IC694ALG223
IC694ALG223 16-Channel Analog Current Input Module
The IC694ALG223 provides 16 single-ended input channels. Each input can be configured using the configuration software for any of the following input ranges:
4 to 20 mA
0 to 20 mA
4 to 20 mA Enhanced
High and low alarm limits are available on all ranges. In the 4 to 20 mA Enhanced range, a low alarm limit can be set to detect input current from 4 mA to 0 mA, providing open-wire fault detection for 4-20 mA applications.
The module also reports module status and external power supply status to the CPU using the assigned program reference addresses.
This module can be installed in any I/O slot in an RX3i system.
Module Power
This module consumes 120 mA from the 5 VDC bus on the PLC backplane. It also requires 65 mA plus loop current(s) from a user-supplied +24 VDC source.
LED Indicators
MODULE OK LED provides the following status information upon power-up:
ON: Status is OK, module is configured
OFF: No backplane power or software is not running (watchdog timer timed out)
Continuous rapid flashing: Configuration data not received from CPU
Slow flashing, then OFF: Power-up diagnostics failed or encountered a code execution error
User Supply LED indicates that the external 24 VDC power supply is within specifications.
Specifications: ALG223
Number of Channels: 1 to 16 selectable, single-ended
Input Current Ranges: 0 to 20 mA, 4 to 20 mA, and 4 to 20 mA Enhanced (selectable per channel)
Calibration: Factory calibrated:
4 μA per count in the 4 to 20 mA range
5 μA per count in the 0 to 20 mA and 4 to 20 mA Enhanced ranges
Update Rate: 13 milliseconds (all 16 channels)
Resolution:
4 to 20 mA range: 4 μA/bit
0 to 20 mA range: 5 μA/bit
4 to 20 mA Enhanced range: 5 μA/bit
Accuracy: +/-0.25% of full scale @ 25°C; +/-0.5% over the specified operating temperature range
Linearity: < 1 LSB in the 4 to 20 mA range
Isolation (Field to Backplane): 250 VAC continuous; 1500 VAC for 1 minute
Common Mode Voltage: 0 volts (single-ended channels)
Cross-Channel Rejection: > 80 dB from DC to 1 kHz
Input Impedance: 250 Ohms
Low Pass Filter Response: 19 Hz
External Supply Voltage Range: 20 to 30 VDC
Power Consumption:
120 mA from the +5 VDC backplane bus
65 mA from the +24 VDC external power supply (in addition to loop current)
Configuration: ALG223
IC694ALG223 is configured using configuration software. The configurable parameters are as follows:
Active Channels: 1 to 16 – the number of channels to be scanned in sequential order
Reference Address for Input Data: The memory location where input data from the module is stored. Each channel provides 16 bits of analog input data to the PLC CPU.
Reference Address for Status Data: The memory location where status information starts.
Range: 4-20 mA (default), 0-20 mA, or 4-20 mA Enhanced
In the 4-20 mA range, input currents are reported as values from 0 to 32000 units to the CPU.
In the 0-20 mA range, input currents from 0 to 20 mA are reported as values from 0 to 32000 units.
In the 4-20 mA Enhanced range, currents below 4 mA are reported as negative values, with 0 represented as -8000 units.
Alarm Limits: You can assign low and high alarm limits for each channel.
Data Format: ALG223
The module’s 12-bit resolution analog input data is stored in the PLC CPU in 16-bit 2’s complement format.
In the 4 to 20 mA range, 4 mA corresponds to a count of 0 and 20 mA corresponds to a count of 32000.
In the 0 to 20 mA range, 0 mA corresponds to a count of 0 and 20 mA corresponds to a count of 32000.
In the 4 to 20 mA Enhanced range, 0 mA corresponds to a count of -8000, 4 mA to 0, and 20 mA to 32000.
Status Data: ALG223
The module can be configured to return 8, 16, 24, 32, or 40 status bits to the CPU. These status bits provide information such as:
Module OK
Power Supply OK
High and Low Alarm status for each channel
>> IC694ALG223 Analog modules User manual (pdf)
----------