6ES7 132-4BD00-0AA0

Siemens 6ES7132-4BD00-0AA0 ET 200S 4 DO 24 V DC / 0.5 A ST Module

6ES7132-4BD00-0AA0 is a four-channel, 24 V DC / 0.5 A Standard (ST) digital output module for SIMATIC ET 200S. This 15 mm-wide electronic module belongs to the Siemens industrial automation range and controls suitable solenoid valves, DC contactors and indicator lights.

Within the Siemens ET 200 distributed I/O family, it fits ET 200S stations and receives its load supply from the station's power module. When selecting modules for industrial automation applications, assess operating current, switching frequency and the existing terminal base together.

0.5 A per channel, 2 A per module

The rated output current is 0.5 A per channel, with a combined limit of 2 A per module. For example, four 0.4 A loads operating together draw 1.6 A; starting currents still require separate assessment. In PLC-based control applications, include the other loads supplied by the same power module when calculating supply requirements.

Five checks before selection or replacement

1. Load voltage and residual current: At signal “1”, the output voltage is at least L+ − 1 V. Residual current at signal “0” is up to 0.3 mA. Check the off-state behavior of low-current electronic inputs and LED loads, and account for voltage drop along longer cables.

2. Terminal base: The Siemens manual includes connection examples for TM-E15S24-01 and TM-E15S24-A1. When reviewing ET 200 system architecture and terminal selection, note that M and AUX connections can differ between base types. Matching module widths alone do not establish wiring compatibility.

3. Switching frequency: The specified limits are 100 Hz for resistive loads, 2 Hz for inductive loads and 10 Hz for lamp loads. Maximum lamp load is 5 W. In SIMATIC S7 control applications, use the limit for the actual load category when setting the switching cycle.

4. Output use: Short-circuit protection is provided per channel. However, outputs must not be paralleled to increase current capacity. A load requiring more current needs suitable output hardware or an appropriately rated interposing control device.

5. Status indication: Green channel LEDs indicate output status, but the module has no diagnostic function. A command displayed on HMI operator panels is different from field feedback confirming that the load has operated. During troubleshooting, check the output command, supply and load circuit together.

Why the complete order number matters

The Siemens product page identifies 6ES7132-4BD01-0AA0 as a replacement type for this model. When planning a replacement within the Siemens PLC and I/O range, also verify the interface module, hardware catalog and project configuration. The catalog wording “5 pieces per packaging unit” describes the packaging quantity; an individual module has four outputs.

PDF manuals and technical resources

Use the Siemens ET 200 PDF manuals page to access documentation resources. Connections for this model are described in Section 12.12 of the ET 200S Distributed I/O System, 07/2003 manual. For component matching, provide the module label, terminal base code and load details through Siemens product technical enquiries.

Editor's note: Siemens notes that applying the 24 V supply to the power module through a mechanical contact can, depending on the circuit, produce a signal “1” at the outputs for approximately 50 µs. Assess the effect of this brief signal when connecting to fast counters.

Related topics and Siemens navigation

Product families
Siemens main menu  |  Siemens PLC products  |  SIMATIC S7

ET 200 resources
ET 200 products  |  ET 200 system overview  |  ET 200 PDF manuals

Control and assistance
HMI operator panels  |  SCADA systems  |  Siemens product enquiries