6ES7 138-4CF41-0AB0

Siemens main menu › SIMATIC S7 › SIMATIC ET 200

Siemens 6ES7 138-4CF41-0AB0 — ET 200S PM-E F pp PROFIsafe Power Module

6ES7 138-4CF41-0AB0 is the PM-E F pp DC24V PROFIsafe power module for ET 200S within the Siemens ET 200 distributed I/O family. It provides fail-safe relay disconnection of the P2 voltage bus in systems with a grounded reference potential. Among ET 200 power supply modules, its role is to switch an external 24 V supply under the control of the safety program.

Order number: 6ES7138-4CF41-0AB0
Module type: PM-E F pp DC24V PROFIsafe
Switched line: P2 voltage bus

Understanding its role in the station

When reviewing the ET 200 system architecture, identify the load group supplied by this module first. Mark its boundaries in the ET 200 power distribution arrangement and record the full codes of the connected ET 200 digital output modules. The cabinet schematic should clearly identify which valves, contactors or other loads must lose power when the safety function operates.

Five checks before selection or replacement

1. Safety function: The manual specifies SIL 2 / Category 3 for fail-safe shutdown of standard output modules supplied through P2. SIL 3 / Category 4 depends on different wiring and relay switching conditions. When selecting ET 200 safety modules, match the actual circuit to the safety design rather than selecting solely by the highest stated rating.

2. Terminal base: Suitable bases are TM-P30S44-A0 and TM-P30C44-A0. The screw-terminal version is 6ES7193-4CK20-0AA0; the spring-terminal version is 6ES7193-4CK30-0AA0. Check ET 200 terminal blocks separately from the electronic module. A similar housing among ET 200 connection modules does not establish compatibility.

3. Supply and return wiring: Siemens requires two separate M connections to the terminal base, and external protection for the relay contacts. Compare existing bridges, load returns and protective devices with the wiring diagram. Verify the connections against the approved cabinet design instead of relying solely on a photograph of the old installation.

4. PROFIsafe and software: Check the address, monitoring time and reintegration behaviour in the ET 200 PROFIsafe configuration. Record the complete codes of the ET 200 communication interface and Siemens S7 control system. Back up the hardware configuration and safety program before replacement, and establish the correct module address from the project.

5. Loads and operating conditions: Assess total load current, load type, switching frequency and cabinet temperature together. Contact operating conditions matter alongside continuous current in a relay-switched power group. Compare the permitted current with the mounting orientation and temperature conditions in the manual.

Useful information for fault investigation

Record the diagnostic message, the operation that triggered it and any recent wiring changes. After correcting the fault, follow the acknowledgement procedure defined by the safety program. Restoring power to the group is not a complete functional test; verify the expected stopping and restart behaviour asline.

Editor's note

Include the 4CF41 code, terminal base and supplied modules together in a spare-part enquiry. Keep the pp and pm designations when identifying PM-E F modules. Correct matching starts with checking that the module label and cabinet wiring describe the same function.

Manuals and PDF documentation

On our Siemens ET 200 PDF and user manuals page, refer to ET 200S Fail-Safe Modules, A5E00103686-04, section 7.3. This section explicitly covers 6ES7138-4CF41-0AB0. Review the safety rating conditions, terminal diagram and technical limits together.

Related topics and Siemens navigation

Product family: Siemens main menu  |  SIMATIC S7  |  ET 200 family

Power and safety: Power supply modules  |  Safety modules  |  ET 200 PROFIsafe

Technical resources: Terminal blocks  |  PROFIBUS and PROFINET  |  ET 200 PDF manuals