6ES7 153-2AB03-0XB0

Siemens 6ES7 153-2AB03-0XB0 – ET 200M IM 153-2 FO Fiber-Optic Interface Module

Siemens 6ES7 153-2AB03-0XB0 is an IM 153-2 FO interface module for ET 200M stations within the SIMATIC ET 200 family. Its integrated optical interface provides PROFIBUS DP communication. FO stands for Fiber Optic, identifying the optical connection that distinguishes this version.

Role within an ET 200M station

The interface connects an ET 200M station containing up to eight suitable S7-300 modules to the supervising control system. It is not a standalone CPU executing a user program. Control logic runs in the main PLC, while the interface transfers the station’s field data.

When selecting S7-300 modules, check more than the physical arrangement. Compare the complete order numbers of digital input modules, digital output modules and other components with the existing project. The eight-module limit does not mean eight input or output channels.

Why use an optical connection?

Optical transmission can help protect the data path against electromagnetic interference and provide electrical separation between communicating devices. This can be useful where motors, drives and power cables create a demanding installation environment. Fiber communication does not remove grounding requirements for power supplies and field wiring.

The IM 153-2 FO connection arrangement has two optical channels for linking adjacent devices in a suitable optical line. Two channels do not automatically establish a redundant ring network.

The optical connection carries PROFIBUS. Using fiber does not make this module an Ethernet switch or a PROFINET interface. Assess the transmission medium and communication protocol separately when reviewing the network design.

Fiber cables and connectors

Siemens’ IM 153-2 FO connection arrangement uses Simplex connectors with suitable plug adapters. SIMATIC NET documentation describes plastic and PCF fiber connections for this interface family. Cable selection must account for the optical characteristics of the partner device, connector arrangement and link losses.

A replacement review should cover the optical adapters, connector ends and existing cable condition as well as the module itself. Similar-looking fiber cables may have different core structures or connection requirements.

Do not apply one distance rating to every optical installation. Connections involving different OBT or OLM types require the installation conditions of both devices to be checked. When planning the industrial communication infrastructure, also consider cable routing, intermediate connections and maintenance access.

Redundancy and station configuration

Redundant operation within the IM 153-2 FO family requires two compatible interfaces, a suitable active backplane and an appropriately configured master system. The connection and bus modules form part of that arrangement.

Before replacing an interface in a redundant station, record the order numbers and versions of both units. The shared IM 153-2 name alone is not a sufficient compatibility check. Optical-path redundancy, interface redundancy and power-supply redundancy should be assessed separately in the project.

Power supply and cabinet installation

Plan the ET 200M station’s 24 V DC supply around the interface and connected modules. The system uses an IP20 cabinet installation arrangement. An optical connection does not provide protection for exposed outdoor or wet locations.

Size the power supply with I/O electronics, sensors and output loads accounted for according to their respective supply paths. Select the DIN rail power supply for the complete station.

Leave sufficient space to prevent optical cables from being pinched, sharply bent or disturbed by cabinet covers. Access for visually checking the fiber connection is useful during maintenance, alongside access to the module itself.

Engineering and fault investigation

In STEP 7 or the applicable PROFIBUS configuration tool, check the interface definition, PROFIBUS address, module sequence and GSD compatibility. Do not reuse another IM 153 variant’s configuration entry without reviewing version compatibility.

For communication faults, begin with power status and diagnostic records. Then examine transmitter/receiver orientation, connector cleanliness, cable damage and the partner device’s operating state. If several stations disappear together, investigate the shared section of the communication path before concluding that all interfaces have failed.

Review station faults displayed on an HMI panel or SCADA system alongside the controller’s diagnostic information. Photographing the label, connections and module sequence before replacement helps preserve the existing arrangement.

Manuals and related topics

For optical connections and station arrangements, consult the ET 200M documents available through our Siemens ET 200 manuals and PDF documentation page. When using an IM 153-2 FO section, check the order numbers and product versions covered by that document.

Related topics: About Siemens ET 200 | PROFIBUS FAQ

Editor’s note: Selection should consider the AB03 order number, optical connection hardware and the station’s redundancy arrangement together. Use documentation matching the supplied product version for current consumption, mechanical dimensions and permitted link distances.