6ES7 194-4AG00-0AA0
Siemens 6ES7194-4AG00-0AA0 ET 200pro Fiber Optic Connection Module
6ES7194-4AG00-0AA0 is the SIMATIC ET 200pro CM IM PN PP FO connection module used with the IM 154-4 PN HF interface. Within the Siemens industrial automation range, it is identified by two SC RJ fiber optic PROFINET connections and two Push-Pull power connections. It connects station network and supply cables to the interface in Siemens ET 200 distributed I/O systems.
Dimensions are 90 × 130 × 51 mm (width × height × depth). The power connections carry the 1L+ electronics/sensor supply and 2L+ load supply. The data sheet specifies a maximum of 16 A for each supply, subject to temperature derating. In machine and process automation applications, check the limits of the cable, connector and internal station distribution together.
Five checks before selection or maintenance
1. Interface and complete order number: Verify 6ES7194-4AG00-0AA0 on the label and confirm the station uses an IM 154-4 PN HF interface. For PLC based control systems, record the interface and connection module as separate parts. When reviewing ET 200 system architecture and module compatibility, photograph both labels as well as the assembled front face.
2. Supply and current calculation: Calculate the 1L+ and 2L+ loads separately, including current passed to subsequent stations when sizing the supply cable. In SIMATIC S7 control systems, the power supply rating does not determine the permitted current through the connection assembly. Compare cable cross-section, ambient temperature and internal busbar limits with the relevant manufacturer table.
3. Fiber cable and connector surfaces: Siemens specifies a maximum length of 50 m for both IE POF Standard Cable and IE POF Trailing Cable in this connection arrangement. Check the cable route and permitted bend radius before installation. Protect SC RJ ends from contamination; if the link fails, inspect the cable identification and connector condition before concluding that the module is faulty.
4. Line topology and isolated replacement: This fiber arrangement uses a line topology. Removing a fiber connection or losing interface power can also interrupt access to downstream devices. When planning maintenance of Siemens PLC and I/O products, identify the stations affected. Isolate both 1L+ and 2L+ before inserting or removing the connection module or Push-Pull power connectors.
5. Latches, caps and diagnostics: Check that the Push-Pull latches engage fully and fit suitable protective caps to unused sockets. After commissioning, review station diagnostics and any optical link maintenance notifications. Compare HMI operator panel alarm records with the records taken before maintenance. Record the work completed and the cable route inspected.
PDF manuals and connection information
Use the Siemens ET 200 PDF manuals page to access documentation. In ET 200pro distributed I/O system, 09/2015, A5E00335544-AJ, section 4.10 covers wiring and cable rules, while section 11.2.3 gives the module specifications. Consult these sections for pin assignments and temperature dependent current limits. Share label and connection photographs through the Siemens product technical contact page.
Editor's note: The 16 A figure is a conditional infeed current limit, not the module's own consumption. Add “SC RJ fiber optic / Push-Pull power” beside the complete order number in the spare parts record to make the installed connection arrangement easier to identify.