6ES7 142-4BF00-0AA0
Siemens Main Menu | SIMATIC S7 | Siemens ET 200 | PDF Manuals
6ES7 142-4BF00-0AA0 - Siemens SIMATIC DP ET 200pro 8 DO Digital Output Module
Series: SIMATIC DP ET 200pro
Product type: Electronic module with 8 digital outputs, 24 V DC / 0.5 A
Order number: 6ES7142-4BF00-0AA0
6ES7 142-4BF00-0AA0 is an eight-channel digital-output electronic module for ET 200pro stations in the Siemens ET 200 distributed I/O family. It switches 24 V DC field loads at up to 0.5 A per channel and is intended for devices such as solenoid valves, DC contactors and indicator lamps controlled by a SIMATIC S7 automation system.
ET 200pro identity and scope of supply
This order number belongs to the ET 200pro family; it is not an ET 200S, ET 200SP or ET 200eco PN module. Products elsewhere in the Siemens ET 200 system architecture may carry the same “8 DO, 24 V DC, 0.5 A” shorthand but use a different housing, backplane interface and accessory arrangement. Use the complete order number when replacing a module.
The bus module is included, while the I/O connection module must be ordered separately. Field wiring cannot be landed directly on the electronic module without the front connection component. For a used unit, confirm whether the offer contains only the electronic module or also the required ET 200pro connection module.
Key technical specifications
Digital outputs: 8, current-sourcing.
Rated load voltage: 24 V DC, 2L+.
Rated output current: 0.5 A per channel.
Total output current: 4 A maximum up to 55 °C.
Process image: 1 output byte maximum.
Short-circuit protection: electronic per channel; typical response threshold 0.7 A.
Lamp load: 5 W maximum per channel.
Load resistance: 48 Ω-4 kΩ.
Switching frequency: 100 Hz with resistive, 0.5 Hz with inductive and 1 Hz with lamp loads.
Cable length: 30 m maximum, shielded or unshielded.
Power loss: typically 2 W.
Dimensions: 45 × 130 × 35 mm, including bus module and excluding connection module.
Weight: approximately 140 g.
Every output has electronic short-circuit protection. On this standard 8 DO version, however, a short circuit is reported at module level; there is no channel-error display. There is one green status LED per channel and one red SF group-error LED for the module. Keep this distinction in mind when comparing ET 200 digital output modules, particularly High Feature variants.
The connection module changes the channel layout
With CM IO 8 × M12 (6ES7194-4CB00-0AA0), CM IO 8 × M12P (6ES7194-4CB10-0AA0) or CM IO 8 × M8 (6ES7194-4EB00-0AA0), each socket carries one output channel. DQ0 through DQ7 appear on X1 through X8 respectively.
With CM IO 4 × M12 (6ES7194-4CA00-0AA0) or CM IO 4 × M12P (6ES7194-4CA10-0AA0), each socket carries two outputs: DQ0-DQ3 on pin 4 and DQ4-DQ7 on pin 2. CM IO 2 × M12 (6ES7194-4FB00-0AA0) groups four outputs in each socket, while CM IO 1 × M23 (6ES7194-4FA00-0AA0) brings all eight outputs to one connector. When designing the ET 200 field connection arrangement, do not infer channel count from connector count alone.
Six field checks for selection and commissioning
1. Calculate channel and total current together. Each of the eight channels is rated at 0.5 A, but the module total is limited to 4 A. Include the behavior of valve and contactor coils, ambient temperature, simultaneity and the current rating of the selected connector. Use a correctly rated interposing relay or contactor for heavier loads.
2. Do not parallel outputs to increase current. The manufacturer does not permit two outputs to be wired in parallel for performance increase. Redundant control of one load is supported, but its wiring and program logic must be engineered for the application.
3. Verify the 2L+ load supply independently. Working channel LEDs or station communication do not prove that output load power is correct. Check 2L+, 2M, voltage drop, protection and potential-group boundaries together with the ET 200 power supply modules and ET 200 power distribution architecture.
4. Allocate one output byte. The module maps its eight outputs to DQ0-DQ7 in one output byte. Match the hardware-configuration start address to the bit addresses used by the PLC program. Verify the station head and network side separately through the ET 200 PROFIBUS and PROFINET interfaces; this electronic module is not a network interface by itself.
5. Interpret SF and channel LEDs correctly. A green LED indicates the commanded output state; it does not prove mechanical actuator movement. The red SF LED points to module-level diagnostics. Use real field feedback such as a contactor auxiliary contact, pressure switch or limit sensor for critical motion.
6. Do not mistake a standard output for a safety output. DQ0-DQ7 may be included in a correctly engineered safety-related group shutdown through 2L+, but 6ES7142-4BF00-0AA0 is not by itself an F-DQ or PROFIsafe module. Targets such as PL d / SIL 2 must not be accepted from the module label alone; assess the ET 200 safety modules, external safe-disconnection circuit and relevant manufacturer instructions as one system.
Used-unit inspection
Check the full order code, 45 mm housing, bus module and presence of the front connection module. Inspect connector threads, sealing surfaces, side bus contacts, every output under 2L+ load, SF diagnostics and all channel LEDs. If the CM IO component is missing, select it separately from the ET 200 supplementary modules and accessories. Sending close photographs of the label and connection module through the Otomasyon AVM Siemens contact page makes the supplied configuration easier to compare.
Editor’s note
The most common mistake with this product is to treat the electronic module and the front connection module as one component. The bus module is included, but the CM IO part providing M12, M8 or M23 field connections is selected separately. The second trap is reading “8 × 0.5 A” as unrestricted 4 A under all conditions. Calculate channel loads, the 4 A total limit, simultaneity and connector current together.
PDF manuals and documentation
Consult ET 200pro Distributed I/O System, 09/2017, A5E00335544-AL and the exact 6ES7142-4BF00-0AA0 data sheet on the Siemens ET 200 PDF manuals page. Section 15.6 covers the module; section 5.11.2 gives the pin assignments for the CM IO options. This page is selection guidance; the device label, installed project, load data and manufacturer manual remain the final authority for wiring and commissioning.
Related topics and Siemens navigation
Digital output modules | Connection modules | Power supply modules