Delta TP70P-RM0
Delta TP70P-RM0 7-Inch Touch Panel with Built-In PLC
Delta TP70P-RM0 belongs to the Delta TP70P family and combines a 7-inch TFT LCD touchscreen with built-in PLC logic. Its display resolution is 800 × 480 pixels. Within the TP panels and remote I/O group, it is intended for applications using an operator interface and control project in the same unit.
The RM0 has no physical digital inputs, digital outputs or analog I/O. Although it contains PLC logic, it is not an I/O expansion module with terminals for direct sensor and load connections. External field signals require separate control or serial I/O hardware compatible with the project, protocol and address structure.
Display, mounting and supply
The nominal panel cutout is 191 × 128 mm, overall dimensions are 205.6 × 142.6 × 37 mm, and the supply is 24 V DC. Check cutout tolerances and mounting arrangements against the manufacturer’s drawing. Even when the old panel looks similar, compare mounting and power connections and the space required for cables inside the cabinet.
Communication connections specific to the RM0
COM2 is RS-232 and COM3 is RS-485; a USB Type-B connection is provided for computer communication and program transfer. Both RM0 serial ports are listed as operating in Text panel mode. Do not copy COM2 settings from TP70P versions with onboard I/O. Select communication peripherals for the electrical interface of the connected device and the project driver.
USB, RS-232 and RS-485 cables serve different purposes. A connector fitting into a socket does not establish that its pinout is correct. When selecting HMI programming and connection cables, check both devices, the port number and the connector orientation shown in the manual.
Preparing the panel and PLC projects
The TP70P manual describes TPEditor for the screen project and WPLSoft for transferring and monitoring the PLC program. If ISPSoft is used, verify target-device support and the existing project version. When choosing Delta PLC software, keep separate records for the screen project and PLC program backups; obtaining one does not establish that the other is complete.
Differences from other TP70P models
TP70P-16TP1R, TP70P-32TP1R, TP70P-22XA1R and TP70P-21EX1R have different physical I/O arrangements. The RM0 must not be treated as a replacement into which their field wiring can simply be connected. Check the required I/O, serial-port duty and hardware expected by the existing program as well as the display dimensions.
Editor’s Note
Start with the nameplate. Seeing TP70P is not enough: the RM0 suffix changes what hardware is present. Do not search for a failed relay output or missing I/O terminal on a version that has no onboard physical I/O.
When buying a used unit, ask for more than a photograph of the startup screen. Check backlight brightness and touch response at all four corners, in the centre and while dragging. Observe cold startup and operation after the panel has warmed up separately.
If the panel is still running a machine, make backups before loading anything into it. Obtain the available screen and PLC projects, then record passwords, software versions and communication settings. Do not describe an unreadable project as a complete backup.
A successful USB connection does not prove that the RS-232 and RS-485 interfaces work. Test each serial port with a suitable device and a verified cable. Check communication settings before deciding that a port has a hardware fault.
If the screen dims or the unit restarts, have the supply wiring, connector and cable contacts checked first. Record the symptom and measurements before replacing board components. Disconnect power before changing wiring or dismantling the unit.
Before reconnecting a replacement panel to the machine, review external-device addresses and command destinations. An address left over from another project can send a command to the wrong device even when the panel itself works correctly.
PDFs and technical documents
Use the Delta TP panel files page for mounting, I/O and communication documentation. In a TP70P family manual, select the TP70P-RM0 column and RM0 port table. The broader Delta PLC and HMI manuals section provides access to other document groups.
Related topics
Explore the Delta PLC family, Delta TP04P and Delta PLC accessories to distinguish panels, controllers and auxiliary hardware. A shared brand or similar enclosure alone does not establish compatibility.
Browse used Delta equipment for listed units, or use Second Hand Models to search other brands by equipment type. Confirm the condition, complete nameplate, included items and any test records with the store responsible for the listing.
External reference
Delta TP70P Quick Start — English, 10 January 2020. A copy of Delta’s manufacturer manual hosted in the Kalatec archive. Review the RM0 mounting drawings, I/O arrangement and communication-port tables together.