6ES7 151-1AA04-0AB0
Siemens 6ES7 151-1AA04-0AB0 – ET 200S IM151-1 STANDARD
The Siemens 6ES7 151-1AA04-0AB0 is an IM151-1 STANDARD interface module for an ET 200S station. Part of the ET 200 range, it handles PROFIBUS communication between the station’s I/O and the main PLC. The PLC runs the machine program, while the ET 200S modules provide the field connections.
63 modules and 244 bytes in each direction
The AA04 supports up to 63 peripheral modules, a maximum station width of 2 metres, and 244 input bytes plus 244 output bytes. Input and output capacity are separate limits.
The AA04 suffix matters here. Earlier STANDARD versions, up to AA03, provide 128 bytes in each direction; AA04 increases that to 244 bytes. Using an older catalogue entry can therefore understate the capacity of this particular interface.
A station can combine digital input, digital output and analog input modules. Before extending it, check address usage, power groups and terminal bases as well as module count. Available physical space is only one part of the assessment.
PROFIBUS connection and operating mode
The module connects through a 9-pin D-sub socket using PROFIBUS DP over RS 485, at rates up to 12 Mbit/s. It supports operation as either a DPV0 or DPV1 slave. Select the operating mode to suit the DP master and project configuration.
The station address is set using the front-panel DIP switches. Valid addresses are 1 to 125, and each must be unique on the network. When replacing an interface, compare its address setting with the station address in STEP 7.
Power connector differences between revisions
The interface requires a 24 V DC supply. Siemens provides separate terminal drawings for AA04 hardware releases up to 6 and release 7 onwards. Two units with the same order number can therefore have visibly different supply terminal arrangements. Check the 1L+, 2L+, 1M and 2M markings against the drawing for the actual unit.
Replacement and maintenance
Siemens’ original manual identifies AA04 as a compatible replacement for earlier STANDARD interfaces from 6ES7151-1AA00-0AB0 through 6ES7151-1AA03-0AB0. It also supports firmware updates over PROFIBUS DP. Record the full order number, hardware release and installed firmware before assessing whether an update is needed.
For a communication fault, compare the installed module order with the saved project first. Then check the supply, PROFIBUS address, cabling and connectors. Capturing diagnostics before making changes helps preserve evidence of where and when the fault began.
Editor’s note: For spare-part identification, record the full order number and hardware release rather than relying on the IM151-1 label alone. If the installation uses PROFINET, review the interface selection accordingly: this model connects to PROFIBUS DP.
Manuals and PDF downloads
Visit the Siemens ET 200 user manuals page for connection and maintenance documents. The AA04 is covered in section 10.5 of the December 2005 ET 200S Operating Instructions. When consulting a later STANDARD manual, check that the relevant information explicitly applies to AA04.
Related topics
Station hardware: Terminal blocks · Connection modules · Power supply modules · Power distribution modules.
More from the ET 200 range: PROFIBUS and PROFINET interfaces · Other network interfaces · Functional modules · Safety modules · PROFIsafe. These links cover other parts of the range; they do not establish compatibility with this interface.
Navigation: Siemens automation · SIMATIC S7 · About ET 200.
Sources: Siemens SiePortal, 6ES7151-1AA04-0AB0 product entry; ET 200S Operating Instructions, 12/2005, A5E00515771-03, section 10.5; 08/2008, A5E00515771-06, PROFIBUS configuration; IM151-1 STANDARD, 07/2015, A5E01075950-AD, terminal drawings for AA04 hardware releases.