6ES7 141-6BH00-0AB0

Siemens Main Menu  |  SIMATIC S7  |  Siemens ET 200  |  PDF Manuals

6ES7 141-6BH00-0AB0 - Siemens SIMATIC ET 200eco PN 16 DI Digital Input Device

Series: SIMATIC ET 200eco PN
Product type: PROFINET I/O device with 16 digital inputs, 24 V DC, 8 × dual-assigned M12
Order number: 6ES7141-6BH00-0AB0

6ES7 141-6BH00-0AB0 is a field-mounted ET 200eco PN digital-input device in the Siemens ET 200 distributed I/O family. It collects sixteen 24 V DC inputs through eight M12 sockets and transfers them to a SIMATIC S7 automation system over PROFINET IO. It is intended for direct machine-level connection of switches and two-, three- or four-wire proximity sensors.

A complete PROFINET device, not an expansion module

Unlike an ET 200X expansion module, this product has its own PROFINET interface and device identity. It is a complete I/O device, not a card installed behind a separate interface module in the Siemens ET 200 system architecture. Device name, IP address, input address and diagnostic parameters are assigned directly to this unit in the project.

Do not treat 6ES7141-6BH00-0BB0 as an identical drop-in unit. The 0BB0 design uses a narrower housing and M12-L power connectors. The 0AB0 version is 60 mm wide, uses the earlier M12 power arrangement and has a different device configuration. Check mounting, power cabling, device name and project record before substituting solely on the description “16 DI ET 200eco PN.”

Key technical specifications

Digital inputs: 16 in two-channel groups.
I/O connection: 8 × five-pin M12 sockets, dual assigned.
Rated input voltage: 24 V DC.
Supply range: 20.4-28.8 V DC with reverse-polarity protection.
Signal 0: -3 to +5 V.
Signal 1: +11 to +30 V; typical input current 7 mA.
Input characteristic: IEC 61131 Type 3.
Input delay: typically 3 ms for both 0→1 and 1→0.
Simultaneous inputs: all 16 up to 60 °C.
Sensor supplies: 8 outputs, 100 mA maximum per socket, electronically short-circuit protected.
Two-wire sensor: supported; permissible quiescent current 1.5 mA maximum.
Cable length: 30 m maximum, shielded or unshielded.
PROFINET: 100BASE-TX, 100 Mbit/s full duplex, integrated two-port switch.
Power loss: typically 6.5 W.
Degree of protection: IP67.
Dimensions: 60 × 175 × 49 mm.
Weight: approximately 910 g.

The sixteen inputs occupy two input bytes in the process image. If the start address is I0, DI0-DI7 are read in the first byte and DI8-DI15 in the second. When comparing ET 200 digital input modules, do not confuse socket count, channel count and PLC address space.

How sixteen channels fit into eight M12 sockets

Every M12 socket carries two input signals. Pin 4 carries DI0-DI7 and pin 2 carries DI8-DI15: socket X1 contains DI0 and DI8, X2 contains DI1 and DI9, continuing through DI7 and DI15 on X8. Pin 1 is the short-circuit-protected 24 V sensor supply 1US, pin 3 is sensor ground 1M and pin 5 is functional earth FE.

A conventional single-channel M12 sensor cable may use only the lower channel on pin 4. Accessing the second channel on pin 2 requires the correct cable, splitter or sensor wiring arrangement. When selecting ET 200 connection modules and connectors, neither “eight sockets means eight inputs” nor “every cable automatically carries two sensors” is a safe assumption.

Separate PROFINET, power and I/O sockets

PROFINET connects through the P1 and P2 D-coded M12 ports on X01. The integrated switch supports line topology, prioritized startup and media redundancy. Configure device name, IP address and ring settings as part of the ET 200 PROFINET interface and network architecture.

