Module data is stored in the PLC CPU in 16-bit two's complement format. Each output provides 15 bits of analog output data as an integer value. The bipolar voltage mode provides 16-bit resolution, with the 16th bit being the sign bit.

   4 to 20 mA: 0 corresponds to 4 mA, and 32000 corresponds to 20 mA.
   0 to 20 mA: 0 corresponds to 0 mA, and 32000 corresponds to 20 mA.
   0 to +10 V: 0 corresponds to 0 volts, and 32000 corresponds to 10 volts.
   -10 to +10 V: -32000 corresponds to -10 volts, and 32000 corresponds to +10 volts.

Field Wiring: IC694ALG392

The terminal connections are used to wire the outputs, which can be either current or voltage, but not both simultaneously. Below is the pinout for each connection:

   Terminal   Signal Name   Signal Definition
   1    24VIN    User Supplied +24 VDC Input
   2    V CH 1    Channel 1 Voltage Output
   3    I CH 1    Channel 1 Current Output
   4    V CH 2    Channel 2 Voltage Output
   5    I CH 2    Channel 2 Current Output
   6    V CH 3    Channel 3 Voltage Output
   7    I CH 3    Channel 3 Current Output
   8    V CH 4    Channel 4 Voltage Output
   9    I CH 4    Channel 4 Current Output
   10    V CH 5    Channel 5 Voltage Output
   11    I CH 5    Channel 5 Current Output
   12    V CH 6    Channel 6 Voltage Output
   13    I CH 6    Channel 6 Current Output
   14    V CH 7    Channel 7 Voltage Output
   15    I CH 7    Channel 7 Current Output
   16    V CH 8    Channel 8 Voltage Output
   17    I CH 8    Channel 8 Current Output
   18    V COM    Voltage Common
   19    I COM    Current Common/User +24 VDC Return
   20    GND    Frame Ground Connection for Shield

Configuration Parameters: IC694ALG392

   Active Channels: Specifies the number of channels to be scanned (1 through 8).
   Reference Address for Module Output Data: Starting address for %AQ reference type.
   Reference Address for Channel Status Data: Starting address for %I reference type.
   Stop Mode: Defines whether the module holds the last state or resets to zero when the system goes from Run to Stop mode.
   Output Channel Range: Defines the output range for each channel:
        0 to +10 V
        -10 to +10 V
        4 to 20 mA
        0 to 20 mA

This configuration ensures smooth operation and control of multiple analog outputs in various industrial and automation processes.

>> IC694ALG392 Analog modules User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC694ALG392 Analog modules and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."