6ES7 151-7AA00-0AB0
Siemens 6ES7 151-7AA00-0AB0 – ET 200S IM 151-7 CPU
The Siemens 6ES7 151-7AA00-0AB0 is an early IM 151-7 CPU for the ET 200S distributed I/O system. Siemens’ original documentation calls it the IM 151/CPU. It gives an ET 200 station its own controller, allowing the local I/O to run under a user program.
A station can operate on its own or exchange data with a higher-level PLC as an intelligent PROFIBUS DP slave. This lets the local CPU handle a machine section while the main controller receives status information and sends the commands defined in the project.
Memory and local I/O
The 7AA00 version has 24 KB of work memory and 40 KB of built-in RAM load memory. Work memory cannot be expanded. The station accepts up to 63 ET 200S modules. Later IM 151-7 CPUs have different specifications, so their memory figures should not be used for this part number.
When selecting digital inputs, digital outputs or analog inputs, start with the ET 200S system designation. An ET 200 category can contain several product families; the module, terminal base and station arrangement must belong to a compatible configuration.
A useful PROFIBUS check
The built-in interface is PROFIBUS DP over RS 485, supporting rates up to 12 Mbit/s. On this early version, the PROFIBUS address is set with switches on the module. The switch setting must match the address in STEP 7. A changed address can make an otherwise healthy station disappear from the network.
Engineering software and MMC
The original manual specifies STEP 7 V5.1 or later. For an existing installation, opening the project successfully is only the first step: check that its hardware configuration identifies the correct CPU version.
A SIMATIC Micro Memory Card (MMC) stores the program and hardware configuration. Card capacity and CPU work memory are separate limits. MMC guidance for a newer IM 151-7 CPU may not apply to the 7AA00, so use the Siemens compatibility information for the complete order number when replacing a card.
Replacing an early CPU
Moving from 6ES7151-7AA00-0AB0 to 6ES7151-7AA10-0AB0 involves more than a change in memory size. Siemens documents differences in system-function behavior. Calls such as SFC 13 execute asynchronously on the newer CPU, which can affect how an existing program waits for completion and reads results. A successful download therefore needs to be followed by communication checks and a controlled test of the machine cycle.
For troubleshooting, save the project and read the CPU diagnostics before changing the configuration. Then compare the power supply, PROFIBUS address, bus termination and module order with the working design. On a long-running machine, checking the exact code of a recently replaced card or module is often a useful way to narrow the search.
Editor’s note: This is a standard CPU, not an IM 151-7 F-CPU. It should not be assigned the F-CPU capabilities required by an application using fail-safe I/O and PROFIsafe. It has no built-in PROFINET interface. For a replacement, match the complete order number rather than relying on the IM 151-7 name on the front.
Manuals and PDF downloads
Visit the Siemens ET 200 user manuals page for wiring, programming and maintenance documentation. The relevant starting point is the ET 200S Interface Module IM 151/CPU manual covering 6ES7151-7AA00-0AB0.
Related topics
Station hardware: Terminal blocks · Connection modules · Power supply modules · Power distribution modules.
Other ET 200 components: PROFIBUS and PROFINET interfaces · Other network interfaces · Functional modules. These categories include different ET 200 systems and should not be read as a list of direct replacements.
Navigation: Siemens automation · SIMATIC S7 · About ET 200.