X03 is the supply infeed and X02 is the supply loop-through socket. Their assignment is pin 1 = 1L+, pin 3 = 1M, pin 4 = 2L+, pin 2 = 2M and pin 5 reserved. 1L+ supplies the electronics and sensors. This input device draws no current from 2L+, although the isolated load circuit may be looped through. When designing the ET 200 power supply arrangement and ET 200 power distribution, calculate the 4 A X02/X03 limit and every downstream load.

The power M12 sockets and I/O M12 sockets use the same mechanical coding. A plug fitting physically does not prove that it is connected to the correct port. Verify cable labels, X02/X03 markings and pin assignments before applying power. IP67 cannot be assumed unless every unused connection is closed with the correct protective cap.

Channel diagnostics versus group diagnostics

Wire break is monitored per channel, while a sensor-supply short circuit to M is monitored per channel pair. The groups are 0/8, 1/9, 2/10, 3/11, 4/12, 5/13, 6/14 and 7/15. A sensor-supply fault at one socket may therefore affect the diagnostic state of both channels at that socket.

Group diagnostics, missing 1L+, wire-break and sensor-supply short-circuit diagnostics are disabled by default. Wire break is detected when input current falls below approximately 0.3 mA. On an S7 system, a diagnostic interrupt can call OB82; an absent or incorrectly handled OB82 may cause the IO Controller to enter STOP. Enable diagnostics together with a deliberate PLC fault-handling strategy.

Six field checks for selection and commissioning

1. Confirm the dual-assigned cable arrangement. DI0-DI7 are on pin 4 and DI8-DI15 on pin 2. If the existing installation uses only standard three-wire sensor cables, the upper eight channels may not be physically available.

2. Calculate sensor current per socket. Each 1US supply is limited to 100 mA. Where two sensors share one socket, include both current demands, startup behavior and the paired effect of a supply short circuit.

3. Preserve the 1L+/2L+ separation. Electronics and sensors use 1L+; 2L+ is a separate isolated load circuit. When power is looped through X02, keep total current and conductor size within the connection limits.

4. Read network LEDs as a set. BF indicates a bus fault, P1 LK/P2 LK show physical network links and ON confirms 1L+ power. If SF/MT is red or yellow, read the diagnostic buffer before replacing cables at random.

5. Do not treat an input LED as proof that the sensor is measuring correctly. A green channel LED confirms electrical input state, not sensor alignment or process condition. For critical signals, include a comparison sensor or process feedback in the ET 200 field connection arrangement.

6. Separate standard inputs from safety inputs. This product is not a PROFIsafe F-DI. Emergency-stop, guard-door and light-curtain signals require appropriate ET 200 safety modules and a validated safety architecture.

Used-unit inspection

Confirm the complete 0AB0 code, hardware revision and MAC address on the label. Inspect the eight I/O sockets, two D-coded PROFINET ports, X02/X03 power sockets, seals and housing surface separately. Test P1/P2 link, BF, SF/MT, ON and every green/red channel LED. Missing caps, mounting parts and cable components can be completed from the ET 200 supplementary modules and accessories. Send photographs showing the label and every socket through the Otomasyon AVM Siemens contact page for a more reliable supplied-configuration check.

Editor’s note

Three mistakes repeatedly cause trouble on this device: reading eight M12 sockets as eight inputs, overlooking the second eight channels on pin 2, and confusing a power socket with an I/O socket. A sensor-supply short circuit also affects a channel pair rather than only one channel. On a used device, broken caps and damaged seals are not cosmetic; they directly reduce IP67 protection and field value.

PDF manuals and documentation

Consult ET 200eco PN Operating Instructions, 01/2015, A5E01250250-AH and the exact 6ES7141-6BH00-0AB0 data sheet on the Siemens ET 200 PDF manuals page. Manual section 9.1.3 covers channel and pin assignment, section 9.1.4 covers diagnostic parameters, and section 3.6 covers PROFINET and power sockets. For final commissioning, use the device label, hardware revision, GSD/STEP 7 project and manufacturer manual as the authority.