Gd20 fault codes

INVT GD20 Fault Codes and Fault History

This page is the main fault-code reference for INVT Goodrive20 (GD20 / GD20-EU) variable frequency drives. When a trip occurs, the code shown on the keypad should be checked together with the P07 fault history and the operating data captured at the moment of the fault.

Repeatedly resetting the drive without identifying the cause can hide useful diagnostic information. Record the displayed code first, then review the stored frequency, current, DC-bus voltage, temperature and terminal-state information.

Safety: Electrical inspection and maintenance of the GD20 should only be performed by qualified electrical personnel. Read the safety precautions for the drive before working on the VFD or motor circuit.

Alarm and Trip Indication

GD20 faults are indicated by the drive LEDs and keypad display. When the TRIP indicator is active, the displayed code identifies an abnormal condition detected by the inverter.

Resetting a GD20 Fault

After the cause of the fault has been corrected, the GD20 can be reset by pressing the STOP/RST key, using a digital input assigned to fault reset, or by cycling the drive power when appropriate.

The motor should only be restarted after confirming that the original fault condition has been removed.

Recommended GD20 Diagnostic Sequence

1. Check the keypad and keypad connection.
2. Review the stored fault information in the P07 parameter group.
3. Compare the recorded operating data with the actual machine condition at the time of the trip.
4. Identify the corresponding fault code below.
5. Correct the real cause of the fault.
6. Reset and restart the drive only after the abnormal condition has been removed.

P07.27 - Current Fault Type

0 - No fault
1 - OUt1 - IGBT U-phase fault
2 - OUt2 - IGBT V-phase fault
3 - OUt3 - IGBT W-phase fault
4 - OC1 - Overcurrent during acceleration
5 - OC2 - Overcurrent during deceleration
6 - OC3 - Overcurrent at constant speed
7 - OV1 - Overvoltage during acceleration
8 - OV2 - Overvoltage during deceleration
9 - OV3 - Overvoltage at constant speed
10 - UV - Low DC-bus voltage
11 - OL1 - Motor overload
12 - OL2 - Inverter overload
13 - SPI - Input phase loss
14 - SPO - Output phase loss
15 - OH1 - Rectifier module overtemperature
16 - OH2 - Inverter module overtemperature
17 - EF - External fault
18 - CE - RS485 communication fault
19 - ItE - Current-detection fault
20 - tE - Motor auto-tuning fault
21 - EEP - EEPROM operation fault
22 - PIDE - PID feedback offline
23 - bCE - Braking-unit fault
24 - END - Operating-time limit reached
25 - OL3 - Electrical overload
26 - PCE - Keypad communication fault
27 - UPE - Parameter upload error
28 - DNE - Parameter download error
32 - ETH1 - Ground short-circuit fault 1
33 - ETH2 - Ground short-circuit fault 2
34 - dEu - Speed-deviation fault
35 - STo - Incorrect-setting fault
36 - LL - Underload fault
37 - STO - Safe Torque Off
38 - STL1 - Safety channel 1 abnormal
39 - STL2 - Safety channel 2 abnormal
40 - STL3 - Safety channels 1 and 2 abnormal simultaneously
41 - CrCE - Safety-code FLASH CRC check fault

Important: The source lists STo and STO as two different entries. STo refers to an incorrect-setting fault, while STO refers to the Safe Torque Off function. They should not be treated as the same code.

P07.28 - P07.32 Fault History

P07.28 - Last fault
P07.29 - Previous fault
P07.30 - Second previous fault
P07.31 - Third previous fault
P07.32 - Fourth previous fault

These parameters make it possible to see whether the drive has been producing the same fault repeatedly or whether several different faults occurred before the machine stopped.

P07.33 - P07.40 Current-Fault Operating Data

P07.33 - Reference frequency
P07.34 - Ramp reference frequency
P07.35 - Output voltage
P07.36 - Output current
P07.37 - DC-bus voltage
P07.38 - Maximum temperature
P07.39 - Input-terminal status
P07.40 - Output-terminal status

This snapshot can be particularly useful for determining whether a trip occurred during acceleration, under heavy load, at high DC-bus voltage or while a specific digital input or output was active.

P07.41 - P07.48 Previous-Fault Operating Data

P07.41 - Operating frequency
P07.42 - Ramp reference frequency
P07.43 - Output voltage
P07.44 - Output current
P07.45 - DC-bus voltage
P07.46 - Maximum temperature
P07.47 - Input-terminal status
P07.48 - Output-terminal status

P07.49 - P07.56 Earlier-Fault Operating Data

P07.49 - Reference frequency
P07.50 - Ramp reference frequency
P07.51 - Output voltage
P07.52 - Output current
P07.53 - DC-bus voltage
P07.54 - Maximum temperature
P07.55 - Input-terminal status
P07.56 - Output-terminal status

Using these stored values together with the displayed trip code can provide a much clearer picture of what happened before the GD20 stopped.

Related INVT GD20 Resources

+ INVT GD20 Main Page

+ INVT GD20 User Manual

+ INVT General Fault Codes and Troubleshooting

+ INVT User Manuals and Technical Documents

+ INVT Commissioning and Application Notes

+ INVT Contact and Technical Support

+ INVT Main Page


Refine Search