Delta VFD-F Fault codes 2
Hello! Welcome to Maintenance and Inspections of your Delta VFD-F.
Maintenance Basics
Your
modern AC drive is a solid piece of tech, but it does need some regular
care to keep it running smoothly and to ensure it lasts a long time.
It's a good idea to have a qualified technician check it out every
month.
Before any check-up, remember to turn off the AC Input Power
and wait about 10 minutes until all the lights are off. Then, use a
multimeter to make sure the capacitors have fully discharged by checking
the voltage between B1 and Ground.
Periodic Inspection
Here's what to look out for during operation:
Check if the motors are working as they should.
Make sure the installation environment is all good.
See if the cooling system is doing its job.
Listen for any weird vibrations or sounds.
Keep an eye on the motors to make sure they're not getting too hot.
Always use a voltmeter to check the input voltage of the AC drive.
Periodic Maintenance
Warning! Always disconnect AC power before doing any maintenance!
Tighten any loose screws on the AC drive, as they can come loose due to vibration or temperature changes.
Check if any conductors or insulators are corroded or damaged.
Use a Meg-ohmmeter to check the insulation resistance.
Regularly check and replace capacitors and
If you're not using the AC drive for a long time, turn it on at least once every two years to make sure it's still working properly. Before running a motor with it, disconnect the motor and energize the AC drive for at least 5 hours.
Use a vacuum cleaner to remove any dust and dirt, especially around the ventilation ports and PCBs. Keeping these areas clean can prevent unexpected failures.
Troubleshooting and Fault Information
Your AC drive has a great fault diagnostic system with various alarms and fault messages. When a fault is detected, the right protective functions kick in. You can see the faults displayed on the digital keypad, and the four most recent faults can be read there too.
Note: You can clear faults with a reset from the keypad or the Input Terminal.
HPF.1 to HPF.5: Hardware Errors
What's happening: These are various hardware errors, like GFF, Current Clamp, Overcurrent, Overvoltage, and Overheat.
Fix: For all these errors, the best course of action is to return the drive to the factory for repair or replacement.
cE: Communication Error
What's happening: There's a problem with the communication between the AC drive and the computer.
Fixes:
- Check for any loose wires in the connection.
- Make sure the communication protocol is set correctly.
ocA: Over-current during Acceleration
What's happening: There's too much current during acceleration.
Fixes:
- Check for a short-circuit at the motor output or poor insulation on the output line.
- Lower the torque boost setting (Pr.7-02).
- Increase the acceleration time.
- If needed, replace the AC drive with one that has a higher output capacity (next HP size).
ocd: Over-current during Deceleration
What's happening: There's too much current when the drive is slowing down.
Fixes:
- Check for a short-circuit at the motor output or poor insulation on the output line.
- Increase the deceleration time.
- If needed, replace the AC drive with one that has a higher output capacity (next HP size).
ocn: Over-current during Steady State Operation
What's happening: There's too much current during normal operation.
Fixes:
- Check for a short-circuit at the motor output or poor insulation on the output line.
- Look for a sudden increase in motor loading or possible motor stall.
- If needed, replace the AC drive with one that has a higher output capacity (next HP size).
EF: Analog Signal Error
What's happening: There's an issue with the analog signal.
Fixes:
- Check the wiring of the ACI (Analog Current Input).
- Make sure the input current of ACI is not lower than the setting in Pr.04-13/04-17.
EF1: Emergency Stop
What's happening: The drive has stopped due to an emergency stop signal from the multi-function input terminals (MI1 to MI8).
Fix: Press RESET after the fault has been cleared to resume operation.
cF1: Internal Memory IC Error
What's happening: The internal memory IC can't be programmed.
Fixes:
- Return the drive to the factory for repair.
- Check the EEPROM on the control board.
cF2: Internal Memory IC Cannot Be Read
What's happening: The drive can't read the internal memory IC.
Fixes:
- Return the drive to the factory for repair.
- Try resetting the drive to factory defaults.
cF3.3 to cF3.8: Phase and Other Errors
What's happening: These errors relate to issues with the U-phase, V-phase, W-phase, overvoltage or undervoltage (OV or LV), Isum, and overheat (OH).
Fix: For all these errors, the best course of action is to return the drive to the factory for repair.
codE: Software Protection Failure
What's happening: There's a failure in the software protection system.
Fix: Return the drive to the factory for repair.
cFA: Auto Accel/Decel Failure
What's happening: The auto acceleration/deceleration function has failed.
Fix: Don't use the auto acceleration/deceleration function until the issue is resolved.
GFF: Ground Fault
What's happening: There's an abnormality in the AC drive output, possibly due to a ground fault. This can damage the power module.
Fixes:
- Check if the IGBT power module is damaged.
- Check for poor insulation on the output line.
bb: External Base Block
What's happening: The AC drive output is turned off due to an active external input terminal (B.B).
Fixes:
- When the external input terminal (B.B) is active, the AC drive output will be turned off.
- Disable this connection, and the AC drive will start working again.
FbL: PID Feedback Signal Error
What's happening: There's an issue with the PID feedback signal.
Fixes:
- Check the parameter settings (Pr.10-00) and the wiring of AVI/ACI1/ACI2.
- Look for a possible mismatch between the system reaction time and the feedback signal detection time (Pr.10-08/Pr.10-09).
FAnP: Fan Power Fault (150~300HP)
What's happening: There's a fault in the fan power.
Fix: Return the drive to the factory for repair.
FF1, FF2, FF3: Fan 1, 2, 3 Faults (150~300HP)
What's happening: There are issues with Fan 1, Fan 2, or Fan 3.
Fix: Remove any foreign objects on the heatsinks and check for dirty heat sink fins.
FF123: Fan 1, 2, 3 Fault (150~300HP)
What's happening: All three fans (Fan 1, Fan 2, and Fan 3) have faults.
Fix: Remove any foreign objects on the heatsinks and check for dirty heat sink fins.
FF12: Fan 1, 2 Fault (150~300HP)
What's happening: Both Fan 1 and Fan 2 have faults.
Fix: Remove any foreign objects on the heatsinks and check for dirty heat sink fins.
FF13: Fan 1, 3 Fault (150~300HP)
What's happening: Both Fan 1 and Fan 3 have faults.
Fix: Remove any foreign objects on the heatsinks and check for dirty heat sink fins.
Fan 2, 3 Fault (150~300HP)
What's happening: Both Fan 2 and Fan 3 have faults.
Fix: Remove any foreign objects on the heatsinks and check for dirty heat sink fins.
Fu: Gate Drive Low Voltage Protect
What's happening: The gate drive has low voltage protection.
Fix: Return the drive to the factory for repair.
-----------------