6ES7 193-4DL10-0AA0
Siemens main menu › SIMATIC S7 family › ET 200 › Terminal blocks
6ES7 193-4DL10-0AA0 — ET 200S COMPACT TM-C120S Screw-Terminal Module
6ES7 193-4DL10-0AA0 is the TM-C120S screw-terminal module for ET 200S COMPACT, part of the Siemens ET 200 family. Among ET 200 terminal bases, it carries the field wiring and supply connections for an IM151-1 COMPACT unit. The plug-in COMPACT unit provides the I/O electronics and communication functions.
Construction and compatible modules
Connection: Screw terminals. Dimensions: 120 × 132 × 43 mm (width × height × depth). The installed COMPACT module determines the functions of terminals 1–80. When comparing ET 200 connection modules, check the terminal assignment as well as the dimensions.
Verified combinations: 6ES7151-1CA00-1BL0, IM151-1 COMPACT with 32 digital inputs; and 6ES7151-1CA00-3BL0, IM151-1 COMPACT with 16 digital inputs and 16 digital outputs. The channel specifications of digital input modules and digital output modules belong to the electronic unit, not to this terminal base.
The base feeds the power buses for electronic modules to its right from the COMPACT unit's final potential group. Review the ET 200 power distribution arrangement together with the power supply modules. The AUX1 bus is continuous, but its potential is not accessible through this base's terminals.
Five checks before selection or replacement
1. Identify the COMPACT unit: Read the labels on both the base and the plug-in unit. Sharing a TM-C120S base does not give the 32 DI and 16 DI / 16 DO versions identical field wiring.
2. Distinguish screw and spring terminals: 6ES7193-4DL10-0AA0 / TM-C120S uses screw terminals; 6ES7193-4DL00-0AA0 / TM-C120C uses spring terminals. Cable-end preparation and the connection method also need checking when changing versions.
3. Follow the terminal assignment: Label wires before disconnecting them. When changing to another COMPACT model, use that model's wiring table instead of transferring the old wire sequence unchanged.
4. Check additional potential connections: A suitable supplementary terminal can provide the extra potentials required for three- or four-wire field connections. Select ET 200 additional modules and accessories against the wiring diagram and the approved component combination.
5. Inspect the hardware: On a used base, check screw heads, wire clamps, contacts and latches. Heat damage, cracked insulation or distorted terminals require closer investigation before the part is accepted.
Communication and fault assessment
This base has no PROFIBUS address or user program of its own. Within the ET 200 interface and communication range, the IM151-1 COMPACT unit handles PROFIBUS DP communication. Understanding the ET 200 system structure helps separate wiring and supply faults from problems in the plug-in unit or network.
Editor's note
Physical fit does not establish an identical electrical assignment. A 32-input COMPACT unit and a 16-input / 16-output unit can share this base while assigning different functions to the wiring. Before ordering, check the complete COMPACT unit number as carefully as the terminal-base label.
PDF documentation and user manuals
Use the Siemens ET 200 PDF and user manual page to locate the relevant documents. For terminal construction, consult the TM-C120x section of ET 200S Terminal Modules. For compatible units and terminal assignments, refer to pages 12–13 and 20–21 of IM151-1 COMPACT Modules, A5E01077635-01.
Related topics
Terminal bases • Connection modules • Digital inputs • Digital outputs • Power distribution • Additional modules
Otomasyon AVM • Siemens guide
Siemens main menu | SIMATIC S7 family | ET 200 module categories | ET 200 PDF archive