Gemo UC107 is a universal process controller designed for standard industrial analog signals. The input can be configured for 0–10 V, 0–1 V, 0–20 mA or 4–20 mA, allowing the measured signal to be scaled to the required process value. OtomasyonAVM has been supplying Gemo products since 2013.
Standard supply: 100–240 VAC, 50–60 Hz.
A 24 volt supply version is available when specified at the time of order.
Input: Selectable industrial analog signal.
Output: Relay output as standard. If an SSR output version is required, this should be specified when ordering.
Selectable analog inputs:
0–10 VDC
0–1 VDC
0–20 mA DC
4–20 mA DC
The UC107 can be used with transmitters and industrial sensors that provide standard analog signals for pressure, level, flow, temperature and similar process measurements.
Analog input scaling
Calibration is carried out with the LO.SC and HI.SC parameters. First select the required input type, then enter the process values that should correspond to the minimum and maximum input signal.
LO.SC: Display value at the bottom of the selected input range.
HI.SC: Display value at the top of the selected input range.
The selected analog input is then scaled linearly between these two values.
Example 1 – 0–10 V input
With LO.SC = -100 and HI.SC = 1750:
0 V displays -100.
10 V displays 1750.
5 V displays 825.
Example 2 – 0–1 V input
With LO.SC = -100 and HI.SC = 1750:
0 V displays -100.
1 V displays 1750.
0.5 V displays 825.
Example 3 – 4–20 mA input
With LO.SC = -300 and HI.SC = 750:
4 mA displays -300.
20 mA displays 750.
12 mA displays 225.
Example 4 – 0–20 mA input
With LO.SC = -300 and HI.SC = 750:
0 mA displays -300.
20 mA displays 750.
10 mA displays 225.
The d.Pnt parameter is used to select the decimal-point position.
Control and alarm settings
Control method: ON/OFF.
OUT control direction: Direct or reverse.
OUT SET range: LO.SC to HI.SC.
OUT hysteresis: 1–100.
OUT relay: NO + NC, 250 VAC / 2 A resistive load; SSR version optional.
ALARM relay: NO + NC, 250 VAC / 2 A resistive load.
Alarm hysteresis: 1–100.
Offset: -500 to +500 using the oFFS parameter.
Alarm SET ranges:
AL.tY = Abs / -Abs: LO.SC to HI.SC.
AL.tY = rel / -rel / bnd / -bnd / bn.i / -bn.i: -500 to +500.
Input fault protection: If the analog input cannot be measured correctly, both OUT and ALARM switch OFF.
Important: A 27 Ω shunt resistor is connected internally between terminals 14 and 15 of the UC107 current input. Do not apply a voltage signal to these terminals.
Applying voltage to the current-input terminals may cause permanent hardware damage. All analog inputs are DC and the correct polarity must be observed.
Analog input specifications
Voltage input: Input impedance > 22 kΩ; maximum applied voltage 20 VDC.
Current input: Internal 27 Ω shunt; maximum applied current 50 mA DC.
Calibration range: -1999 to 4000.
Decimal point: Selectable at the 2nd, 3rd or 4th digit.
Display tolerance: ±1 digit.
Accuracy: ±0.5% of full scale.
Supply voltage: 100–240 VAC, 50–60 Hz or optional 24 VAC/DC.
24 V version isolation voltage: Maximum 40 VAC.
Power consumption: < 6 VA.
Relative humidity: Up to 80% at 30 °C, decreasing linearly to 50% at 50 °C, non-condensing.
Operating altitude: < 2000 m.
EMC: EN 61000-6-1 and EN 61000-6-3 for light industrial environments.
When the UC107 is installed in the same control panel as AC drives or other electrically noisy equipment, signal wiring, cable routing and shielding should be arranged with normal EMC practice in mind.
When replacing an existing UC107, check the analog input type, supply voltage and output configuration as well as the physical fit. Similar-looking units may not have the same electrical configuration.
Gemo price list
Gemo contact information
Gemo main page
Industrial control devices
Installation: Wiring and commissioning should be carried out by qualified technical personnel.
Before applying power, check the supply voltage, selected analog input type, terminal connections and output configuration against the product documentation.
Gemo UC107
- Mağaza: Efes Otomasyon
- Store: Efes Automation
- Brands GEMO
- Product Code: Gemo UC107-230VAC-R
- Availability: 28
-
37.00USD
- Ex Tax: 37.00USD
Related Products
Siemens SIPART DR21
Hello, Wellcome to our Siemens SIPART DR 21-PROCESS CONTROLLER SIPART DR21 Module page&n..
228.00USD Ex Tax: 228.00USD
inovance H0U 88B1G
Hello,Wellcome inovance H0U 88B1G, PLC + HMI product page, Communication PortsThe H0U series PLC ha..
1.00USD Ex Tax: 1.00USD