6ES7 193-0CB10-0XA0

Siemens 6ES7 193-0CB10-0XA0 – ET 200B TB2/DC Screw Terminal Block

Siemens 6ES7 193-0CB10-0XA0 is the TB2/DC terminal block for ET 200B stations in the SIMATIC ET 200 family. Designed for digital electronics blocks, it has three-tier screw terminals and a width of 235 mm. It belongs to the ET 200 terminal block range and is relevant when replacing the field-wiring base of an existing station.

Identify the base and its fitted electronics separately when sourcing a replacement. TB2/DC alone is not a complete I/O station: the electronics block determines the input/output function and channel count. Our guides to PLC operation and the Siemens ET 200 system explain how this arrangement connects field devices to the controller.

Technical Data and Supply Requirements

The nominal supply is 24 V DC, with a permissible range of 18.5–30 V DC including ripple. Siemens lists 100–200 mA for internal logic consumption. Protection is IP20, operating temperature is 0–60 °C, and the listed dimensions are 235 × 130 × 59 mm, in width × height × depth order. The electronics block and PROFIBUS-DP are electrically isolated from each other.

Internal logic consumption is not the current rating of the field outputs. Include sensor and load consumption separately when assessing the power supply. A satisfactory voltage reading at an unloaded DIN rail power supply does not establish that the station receives sufficient voltage when loads operate. Check at the station as well, and compare the supply branch fuse protection with the cabinet drawings.

Examples of Compatible Electronics Blocks

Examples used with TB2/DC include 6ES7 131-0BL00-0XB0 / 32DI, 6ES7 132-0BL01-0XB0 / 32DO, 6ES7 132-0BH11-0XB0 / 16DO-2A and 6ES7 133-0BN01-0XB0 / 24DI/8DO. These combinations illustrate the different I/O arrangements supported by the terminal base.

Describing the base simply as a “32-input module” would therefore be misleading. Read the full order number of the installed digital input or digital output electronics block. A different electronics block that fits the base is not automatically suitable for the existing field wiring or PLC configuration.

How the Three-Tier Wiring Arrangement Works

The terminal tiers accommodate signals, +24 V and the M reference. Use the diagram for the installed electronics to establish each terminal's function. TB2/DC has no fourth tier for individual PE connections, so protective grounding must be provided according to the cabinet design.

Keeping supply and signal connections identifiable helps when servicing a three-wire inductive sensor or photoelectric sensor. However, three-wire construction does not establish PNP/NPN compatibility. Compare the sensor output circuit with the input electronics. The guide to sink/source connections provides useful background for this check.

TB2/DC Compared with TB2-4/DC and TB4/DC

6ES7 193-0CB10-0XA0 / TB2/DC has three-tier screw terminals. 6ES7 193-0CB20-0XA0 / TB2-4/DC uses four-tier screw terminals, while 6ES7 193-0CB30-0XA0 / TB4/DC uses three-tier spring terminals. The small differences in these order numbers identify different connection arrangements.

Compare the complete part number, terminal tiers and existing wiring before selecting an alternative. Screw and spring terminals require different connection procedures. Similar dimensions or appearance are not sufficient evidence that a replacement will suit the installation.

PROFIBUS Addressing and STOP/RUN

The base incorporates station address switches, STOP/RUN, a fuse, a coding slide and the PROFIBUS-DP connection. A new address takes effect after switching from STOP to RUN. The coding slide must match the electronics block class.

If communication does not return after a base replacement, compare the recorded address with the project configuration first. Then investigate the supply, bus connector, cable continuity and network termination. Both the physical PROFIBUS connection and the configured station must be correct; replacing the base does not resolve an incorrect hardware configuration.

Checking Digital Input and Output Faults

When a pushbutton or limit switch operates without a corresponding PLC input change, start at the field device. Compare the contact state, voltage at the terminal, M reference and electronics channel indication. A loose connection and an incorrect program address can produce similar symptoms, so measurements should guide the diagnosis.

For an output fault, a command in the program does not prove that the load is receiving power. Check the load supply, wiring and output electronics limits. If the circuit operates a relay or contactor coil, verify coil voltage, current demand and suitable suppression. These requirements cannot be determined from the terminal base part number.

Installation and Maintenance

The base supports mounting on a suitable standard rail or flat surface. Field wiring can remain on the base during an electronics replacement; replacing the base itself requires the wiring to be recorded beforehand. Select STOP before fitting or removing electronics, and safely isolate the supplies to circuits being worked on.

Arrange field cables and connectors so that they do not pull on the terminals. Follow the manufacturer's conductor preparation and tightening requirements. On a previously used base, inspect screw threads, clamping parts, contact surfaces and the rail latch rather than judging its condition from the housing alone.

Editor's Advice

The most useful replacement record is a clear photograph showing both the terminal base and electronics order numbers. Add the station address and readable cable labels. If several channels fail together, investigate their shared supply and reference connections before replacing the base. For a used unit, inspect terminal grip, contacts and mechanical parts, and confirm whether the electronics block and bus connector are included in the supply scope.

Technical Documentation and PDF Manuals

Visit our Siemens ET 200 PDF manuals page for terminal numbering, electronics combinations and connection diagrams. In the ET 200B manual, use the TB2/DC terminal drawing together with the wiring section for the installed electronics. Do not assume that a terminal number has the same function with every electronics block.

Related Topics

For other station components, browse ET 200 connection modules and ET 200 additional modules. Check each component's series and complete order number separately for compatibility.