IC694ALG220

IC694ALG220 4-Channel Analog Voltage Input Module: High-Precision Analog Signal Processing

The IC694ALG220 is a 4-channel analog input module that accepts voltage inputs in the range of -10 to +10 volts. Each channel can also be configured to handle 4 to 20 mA inputs by placing a jumper across the input terminals. This module is designed for high-precision signal processing and provides rapid conversion with a speed of 1 millisecond per channel. With all four channels updating within 4 milliseconds, it ensures real-time performance in monitoring and control systems.

This module can be installed in any I/O slot of the RX3i PLC system, offering flexibility in various configurations.

Isolated +24 VDC Power

When the IC694ALG220 module is installed in an RX3i Universal Backplane, an external source of isolated +24 VDC is required to power the module. This external source should be connected through the TB1 connector located on the left side of the backplane.

If the module is installed in an Expansion Backplane, the backplane’s power supply will provide the isolated +24 VDC required for the module’s operation.

LED Indicators

The Module OK LED is illuminated when the module’s power supply is operating correctly, providing a quick and easy status check.

Technical Specifications

   Voltage Range: -10 to +10 volts
   Calibration: Factory calibrated
   Update Rate: 4 milliseconds (all four channels)
   Resolution: 5 mV/20 μA (1 LSB = 5 mV)
   Accuracy:
        Typical: ±10 mV/40 μA over operating temperature
        Maximum: ±30 mV/160 μA over operating temperature
   Linearity: Less than 1 Least Significant Bit (LSB)
   Input Impedance:
        Voltage Mode: >9 Megohms
        Current Mode: 250 Ohms
   Power Consumption:
        27 mA from the +5 VDC bus on the backplane
        98 mA from the isolated +24 VDC backplane bus
   Isolation: 250 VAC continuous; 1500 VAC for 1 minute between field and backplane/frame ground

Data Format

The module stores data in the PLC CPU in a 16-bit 2’s complement format. The scaling for voltage inputs is such that -10 V corresponds to -32000 and +10 V corresponds to +32000, with a resolution of 5 mV per bit. For 4 to 20 mA inputs, the resolution is approximately 10 bits, but this can be increased to 11 bits by using a precision 250 Ohm resistor instead of the jumper, allowing for more accurate readings.

Field Wiring

The following terminal assignments are used for the IC694ALG220 module:

   Terminal    Connection
   1-3    Current mode input jumper for Channel 1
   2-4    Current mode input jumper for Channel 2
   3    Channel 1 (+)
   4    Channel 2 (+)
   5    Channel 1 (-)
   6    Channel 2 (-)
   7    Common
   8    Common
   9    Shield Termination for Channel 1
   10    Shield Termination for Channel 2
   11-13    Current mode input jumper for Channel 3
   12-14    Current mode input jumper for Channel 4
   13    Channel 3 (+)
   14    Channel 4 (+)
   15    Channel 3 (-)
   16    Channel 4 (-)
   17    Common
   18    Common
   19    Shield Termination for Channel 3
   20    Shield Termination for Channel 4

To minimize noise and capacitive loading, use good quality twisted, shielded instrumentation cable for all field connections. Shields can be connected either to the common (COM) or ground (GND) terminals. The COM terminal provides access to the common of the analog circuitry, while the GND terminal connects to the backplane frame ground.

If using the module for 4 to 20 mA inputs, install a 250 Ohm precision resistor in place of the jumper to improve resolution from 10 bits to approximately 11 bits. Additionally, unused inputs should have their + and - terminals tied together to prevent fluctuations in the analog input data for those channels.

Recommendations

The IC694ALG220 analog input module is ideal for applications requiring high-precision voltage or current signal monitoring. Its fast update rate and accurate conversion make it a reliable choice for real-time control systems. For best results in current mode, use the precision resistor method to enhance resolution, especially when dealing with 4 to 20 mA signals. Its isolated design ensures safe and reliable performance in complex industrial environments.

>> IC694ALG220 Analog modules User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC694ALG220 Analog modules and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."