• Gemo DT106A

Gemo DT106A-230VAC-R Temperature Controller

Gemo control products have been sold by our company since 2013.

Gemo DT106A is a microprocessor-based industrial temperature controller with selectable sensor inputs and Auto-tune PID control. Heating applications can operate in ON-OFF, P, PI, PD or PID control modes.

Front dimensions: 48 x 96 mm
Panel cut-out: 93.5 x 45.5 mm
Supply voltage: 100..240VAC, 50-60Hz
Control output: Relay, NO + NC, 250VAC, 2A resistive load
Alarm output: Relay, NO + NC, 250VAC, 2A resistive load

A 24VDC/AC supply version and SSR control output version are available and must be specified when ordering.

Control Features

Heating Hysteresis (H.Hys): 0 .. 50 °C or 0.0 .. 5.0 °C with Pt.0 input. When H.Hys is set to 0, PID control becomes active for the heating function.

Alarm Hysteresis (A.Hys): 1 .. 50 °C or 0.1 .. 5.0 °C with Pt.0 input.

Alarm functions: Absolute, inverse absolute, relative, inverse relative, band and inverse band alarm modes can be selected.

Heating / Cooling: Selectable. Cooling operation uses ON-OFF control only. A delay function is available for the cooling output.

Control Period (Ct): 4 .. 200 seconds. For good PID control performance, a value between 4 and 10 seconds is generally recommended.

Proportional Band (Pb.C): Determines how many degrees before the H.SET value time-proportional operation begins.

Integral Time (Ti): The PID algorithm compensates for the difference between the process value and the SET value. Lower Ti values provide faster response; however, excessively low values should be avoided because they may cause process oscillation. When Ti is set to 0, the integral section is disabled and the controller operates as P or PD.

Derivative Time (Td): Compensates for sudden changes between the process value and the SET value. Increasing Td increases sensitivity to sudden changes. Excessively high Td values should be avoided. When Td is set to 0, the derivative section is disabled and the controller operates as P or PI.

Auto-tune: PID parameters can be calculated automatically by the controller for heating applications. The PID algorithm also includes an anti-windup function to help reduce overshoot.

Sensor Inputs and Measurement Ranges

Gemo DT106A supports selectable J, K, T, S and R type thermocouples and Pt100 sensors.

J type T/C: -100 .. 600 °C
K type T/C: -100 .. 1300 °C
T type T/C: -100 .. 400 °C
S type T/C: 0 .. 1750 °C
R type T/C: 0 .. 1750 °C
Pt100: -100 .. 600 °C
Pt100 (Pt.0): -99.9 .. 600.0 °C

For suitable thermocouples, see our temperature sensor models. You can also view our K type thermocouple sensors.

Sensitivity: ±1 °C or ±0.1 °C
Accuracy: ±0.3% of full scale

Pt100 Line Compensation: Maximum 10 Ohm with a 3-wire Pt100 sensor.

For a short technical explanation, see our Pt100 vs Thermocouple comparison.

Sensor Protection

If the sensor or sensor line is broken, the measurement is outside the selected range or the input signal cannot be measured, the controller displays a FAIL warning.

In this condition, the ALARM output remains OFF. The OUT output operates according to the P.Err and Ct parameters. If P.Err is set to 0, the OUT output also remains OFF.

Additional Technical Specifications

Display: 4-digit 7-segment PV + 4-digit 7-segment SV
Heat SET: Lo.L .. UP.L °C (H.Set)
Offset: -100 .. +100 °C or -10.0 .. +10.0 °C with Pt.0
Integral Time: 0 .. 30.0 minutes
Derivative Time: 0 .. 10.0 minutes
Power consumption: < 8VA
Protection class: IP20
Operating temperature: 0 .. 50 °C
Storage temperature: -10 .. 60 °C
Weight: < 0.5 kg

The controller is password protected and stores program and control parameters in non-volatile memory.

The control relay and alarm relay are rated at 250VAC, 2A for resistive loads. For related switching components, see our relay and socket products.

Documentation and Gemo Links

Gemo DT106A User Manual (PDF)

Gemo Price List

Gemo Contact

Gemo Electronic Main Page

Electronic Control Devices Main Page

Installation and Safety

Gemo DT106A is intended for fixed panel mounting. Installation, wiring and commissioning must be performed only by trained and qualified technical personnel. All electrical power sources must be disconnected before installation or wiring work is started.

Check the supply voltage before energizing the controller. Do not install or operate a damaged unit. The controller must not be used in environments containing flammable or explosive gases, combustible materials or corrosive atmospheres.

For detailed product and ordering information, please visit the Gemo Contact page or contact gemo@otomasyonavm.com.

Write a review

Note: HTML is not translated!
Bad Good

Gemo DT106A

  • 55.00USD

  • Ex Tax: 55.00USD

Related Products

DGS-49R-A Advanced Temperature Controller (220V)

DGS-49R-A Advanced Temperature Controller (220V)

— Next-generation temperature compensation with high precision DGS-49R-A >> 220V pow..

133.00USD Ex Tax: 133.00USD

DGS-49T-A – Advanced Serial Type with SSR Output – 220V

DGS-49T-A – Advanced Serial Type with SSR Output – 220V

— Next-generation temperature compensation with high precision DGS-49T-A >> 220V pow..

138.00USD Ex Tax: 138.00USD

DGS-49R-B Advanced Temperature Controller (24VAC/DC)

DGS-49R-B Advanced Temperature Controller (24VAC/DC)

— Next-generation temperature compensation with high precision DGS-49R-B >> 24VDC/AC..

203.00USD Ex Tax: 203.00USD

DGS-49T-B – Advanced Serial Type with SSR Output – 24VDC/AC

DGS-49T-B – Advanced Serial Type with SSR Output – 24VDC/AC

— Next-generation temperature compensation with high precision DGS-49T-B >> 24VDC/AC..

204.00USD Ex Tax: 204.00USD