6ES7 138-4DB03-0AB0 — Siemens ET 200S 1 SSI Absolute Encoder Module

6ES7 138-4DB03-0AB0 is a single-channel SSI absolute encoder interface for ET 200S in the Siemens industrial automation range. Its catalog designation is 1 SSI 25 bit / 1 MHz. It transfers encoder position data to the controller through the ET 200 distributed I/O system. Its role is position acquisition; it is not a drive that directly powers a motor.

Key features and purpose

The module supports one SSI encoder, data up to 25 bits, and Gray or binary code. It is 15 mm wide and operates from a nominal 24 V DC supply, with a permissible range of 20.4–28.8 V DC. In industrial automation applications, it provides the data interface between an absolute position encoder and the PLC.

Within SIMATIC S7 control systems, conversion of the raw position value into millimetres, degrees or another machine-specific unit requires separate consideration. Encoder bit depth alone does not establish mechanical accuracy; transmission mechanics, backlash and software scaling also affect the result.

Five checks for selection and commissioning

1. Encoder interface and data format: Confirm that the encoder has an SSI output. Incremental A/B/Z signals, analog outputs and other serial protocols are different interfaces. Telegram length and Gray/binary selection must match the encoder documentation.

2. Separate supply voltage from signal levels: SSI clock and data use RS-422 differential signals. The encoder supply output is specified as L+ − 0.8 V, up to 500 mA; it is not a regulated 5 V supply. When designing the PLC wiring and control architecture, do not select encoder supply voltage from the SSI designation alone.

3. Clock frequency and cable: Siemens specifies shielded twisted-pair cable limits of 320 m at 125 kHz and 20 m at 1 MHz. Select frequency and distance together. When planning the ET 200 system layout, also consider the encoder manufacturer's cable and frequency limits.

4. Operating mode: Standard mode provides a latch function to capture a position value and a comparison function. Fast mode does not provide these two functions. Decide whether the position displayed on HMI operator panels should be continuously updated or captured at a specific event.

5. Terminal and project compatibility: The manual lists TM-E15S24-01 and TM-E15S26-A1 terminal modules. Check terminal wiring, station interface and the project's standard/fast mode selection. Using the module's isochronous capability also requires a supporting controller and communication configuration.

Checking an incorrect position value

If position jumps, changes in the wrong direction or appears incorrectly scaled, compare data format, direction settings, scaling and encoder wiring first. Recording both raw and processed values in SCADA monitoring and logging systems can help distinguish acquisition problems from calculation errors.

For wiring and parameter details, consult the ET 200S Technological Functions — 1SSI section through the Siemens ET 200 PDF manuals page.

Editor's note: The “25 bit / 1 MHz” catalog designation does not describe every setting: Siemens' June 2010 manual also lists a 2 MHz option for this order number, with an 8 m cable limit. Select a setting supported by the encoder, cable and application together. SSI clock frequency is not the number of complete position values acquired per second.

For product assessment, provide the complete module code, encoder model, cable length and existing project details through our Siemens product selection and technical contact page.