6ES7 153-2BB00-0XB0
Siemens 6ES7 153-2BB00-0XB0 – ET 200M IM 153-2 FO High Feature Interface Module
Siemens 6ES7 153-2BB00-0XB0 is an IM 153-2 FO High Feature interface module used to connect ET 200M stations to an optical PROFIBUS DP network. Within the Siemens ET 200 distributed I/O architecture, it exchanges data between compatible S7-300 modules and the central PLC. The FO designation identifies its fiber-optic communication interface.
This version is particularly relevant when maintaining an existing installation that uses an optical PROFIBUS line. When selecting a replacement, the complete 2BB00-0XB0 suffix matters: the IM 153-2 family includes variants with different interfaces and hardware capabilities.
Station function and module capacity
The interface supports up to 8 compatible S7-300 modules, with an address area of 128 bytes of inputs and 128 bytes of outputs. Station planning must account for the module count, address allocation and backplane current budget together. The 12-module capacity available on certain later IM 153-2 versions does not apply to this order number.
A station can combine suitable digital input modules, digital output modules and compatible analog modules. Field sensors connect to the appropriate I/O cards, while the IM 153-2 FO transfers their data across the network. Support for 4–20 mA or 0–10 V signals depends on the selected analog module.
Optical PROFIBUS connection
The module has two duplex optical sockets. Its optical interface operates at 660 nm and supports a maximum transmission rate of 12 Mbit/s. PROFIBUS station addresses range from 1 to 125, with automatic transmission-rate detection. This version does not provide an electrical RS485 PROFIBUS port.
With suitable SIMATIC NET cables and connectors, the distance between adjacent devices can reach 50 metres with plastic fiber or 300 metres with PCF fiber. These limits apply to individual links, rather than the total network length. Cable type, connector arrangement and the partner device's optical interface must all match. Fiber transmission is useful where electromagnetic interference is a concern; cabinet power and field wiring still require appropriate installation practices.
The two optical connections allow the line to continue between stations. They do not, by themselves, create a redundant ring. When reviewing an existing installation, consider the complete ET 200 communication architecture, including its topology and optical network components.
Redundancy and module replacement during operation
Redundant operation requires two compatible IM 153-2 FO interfaces, a suitable DP master system and an active backplane arrangement. The BM IM/IM 6ES7 195-7HD10-0XA0 active bus module accommodates the two interfaces for this configuration. Hardware and firmware compatibility must be checked against the requirements of the existing project.
Module replacement during operation also requires active bus modules, the appropriate mounting rail and the necessary configuration settings. This capability cannot be assumed for every ET 200M station assembled with standard backplane connectors. The connection modules and rail arrangement should therefore be reviewed alongside the interface itself.
Power supply and mechanical specifications
The rated supply is 24 V DC, with a permitted range of 20.4–28.8 V DC. Maximum current consumption at 24 V DC is 500 mA, and typical power loss is 4.5 W. The backplane supply provides 5 V DC at up to 1 A. When sizing the power supply, assess interface consumption and field-load requirements separately.
Dimensions are 40 × 125 × 117 mm (width × height × depth), approximate weight is 360 g, and the protection rating is IP20. ET 200M installation rules specify ambient temperatures of 0 to +60 °C for horizontal mounting and 0 to +40 °C for vertical mounting. Cabinet planning should coordinate DIN-rail power supplies, ventilation clearances and power distribution.
Configuration, diagnostics and practical checks
Configuration is possible with STEP 7 or engineering tools using the appropriate GSD file. With compatible system components, the High Feature design supports functions including HART communication, FM modules, time stamping and configuration changes in RUN. Each required function should be checked against the CPU, engineering software, firmware and I/O module versions.
The front indicators identify SF group faults, BF PROFIBUS faults, ON supply status and ACT activity in a redundant arrangement. Troubleshooting should combine the LED indications with checks of the station address, project configuration, optical connector cleanliness and fiber continuity. For installation and commissioning details, visit the Siemens ET 200 manuals and PDF documentation section.
Editor's note: A replacement assessment should include the complete order number, firmware version, optical socket arrangement and the station's active bus configuration. Comparing a clear photograph of the existing module label with the STEP 7 hardware configuration helps identify the correct variant.