6ES7 121-1BB00-0AA0
Siemens 6ES7 121-1BB00-0AA0 – ET 200L-SC 2 DI 24 V DC Digital Input Module
The 6ES7 121-1BB00-0AA0 is a two-channel digital input submodule for ET 200L-SC distributed I/O systems in the Siemens ET 200 family. It reads 24 V DC on/off signals from the field and passes their states through the station to the main PLC.
The inputs can monitor pushbuttons, limit switches, relay contacts or suitable sensor outputs. This is an input module: it does not directly drive a contactor, valve or other load. Its job is to bring two separate field status signals into the control system.
Technical specifications
The module has 2 digital inputs, both of which can be used simultaneously. The nominal input voltage is 24 V DC, and the input circuit follows the IEC 61131 Type 1 characteristic. There is no galvanic isolation between the two channels, so the reference and connections of different signal sources must be considered together.
The specified voltage for logic 0 is −3 V to +5 V; for logic 1, it is +13 V to +30 V. A definite 0 or 1 state should not be assumed between +5 V and +13 V. Typical input current at logic 1 is 7 mA.
Typical power loss is 0.4 W. The module measures approximately 10 × 64 × 51 mm, weighs approximately 15 g and occupies one module slot on the terminal block.
Which signals can be connected?
With suitable wiring, the module can read pushbuttons and limit switches as well as compatible 24 V DC switching outputs from inductive sensors and other proximity sensors. A “24 V” label alone does not establish compatibility: check the output type, wiring and input reference as well.
The input detects a positive 24 V signal with the appropriate reference. A PNP output can therefore be used when its electrical characteristics and reference are compatible. An NPN output switches the return path towards 0 V rather than supplying positive voltage to the input. It should not be wired on the assumption that it behaves like a PNP output; a suitable interface may be required. See NPN and PNP sensor outputs for the distinction.
NO and NC describe the normal behaviour of a sensor output or contact, while PNP and NPN describe its electrical output arrangement. A PNP sensor can be either NO or NC. Check the sensor and the PLC project to establish what an input state of 1 or 0 means for the machine.
The Siemens manual also permits suitable two-wire sensors. Their permissible off-state leakage or quiescent current is specified as 1.5 mA maximum. Also check the sensor's on-state voltage drop and wiring to ensure that the input reaches its logic 1 voltage range.
This product is not intended to measure a continuously varying 0–10 V or 4–20 mA process value. Such measurements need a suitable analog input. See analog input versus digital input for the difference.
Terminal block and wiring
The 6ES7 121-1BB00-0AA0 is not a standalone PLC or an independent PROFIBUS station. It is installed on a suitable ET 200L-SC terminal block. The Siemens manual describes the TB 16SC expansion block and the TB 16IM-SC arrangement used with the appropriate IM-SC interface.
Each terminal block provides positions for up to 8 SC submodules. This device has two inputs but occupies only one position. The complete station capacity depends on its interface and any expansion block. The general product groups are listed under ET 200 connection modules and additional modules.
In the Siemens manual's first-slot, or slot A, example, A1 is the channel 0 input, A2 is the channel 1 input, and A3 and A4 are L+ connections. For example, if the L+ signal at A3 is connected to A1 through a suitable dry contact, channel 0 becomes active when the contact closes, provided the station supply and M reference are correct.
These terminal names apply to the first-slot example. For a module in another position, check the appropriate terminal numbers and supply group in the manual for the installed terminal block. A dry contact does not generate voltage; the voltage detected by the input comes from the suitable supply. Safely isolate the relevant supplies before changing wiring.
Input delay and fast pulses
The Siemens ET 200L-SC manual specifies an input delay of 1.2–4.8 ms for both 0-to-1 and 1-to-0 transitions at the nominal input voltage. Sensor response time, station cycle, communication and PLC scan time are additional factors.
In the 2017 Siemens data sheet, the upper limit for the 1-to-0 transition appears with a different unit. For fast or timing-critical applications, confirm the applicable device information with Siemens.
This is a standard digital input module. Do not assume that every very short pulse or fast encoder signal will be registered by the PLC. Where fast counting is needed, assess a counter solution compatible with the installed station. The ET 200L-SC 6ES7 127-1BE00-0AB0 counter module has a different function and is not a direct equivalent of this input module.
Status LEDs and troubleshooting
The module has one green status LED per channel. Siemens specifies no separate alarm or diagnostic function for this submodule. Communication and fault indicators on the station interface must be assessed separately.
If an input does not work, first check the sensor supply and measure the input voltage relative to M. Then inspect the cable, contact or sensor output and channel LED. If the LED state changes but the PLC bit does not, check station communication, module order and the configured input address.
The ET 200L-SC station exchanges data over PROFIBUS through its interface; this small input submodule has no separate PROFIBUS socket. In the main controller, such as a suitable S7-300 system, check the actual input address in the hardware configuration. Compare the PLC bit with the indication on the operator panel or SCADA system.
Distinguishing similar order numbers
6ES7 121-1BB00-0AA0 provides two 24 V DC digital inputs. The 6ES7 122-1BB00-0AA0, by contrast, is a two-channel digital output module. The 6ES7 121-1FA00-0AA0 is a single-channel AC input module for a different voltage range. Similar housings do not make their functions or voltage ratings interchangeable.
Siemens specifies an original packaging unit of 8 modules. This does not mean that one module has eight inputs: each module has two inputs. Check the relevant sales information to establish whether the offered item is a single module or a package.
Editor's Note: The details most easily confused are the input/output function, the sensor's PNP or NPN output and the eight-piece packaging unit. During replacement, check the complete order number, terminal-block position and PLC input address. A lit LED on the sensor alone does not prove that the correct voltage reaches the PLC input; when in doubt, measure at the module terminal relative to M.
Manuals and related topics
For terminal diagrams, module arrangement and technical data, visit Siemens ET 200 manuals and PDF files. For the system overview, see About Siemens ET 200 and ET 200 communication modules.
Related topics: Two-wire sensors · High-speed modules · S7-300 digital input modules