6ES7 138-4FB03-0AB0

Siemens main menu › SIMATIC S7 › SIMATIC ET 200

Siemens 6ES7 138-4FB03-0AB0 — ET 200S 4 F-DO PROFIsafe Fail-Safe Output Module

6ES7 138-4FB03-0AB0 is a 4 F-DO DC 24 V/2 A PROFIsafe fail-safe digital output module for the ET 200S series within the Siemens ET 200 distributed I/O family. It controls suitable loads, such as contactors or valves, as part of an engineered safety application. Unlike standard ET 200 digital output modules, it is designed for safety-related use.

Order number: 6ES7138-4FB03-0AB0
Outputs: 4 fail-safe digital outputs; transistor, P/M switching
Load voltage: 24 V DC
Rated current per channel: 2 A
Dimensions (W × H × D): 30 × 81 × 52 mm
Approximate weight: 85 g

Safety depends on the complete system

Siemens specifies this model among the ET 200 fail-safe modules suitable for applications up to SIL 3 and PL e. These ratings do not automatically apply to the machine. The controller, program, field devices and validation must be considered together.

PROFIsafe safety communication requires an F-CPU and a suitable station configuration. The product description explicitly permits PROFINET operation with IM151-3 HF; this does not establish unconditional compatibility with every ET 200 PROFIBUS and PROFINET interface.

Five checks before ordering

1. Identification and project: Compare the 4FB03 order code, hardware revision and configured module. Verify the F-address and safety parameters against the existing project. When reviewing the ET 200 system architecture, distinguish the electronic module from the station interface.

2. Terminal base: The Siemens manual lists TM-E30S44-01, TM-E30C44-01, TM-E30S46-A1 and TM-E30C46-A1. Check the termination method and AUX1 arrangement when selecting ET 200 terminal blocks. Do not match ET 200 connection modules by housing width alone.

3. Combined load: Four 2 A channels do not provide an 8 A module rating. The maximum combined output current is 6 A, with derating for temperature and mounting position: horizontal mounting allows 6 A up to 40 °C, 5 A up to 55 °C and 4 A up to 60 °C; vertical mounting allows 4 A up to 40 °C. Include the ET 200 power supply modules and ET 200 power distribution arrangement in the load calculation.

4. Response to test pulses: P/M switching controls both sides of the load. Short diagnostic test pulses can affect fast-responding actuators. Check the load documentation, wiring arrangement and read-back time together. Do not connect outputs in parallel to increase current capacity.

5. Supply scope and replacement: Confirm whether the terminal base and required ET 200 additional modules and accessories are included. Siemens identifies 6ES7138-4FB04-0AB0 as the successor; verify hardware configuration and application compatibility before replacement.

Look beyond the output LED during maintenance

An output that remains off does not necessarily indicate failed electronics. Check the supply, field wiring, load and safety diagnostics together. Passivation places a channel or module in a safe state following a fault. Repeated reintegration attempts do not resolve the underlying cause.

Editor's note

A successful “24 V applied, output switched” test does not validate the safety functions. Compare the base and project details as well as the module label when selecting a spare. Following replacement, the relevant safety functions must be validated by qualified personnel.

Manuals and PDF documentation

Use our Siemens ET 200 PDF and user manuals page to locate ET 200S Fail-Safe Modules, A5E00103686-07, section 7.7. For diagnostic pulses, also consult section 4 of Siemens technical note 44452714. Confirm that the manual covers the 4FB03 order code.

Related topics and Siemens navigation

Product family: Siemens main menu  |  SIMATIC S7  |  ET 200 family

Safety and outputs: Fail-safe modules  |  PROFIsafe  |  Digital output modules

Connections and documentation: Terminal blocks  |  Power supply modules  |  ET 200 PDF manuals