6ES7 132-7RD20-0AB0

Siemens Main Menu  |  SIMATIC S7  |  Siemens ET 200  |  PDF Manuals

6ES7 132-7RD20-0AB0 — Siemens ET 200iSP 4 DO 17.4 V DC/40 mA Digital Output Module

6ES7 132-7RD20-0AB0 is a four-channel, intrinsically safe digital output module for the ET 200iSP series in the Siemens ET 200 distributed I/O family. It is used to operate suitable Ex i actuators in hazardous-area applications from a SIMATIC S7 or PCS 7 control architecture.

Output arrangement and load characteristic

The designation is often read simply as “17.4 V/40 mA”, but the output is not a general-purpose regulated 24 V output. The Siemens data sheet specifies 17.4 V no-load voltage, an internal resistance of 150 Ω and a characteristic point of 11 V / 40 mA. When comparing ET 200 digital output modules, therefore check the actuator’s voltage-current characteristic as well as its nominal current.

Key technical details

Order number: 6ES7132-7RD20-0AB0.
System: SIMATIC DP ET 200iSP.
Outputs: 4 digital outputs.
No-load output voltage: 17.4 V DC.
Characteristic operating point: 11 V / 40 mA; 80 mA with an approved parallel connection.
Internal resistance: 150 Ω.
L+ current without load: 400 mA maximum.
Typical power loss: 2.8 W.
Dimensions: 30 × 129 × 136.5 mm.

The module provides a green status LED per channel and a red SF fault indicator. It supports parameterizable diagnostic interrupts plus wire-break and short-circuit diagnostics. This information can be transmitted through the ET 200 PROFIBUS interface; use the manual applicable to the project version for diagnostic thresholds and cable behaviour.

Five selection and commissioning checks

1. Distinguish the 7RD20 from the 7RD21. The 6ES7132-7RD20-0AB0 is identified as the 4 DO 17.4 V/40 mA version without Shutdown H in its designation. The 6ES7132-7RD21-0AB0 is identified as a Shutdown H version. Similar channel counts and electrical ratings do not establish identical functionality.

2. Verify the actuator’s Ex data. The connected coil, relay or actuator certificate must provide input voltage, current, gas/dust group and permitted cable parameters. Assess ET 200 connection modules together with field-cable capacitance and inductance in the same intrinsic-safety calculation. A general 24 V solenoid is not suitable merely because it can be wired physically.

3. Verify the complete terminal-module code. Siemens’ current control drawing associates the 7RD family with TM-IM/EM 6ES7193-7AA**-0AA0 or TM-EM/EM 6ES7193-7CA**-0AA0 series. When selecting ET 200 terminal modules, check screw/spring terminals, station position and coding element together.

4. Assess parallel outputs against the project. The Siemens data sheet permits two outputs to be connected in parallel for increased power and specifies 80 mA at the characteristic point. This does not permit arbitrary combinations of all four channels. Confirm the approved channel pair, terminal wiring and Ex i calculations in the relevant ET 200 PDF manual.

5. Complete the power and thermal calculation. When selecting ET 200 power supply modules and reviewing the ET 200 power distribution architecture, include the module’s no-load current, four field loads, cable losses and typical 2.8 W power loss. Assess the enclosure layout together with required ET 200 accessories and separation components.

Intrinsic safety is distinct from functional safety

The module’s Ex i classification limits circuit energy for hazardous atmospheres. The product is not designated as an F-DO or PROFIsafe safety output. If a machine safety shutdown is required, engineer ET 200 safety modules and the PROFIsafe system architecture separately.

Editor’s note

For a field report that says “the output is present but the valve does not pull in”, a no-load voltage reading alone is insufficient. Measure voltage and current with the actuator connected, and record the coil label, Ex certificate, cable length and terminal code. Share these details together through the Otomasyon AVM Siemens contact page to make the module-to-actuator assessment more reliable.

PDF manuals and documentation

On the Siemens ET 200 PDF manuals page, consult the ET 200iSP Operating Instructions and Intrinsic Safety Control Drawing A5E00455287. The current control drawing covers the 7RD20 code, terminal families and intrinsic-safety circuit conditions. For final wiring, use the device revision, certificate revision and ET 200iSP station architecture together.