• Gemo DT109A

Gemo DT109A-230VAC-R is a 96 × 96 mm multi-input digital temperature controller designed for industrial heating and temperature-control applications. It supports J, K, T, S and R type thermocouples as well as Pt100 sensors, and can operate in P, PI, PD, PID or ON/OFF control modes. OtomasyonAVM has been supplying Gemo control products since 2013.

Supply voltage: 100–240 VAC, 50–60 Hz.
A 24 VAC/DC version is also available and must be specified when ordering. Related supply products can be found in our power supply section.
Outputs: 2 relay outputs.
If an SSR output version is required, this should also be specified when ordering.

Multi-input sensor support

The DT109A supports selectable J, K, T, S and R type thermocouples together with Pt100 input.

For Pt100 applications, the controller supports 3-wire connection with line compensation up to 10 Ω. Suitable Pt100 sensors are available in our temperature sensor range.

PID and ON/OFF control

The heating hysteresis parameter is defined by H.Hys.

When H.Hys = 0, PID control becomes active for the heating function.

When a hysteresis value above zero is selected, the controller can operate with ON/OFF temperature control.

Heating hysteresis: 0–50 °C or 0.0–50.0 °C.
Control modes: P, PI, PD, PID or ON/OFF.
Control period Ct: 1–200 seconds.
Integral time Ti: 0:00–30:00 min:sec.
Derivative time Td: 0:00–10:00 min:sec.

PID parameter behaviour

PbC – Proportional Band: Determines how many degrees before H.SET the time-proportional control action begins. The proportional band ends at the H.SET value.

Ct – Control Period: Adjustable from 1 to 200 seconds. According to the controller information, a value in the 1–10 second range is recommended for good control in suitable applications.

Ti – Integral Time: The integral part of the PID algorithm compensates for the remaining difference between the Process Value and SET value. Lower Ti values generally give a faster response, but excessively low values may cause process oscillation.

Ti = 0 disables the integral action, so the controller operates as P or PD depending on the other parameters.

Td – Derivative Time: Determines the response to rapid changes between the Process Value and SET value. Increasing Td increases sensitivity to sudden process changes.

Td = 0 disables derivative action, so the controller operates as P or PI depending on the remaining parameters.

Alarm functions

The DT109A allows selection of relative, absolute, band or sensor-break alarm functions.

Alarm hysteresis: 1–50 °C or 0.1–50.0 °C.
Alarm SET: Lo.L–UP.L according to the selected AL.tY setting.
Alarm output: Relay, NO + NC, 250 VAC / 2 A resistive load.

The controller also provides a delay function for the cooling output.

Sensor fault protection

If the sensor or sensor wiring is open, the selected measuring range is exceeded or the input measurement fails, the OUT behaviour is determined by the P.Err and Ct parameters.

If P.Err = 0, the OUT output remains OFF during the corresponding sensor fault condition.

This setting should therefore be checked during commissioning according to the safety requirements of the process.

Measurement ranges

J type T/C: -100 to 600 °C.
J.0 type: -100.0 to 600.0 °C.

K type T/C: -100 to 1300 °C.
K.0 type: -100.0 to 999.9 °C.

T type T/C: 100 to 400 °C.
T.0 type: -100.0 to 400.0 °C.

S type T/C: 0 to 1750 °C.
R type T/C: 0 to 1750 °C.

Pt100: -100 to 600 °C.
Pt100 decimal range: -100.0 to 600.0 °C.

Compatible probes are available in our temperature measuring sensors section.

If you are deciding between RTD and thermocouple measurement, see our short guide: Pt100 vs. thermocouple.

Gemo DT109A technical specifications

Front size: 96 × 96 mm.
Display: 4-digit 7-segment PV display + 4-digit 7-segment SV display.
Sensor input: J, K, T, S, R type T/C and Pt100, selectable multi-input.
Heat SET: Lo.L–UP.L, adjustable with H.SET.
Control period: 1–200 seconds.

Relay outputs: 2 outputs.
SSR output: Optional.
Power consumption: < 8 VA.
Supply: 100–240 VAC, 50–60 Hz or optional 24 VAC/DC.
24 V version isolation voltage: Maximum 40 VAC.

Parameter access: Password-protected.
Memory: Program and control parameters are retained in non-volatile memory.

Installation with AC drives

The DT109A can be installed in industrial control panels containing AC drives and speed controllers. Thermocouple and Pt100 signal cables should be routed separately from inverter output, motor and other high-current power cables where possible.

Separating low-level sensor wiring from power wiring and using suitable shielding helps reduce electrical interference and unstable temperature readings.

Gemo DT109A User Manual (PDF)

Gemo price list
Gemo contact and technical support
Gemo main page
Industrial control devices

Installation: Sensor, supply and relay/SSR wiring should be carried out by qualified technical personnel.

Before applying power, check the selected sensor type, wiring, supply voltage and relay/SSR output configuration against the Gemo user manual.

Write a review

Note: HTML is not translated!
Bad Good

Gemo DT109A

  • 42.00USD

  • Ex Tax: 42.00USD

Related Products

DESA-99R-A Analog Temperature Controller, 220V

DESA-99R-A Analog Temperature Controller, 220V

▪︎ DERELL DESA-99R-A >> 220V Power Supply, Relay Output, 96x96 mm Panel Type Temperature Contr..

129.00USD Ex Tax: 129.00USD

DGS-99R-A Advanced Temperature Controller (220V)

DGS-99R-A Advanced Temperature Controller (220V)

— Next-generation temperature compensation with high precision DGS-99R-A >> 220V pow..

132.00USD Ex Tax: 132.00USD

DGS-99T-A – Advanced Serial Type with SSR Output – 220V

DGS-99T-A – Advanced Serial Type with SSR Output – 220V

— Next-generation temperature compensation with high precision DGS-99T-A >> 220V pow..

137.00USD Ex Tax: 137.00USD

DGS-99R-B Advanced Temperature Controller (24VAC/DC)

DGS-99R-B Advanced Temperature Controller (24VAC/DC)

— Next-generation temperature compensation with high precision DGS-99R-B >> 24VDC/AC..

209.00USD Ex Tax: 209.00USD