6ES7 194-4AD00-0AA0
Siemens main menu › SIMATIC S7 family › ET 200 › ET 200 manuals
6ES7 194-4AD00-0AA0 — Siemens ET 200pro CM IM DP M12, 7/8″ Connection Module
6ES7 194-4AD00-0AA0 is the ET 200pro CM IM DP M12, 7/8″ connection module in the Siemens SIMATIC product family. It provides PROFIBUS DP and 24 V supply connections for IM154-1 DP and IM154-2 DP interfaces. Within the ET 200 station architecture, it is the connection component fitted to the interface module. List the interface and connection module order numbers separately.
Five checks for selection and commissioning
1. Interface and protocol: When selecting ET 200 communication interfaces, check that this order number is intended for PROFIBUS DP. With ET 200 connection modules, the presence of M12 and 7/8″ connectors alone does not establish compatibility. Do not assume interchangeability with PROFINET connection components; compare the installed IM label with the complete connection module order number.
2. Incoming and outgoing connections: DP1/X03 is the PROFIBUS input and DP2/X04 continues the bus; the M12 connections are B-coded. X01 receives the power supplies and X02 forwards them. Select shielded PROFIBUS cable and suitable connectors together when specifying ET 200 cable and connection accessories. Label cables with station and port numbers in the Siemens S7 network plan to reduce connection errors during maintenance.
3. PROFIBUS address and termination: DIP switches select an address from 1 to 125. It must match the hardware configuration and be unique on the network. A change takes effect after cycling the 1L+ supply. Both ends of the PROFIBUS segment require termination. Enabling this module’s termination in the middle of a segment disconnects subsequent DP stations. Include the address and termination settings in fault checks alongside the cabling.
4. Distinguish the supply limits: The 7/8″ connection carries the 1L+ electronics/sensor supply and 2L+ load supply. In the ET 200 power supply arrangement, each supply has an 8 A feed limit. This does not mean that the entire current can be drawn through the internal busbars: the manual specifies internal limits of 5 A for 1L+ and 10 A for 2L+. When planning ET 200 power distribution, calculate incoming, internal and forwarded loads separately and respect the limit of each section.
5. Installation and maintenance: Dimensions are 60 × 130 × 60 mm; allow additional space for cable bends. Switch off both 1L+ and 2L+ before connecting or disconnecting a 7/8″ connector. Removing a forwarding connection also interrupts power to downstream stations. Include the sensor supplies for ET 200 digital inputs and the load circuits for ET 200 digital outputs in the maintenance plan. Seal unused sockets with suitable M12 and 7/8″ caps.
Editor’s note
Connector shape is only one selection criterion. Check IM compatibility, PROFIBUS address, termination and the two supply circuits together. In particular, an “8 A feed” rating does not mean that 8 A is available at every point. Adding a photograph of the DIP settings to the maintenance record alongside the full order number makes subsequent service work easier.
PDF and technical documentation
Visit the Siemens ET 200 PDF and user manual library for the documentation guide. In the ET 200pro manual, 09/2015, A5E00335544-AJ, printed pages 63–64 cover addressing and termination, pages 88–91 cover wiring, and pages 256–257 describe this module. The Siemens product datasheet also identifies the compatible interfaces and feed-current limits.
Related topics
Terminal bases • Connection modules • Communication interfaces • Other network interfaces • Power distribution • Additional modules
Otomasyon AVM • Siemens guide
Siemens main menu | SIMATIC S7 family | ET 200 module categories | ET 200 PDF archive