Gemo DT105A-230VAC-R Auto-tune PID Temperature Controller
Gemo control products have been sold by our company since 2013.
Gemo DT105A is a microprocessor-based industrial temperature controller with selectable sensor inputs and Auto-tune PID control. It supports ON-OFF, P, PI, PD and PID control modes for heating applications.
Front dimensions: 48 x 96 mm
Panel cut-out: 93.5 x 45.5 mm
Supply voltage: 100..240VAC, 50-60Hz
Control output: Relay, NO + NC, 250VAC, 2A resistive load
Alarm output: Relay, NO + NC, 250VAC, 2A resistive load
A 24VDC/AC supply version and SSR control output version are available and must be specified when ordering.
Control Features
Control mode: ON-OFF, P, PI, PD or PID selectable. When the H.Hys value is set to 0, PID control becomes active for heating.
Heating Hysteresis (H.Hys): 0 .. 50 °C or 0.0 .. 5.0 °C when Pt.0 is selected.
Alarm Hysteresis (A.Hys): 1 .. 50 °C or 0.1 .. 5.0 °C when Pt.0 is selected.
Alarm functions: Absolute, inverse absolute, relative, inverse relative, band and inverse band alarm modes are selectable.
Heating / Cooling: Selectable. Only ON-OFF control is available in cooling mode. An output ON-delay can also be set for cooling applications.
Control Period (Ct): 4 .. 200 seconds. For PID applications, a control period between 4 and 10 seconds is generally preferred.
Proportional Band (Pb.C): Defines the proportional control range before the H.SET value.
Integral Time (Ti): 0 .. 30.0 minutes. The integral function compensates for the difference between the process value and SET value. Lower Ti values provide faster correction; however, excessively low values may cause process oscillation. When Ti is set to 0, the integral section is disabled and the controller operates as P or PD.
Derivative Time (Td): 0 .. 10.0 minutes. The derivative function reacts to sudden changes in the process value. Excessively high Td values should be avoided. When Td is set to 0, the derivative section is disabled and the controller operates as P or PI.
Auto-tune: The controller can automatically calculate PID parameters for the connected process. PID operation also includes anti-windup and automatic overshoot reduction.
Sensor Inputs and Measurement Ranges
Gemo DT105A supports selectable J, K, T, S and R type thermocouples and Pt100 temperature sensors.
J type T/C: -100 .. 600 °C
K type T/C: -100 .. 1300 °C
T type T/C: -100 .. 400 °C
S type T/C: 0 .. 1750 °C
R type T/C: 0 .. 1750 °C
Pt100: -100 .. 600 °C
Pt100 (Pt.0): -99.9 .. 600.0 °C
Resolution: ±1 °C or ±0.1 °C
Accuracy: ±0.3% over full scale
Pt100 Line Compensation: Maximum 10 Ohm with a 3-wire Pt100 sensor.
You can view our temperature sensor models or our K type thermocouple sensors for compatible measurement sensors.
For further information about sensor selection, see our Pt100 vs Thermocouple comparison.
Sensor Failure Protection
If the sensor or sensor line is broken, the measurement is outside the selected range, or the controller cannot measure the input signal, the display shows a FAIL warning.
During a FAIL condition, the ALARM output always remains OFF. The OUT output operates according to the P.Err and Ct parameters. P.Err determines the OUT duty cycle during a sensor failure; if P.Err is set to 0, the OUT output remains OFF.
Additional Technical Specifications
Display: 4-digit 7-segment PV + 4-digit 7-segment SV
Heat SET: Lower Limit .. Upper Limit °C (H.Set)
Offset: -100 .. +100 °C or -10.0 .. +10.0 °C with Pt.0
Power consumption: < 8VA
Protection class: IP20
Operating temperature: 0 .. 50 °C
Storage temperature: -10 .. 60 °C
Operating altitude: < 2000 m
Weight: < 0.5 kg
The controller provides cold-junction compensation for thermocouple inputs and line compensation for Pt100 sensors. Program and control parameters are stored in non-volatile memory, and access to programming parameters is password protected.
For related switching products, see our relay and socket products.
Documentation and Gemo Links
Gemo DT105A User Manual (PDF)
Electronic Control Devices Main Page
Installation and Safety
Gemo DT105A is designed for permanent panel mounting. Installation, wiring and commissioning must be performed only by qualified and trained technical personnel. Disconnect all electrical power sources before installation or wiring.
Check the supply voltage before energizing the controller. Do not install or operate damaged equipment, and do not use the controller in environments containing flammable, explosive or corrosive substances.
The manufacturer specifies an external 1A / 250VAC fuse on the power supply line and a separate 2A / 250VAC fuse for each relay output.
For detailed product and ordering information, visit the Gemo Contact page or contact gemo@otomasyonavm.com.
Gemo DT105A
- Mağaza: Efes Otomasyon
- Store: Efes Automation
- Brands GEMO
- Product Code: Gemo DT105A-230VAC-R
- Availability: 12
-
53.00USD
- Ex Tax: 53.00USD
Related Products
DGS-94R-A Advanced Temperature Controller (220V)
— Next-generation temperature compensation with high precision DGS-94R-A >> 220V pow..
134.00USD Ex Tax: 134.00USD
DGS-94T-A – Advanced Serial Type with SSR Output – 220V
— Next-generation temperature compensation with high precision DGS-94T-A >> 220V pow..
139.00USD Ex Tax: 139.00USD
DGS-94R-B Advanced Temperature Controller (24VAC/DC)
— Next-generation temperature compensation with high precision DGS-94R-B >> 24VDC/AC..
207.00USD Ex Tax: 207.00USD
DGS-94T-B – Advanced Serial Type with SSR Output – 24VDC/AC
— Next-generation temperature compensation with high precision DGS-44T-B >> 24VDC/AC..
208.00USD Ex Tax: 208.00USD