6ES7 133-0BH00-0XB0

Siemens 6ES7 133-0BH00-0XB0 – ET 200B Digital Input/Output Module

The 6ES7 133-0BH00-0XB0 is a digital electronics block for the Siemens ET 200B distributed I/O system, part of the ET 200 family. It combines 8 digital inputs and 8 digital outputs, rated at 24 V DC, in one block.

The station exchanges field data with the main PLC over PROFIBUS DP. The machine program runs in the controller; the ET 200B transfers input states and applies output commands. It can be used with a suitable S7-300 or another compatible PROFIBUS DP master.

8 digital inputs

The inputs read on/off signals from suitable 24 V DC sensors, pushbuttons and switches. For example, an inductive sensor can detect a part while the remaining inputs monitor machine positions or operating conditions.

The Siemens manual specifies an input delay of 3 ms for this model. This figure describes the input circuit only. Sensor response, PROFIBUS cycle and PLC program scan also contribute to the machine's overall response. Assess these times together when short pulses must be detected.

Check the sensor voltage, output type and common connection before wiring. The sink and source page provides background; use the actual sensor and terminal-block diagrams for the final connection. Related products can be found under digital input modules and digital I/O modules.

8 digital outputs and load limits

The block provides 8 electronic outputs rated at 24 V DC. The maximum current is 0.5 A per output, while the total current for all outputs is limited to 2 A. Drawing 0.5 A from all eight outputs simultaneously would total 4 A and exceed that limit.

Suitable relay coils, valves or indicator devices may be connected when their electrical requirements are within specification. Check continuous and inrush current as well as the switching requirements of inductive loads. Electronic short-circuit protection does not remove the specified current limits. Other output types are listed under PLC output modules.

Power supply and electrical arrangement

The nominal supply is 24 V DC, with a permitted range of 18.5–30.2 V DC in the Siemens manual. Size the power supply for the electronics block, sensors and connected output loads. See power supplies for the wider product group.

On the terminal block, L3+ supplies the electronics and sensors, while L1+ supplies the output group. Siemens states that L1+ and L3+ are not internally connected. Applying voltage to one terminal therefore does not automatically supply the other. Follow the wiring diagram for the terminal block in use.

The PROFIBUS bus is galvanically isolated from the internal electronics. The inputs and outputs of this model are not individually galvanically isolated from the internal circuits. Take this into account when assessing the common and grounding arrangement.

Terminal block and installation

The 6ES7 133-0BH00-0XB0 is an electronics block and requires a compatible terminal block for field connections. Siemens lists TB1/DC, TB1-4/DC and TB3/DC for this model. Field wiring connects to the terminal block, onto which the electronics block is mounted.

Check terminal coding, existing wiring and the selected block's diagram before choosing a replacement. Protective-earth connections on multi-tier terminal blocks must be assessed according to the manual. Related parts are listed under ET 200 connection modules and ET 200 accessories.

The electronics block and terminal block together measure approximately 160 × 130 × 60 mm. The ET 200B station has an IP20 protection rating and requires an enclosure and installation arrangement suited to the application.

PROFIBUS DP and station address

The ET 200B exchanges data with the master over PROFIBUS DP. Siemens lists rates up to 12 Mbit/s for this model; the 3, 6 and 12 Mbit/s entries are marked in the manual for operation with the IM 308-C. Check the master, cable and connectors for the selected network rate.

The PROFIBUS station number is set on the terminal block. According to the Siemens manual, a changed number becomes valid after a STOP–RUN transition. Assess machine and output states before performing this operation. See ET 200 communication interfaces for other network arrangements.

Comparison with 0BH01 and other ET 200B blocks

The 6ES7 133-0BH01-0XB0 is also an ET 200B block with 8 inputs and 8 outputs. Equal channel counts alone do not establish that the two blocks can be exchanged in every existing project. Check the complete order number, terminal block, station address, master configuration and device description file before replacement.

The 6ES7 133-0BH10-0XB0 is a separate ET 200B model with a hardware output shutdown function. Do not assume that the 0BH00 has that function merely because the blocks look similar or share an 8DI/8DO description.

Indicators and fault checks

The Siemens manual identifies RUN for logic supply, BF for bus faults, DIA for group diagnostics and L1+ for output supply monitoring. Channel LEDs also show the states of inputs and outputs.

If an input is not seen, check the sensor supply, common connection and actual input signal. If an output LED is active but the load does not operate, inspect the L1+ supply, wiring and load current. For a bus fault, check the address, connector, cable, termination and master configuration. Compare the main PLC CPU diagnostics with any message on the operator panel or SCADA system.

Editor's Note: Do not select a spare based only on “8 inputs / 8 outputs”. Check the 0BH00 order code, terminal block and project communication settings together. If the outputs do not operate, check the L1+ supply and the 2 A total load limit before replacing the electronics block.

Manuals and related topics

For terminal wiring, station addressing and technical data, visit the Siemens ET 200 manuals and PDF documents page. For an overview of the family, see about Siemens ET 200.