Siemens 6ES7 120-1AH00-0AA0 – SIMATIC SC Single-Row Screw-Type Supplementary Terminal

The 6ES7 120-1AH00-0AA0 is a single-row, 16-position screw-type supplementary terminal for SIMATIC SC / Smart Connect. It is used with TB 16SC and TB 16IM-SC terminal blocks in the Siemens ET 200 family. Its purpose is to organize common-potential connections for field wiring. It is not an electronic module that adds inputs or outputs to the PLC.

16 connection positions with one common potential

The key feature is that all terminals in the row are internally connected. The manufacturer's 16-channel description must not be interpreted as 16 independent signal circuits. Connecting a potential to the row makes it available at the other positions on that same electrical connection.

Separate sensor signals or voltages that must remain isolated cannot be collected on this row. For example, connecting both L+ and M to it would create a short circuit through the internal common connection. When planning power distribution, clearly label the potential assigned to the terminal. The power supply's M reference and the PE protective conductor must not be treated as interchangeable functions.

How it differs from the main terminal block

The TB 16SC terminal block is the main base that accepts SC electronic modules. The 6ES7 120-1AH00-0AA0 adds a terminal row to that base. For example, 6ES7 120-0AH01-0AA0 identifies a screw-type TB 16SC main base; the 1AH00 supplementary terminal cannot replace it.

Compatibility depends on the exact connection block. Within the ET 200 family, TB 16L, TB 32L, TB 16SC and TB 16IM-SC identify different components. Width or a Siemens logo alone is insufficient for spare selection: compare the housing, locking features and complete order number.

Use in field wiring

Siemens describes this supplementary-terminal family as accessories for extending two-wire arrangements to three- or four-wire connections. The single-row version provides one common-potential row. Depending on the application, it can distribute M or connect protective conductors under the conditions specified in the manual. If its assigned potential changes, the labeling must change to match the actual circuit.

For example, a sensor's signal conductor still connects to the appropriate digital input channel, while its supply and common conductors go to the distribution points defined in the circuit. A valve's switched conductor remains connected to the digital output channel. The supplementary terminal helps organize common conductors; it does not replace those signal channels.

The metal shield clamp used with analog input cables is a separate accessory. Shield termination, PE connections and M distribution serve different purposes and must follow the system's grounding and shielding arrangement.

Installation, dimensions and screw connections

The supplementary terminal engages with the grooves underneath the main terminal block and slides back into its locked position. It does not occupy the SC slots used by electronic modules. The manual specifies 115 mm width, 22 mm height and 40 mm installation depth. The 2019 product data sheet gives an approximate weight of 92 g.

The manual's general screw-terminal wiring rules specify 0.14–1.5 mm² conductor cross-sections for standard connections and a 0.4–0.7 Nm tightening torque. Check the additional conditions for conductor type, ferrules and connection function. Loose screws can cause intermittent contact, while excessive torque can damage the screw or terminal housing.

Differences between similar order numbers

6ES7 120-1BH00-0AA0 is the single-row spring-terminal version; 6ES7 120-2AH00-0AA0 has two screw-terminal rows; and 6ES7 120-2BH00-0AA0 has two spring-terminal rows. Row count and connection method are separate selection criteria. Each row of a two-row version is internally common; this does not mean that the two rows are interconnected.

Maintenance and spare selection

This passive component has no separate PROFIBUS address, PROFINET setting or software parameters. Communication belongs to the station's interface. If field devices lose their common supply connection, software checks alone are insufficient. With power isolated, inspect conductor retention, contact surfaces, continuity of the common connection and the plastic locking features.

Editor's Note: Focus first on the internally common row, rather than the number 16. Having multiple screws does not make this a terminal for multiple independent signals. Before reusing a removed part, check that its old labels match the intended circuit and that every screw holds its conductor correctly.