What is a varistor?

What is a varistor?

What is a varistor, and how does it protect a circuit?

A varistor is a nonlinear electronic component whose resistance falls sharply as voltage rises. The most common type is the metal oxide varistor, or MOV. It carries a small leakage current during normal operation. During a voltage surge within its ratings, it conducts more current and limits the voltage peak.

Unlike an ordinary resistor, an MOV does not have an approximately constant resistance across its operating range. Ohm’s law can describe a particular operating point, but one fixed resistance cannot describe its entire voltage-current curve. Whereas NTC and PTC thermistors respond to temperature, a varistor’s primary response is to voltage.

What happens during a surge?

Switching an inductive load through a relay or another switching device can produce a brief voltage spike. A correctly selected MOV is connected in parallel with the circuit being protected. As voltage rises, current through the MOV branch increases. Together with the source and wiring impedance, this reduces the voltage peak reaching the load. Part of the surge energy becomes heat in the MOV.

Depending on the design, an MOV may be connected between line and neutral, line and protective earth, or another suitable pair of nodes. It does not always divert current to earth. The example below shows L–N protection; there is no earth connection in this circuit.

Explore MOV protection in an animated circuit

Adjust the line voltage or press Send surge. The orange dots show the additional current path through the MOV branch.

Selected: 230 V AC
Peak without MOV

325 V

Model peak with MOV

325 V

MOV behaviour

High resistance / small leakage

AC Source F1 L N MOV Parallel MOV branch Load derell · MV01

Continuous voltage is within the example MCOV. Load withstand requires a separate assessment.

The surge is slowed down on screen; the display time is not its actual electrical duration.

This is an educational model, not a component selection calculation or a load safety test. MCOV = 275 V AC and 430 V at 1 mA are example values. Actual clamping voltage depends on current and the component. F1 fuse operation and load current are not modelled.

Show the model calculation

For the positive peak, the model assumes I ≈ 0.001 × (V / 430)25 A and 20 Ω source impedance. The surge button adds 1,000 V to the open-circuit peak. The solution uses Vsource = VMOV + 20 × I. The exponent, source impedance and surge are illustrative; this does not calculate a real component curve, pulse energy, ageing or temperature rise.

MCOV, varistor voltage and clamping voltage are different ratings

MCOV is the maximum continuous operating voltage under the manufacturer’s specified conditions. An AC rating is normally expressed in Vrms. It is not a sharp switching threshold. Varistor voltage is measured at a specified small test current, commonly 1 mA for MOVs. Clamping voltage is the terminal voltage at a specified surge current; both the current and pulse conditions matter.

A 230 V AC sine wave has a peak voltage of approximately 325 V. An MOV rated for 275 V AC continuous operation does not clamp the peak to 275 V. Disc colour and diameter alone do not identify the voltage rating; match the part marking to the manufacturer’s datasheet.

How do MOVs, TVS diodes and fuses differ?

MOVs, TVS diodes and fuses perform different jobs. An MOV or a suitable TVS diode limits voltage surges, while a fuse interrupts excessive current. A thermal disconnect can isolate the MOV branch if the component overheats. A conventional fuse may not open quickly enough in every MOV overheating scenario. These protections must be coordinated using the manufacturer’s requirements.

An MOV is not a rectifier diode; it does not convert AC to DC or DC to AC. Zener and Schottky diodes also have different functions. Nor does it act as a voltage regulator to correct a persistently high mains voltage. Sustained overvoltage can cause overheating, failure and a fire hazard.

Where are MOVs used, and what determines selection?

MOVs appear in power supply inputs, industrial circuit boards and surge protection arrangements. They reduce transient voltage stress on components such as capacitors, MOSFETs and integrated circuits. Equipment containing a transformer may also use them; the circuit design determines their position and rating.

Selection considers the continuous AC/DC voltage rating, clamping voltage, surge current rating, energy rating, repetitive pulse capability and temperature conditions. A joule rating alone is insufficient. The load’s voltage withstand, pulse duration and expected number of surges all matter; choosing a larger disc without checking these conditions is unreliable.

Can a multimeter prove that an MOV is healthy?

Cracks, charring and broken leads are useful clues when checking for damaged components. However, an MOV can degrade without visible damage. After disconnecting power, verifying the circuit is de-energised and safely discharging capacitors, a multimeter can reveal an obvious short circuit. An “OL” or high-resistance reading does not prove that surge protection still works. Checking the voltage-current behaviour requires suitable test equipment.

If an MOV is damaged, investigate the power input fault, associated protection and solder connections, rather than replacing the disc alone. Removing the MOV and continuing to operate the equipment leaves that protection absent. The replacement must meet the electrical and mechanical specifications accepted by the equipment manufacturer.