Delta TP70P

Delta TP70P:7-inch HMI, PLC and I/O variants

Delta TP70P is an operator-panel family with a 7-inch TFT touchscreen and 800×480 resolution. Local digital/analogue I/O models, RM0/RM1/RM2 communication models and the TP70P-211LC1T weighing model have different terminals and interfaces. Preserve the complete model suffix.

Use TPEditor for screens and the appropriate WPLSoft or ISPSoft environment for supported PLC functions. The screen project and PLC control program are separate projects. Manufacturer references are collected in the Delta HMI PDF archive.

Models and I/O · RM variants · 211LC1T weighing · Ports and pinouts · Software and backup · PDF manuals

Relay and transistor-output models

TP70P-16TP1R has 8 digital inputs and 8 relay outputs. TP70P-16TP1T is the transistor-output version of that I/O class. The 16 in the model name does not mean 16 inputs; read input and output counts separately.

TP70P-32TP1R has 16 digital inputs and 16 relay outputs; TP70P-32TP1T uses transistor outputs. Octal addressing shows X0–X7/X10–X17 and Y0–Y7/Y10–Y17. Do not count X10/Y10 as decimal 10 when determining physical channels.

TP70P-22XA1R has 8 digital inputs,8 relay outputs,4 analogue inputs and 2 analogue outputs. The analogue channels use voltage/current modes. TP70P-22XA1T has transistor outputs. Match terminals, range selection and program channel settings.

TP70P-21EX1R has 8 digital inputs,8 relay outputs,2 current inputs,1 current output and 2 Pt100 inputs. TP70P-21EX1T has transistor outputs. A Pt100 input is not a thermocouple or general 0–10 V input; use the correct sensor diagram and mode.

R and T are electrically different. Relay contacts and transistor outputs have different load-voltage, common-terminal, polarity and current requirements. Confirm sink/source and pulse functions for the actual model rather than transferring wiring solely because the I/O count matches.

RM0, RM1 and RM2: panels without local I/O

TP70P-RM0 is an operator panel without local digital/analogue I/O terminals. It is not a passive terminal base or wiring accessory. It connects to external devices through COM2 RS-232 and COM3 RS-485.

TP70P-RM1 provides COM2 RS-232 and software-selectable RS-485/RS-422 on COM3. TP70P-RM2 has COM2 RS-232 plus two RS-485 channels, COM3 and COM4. Do not generalise RM0 pin assignments to RM1/RM2 or local-I/O models.

The Quick Start PDF 11–14 and 22–24 distinguishes terminals and port roles. RM models have no physical X/Y terminal blocks and therefore do not provide the same field connections as local-I/O models. Verify PLC-program, register and port-mode capabilities for the target.

TP70P-211LC1T: load-cell weighing model

The dedicated weighing manual specifies 17 digital inputs,24 NPN/sinking transistor outputs,4 analogue current outputs,2 multifunction analogue/RTD inputs and 1 load-cell channel for TP70P-211LC1T. Do not reuse 22 XA/21EX channel arrangements or the different TP04P-20EXL1T counts from the same manual.

The load-cell interface supports 4-wire or 6-wire sensors and a 24-bit ADC. ADC resolution does not guarantee complete weighing-system accuracy. Match sensor sensitivity, excitation, rated load, wiring, zero/tare and a known calibration load.

The default interface includes Load Cell Setup, LC Cal. Process and LC Full Screen Display. Delta’s 211LC1T Default Interface record is an application-interface package, not the TPEditor installer or panel firmware. Preserve the machine source and weighing parameters before overwriting an existing application.

Display, enclosure and cutout

The general display specification is 7 inches and 800×480. The 2020 Quick Start gives 205.6×142.6×49 mm for local-I/O R models and 205.6×142.6×37 mm for RM0/1/2. The 211LC1T manual specifies 87.7 mm depth for the weighing model. Allow additional terminal and cable-bend clearance.

The mounting diagrams give an opening range of 190.1–191.0×127.1–128.0 mm and 0.5–4 mm panel thickness, with additional sealing/tolerance requirements. Do not fabricate from an approximate 191×128 mm catalogue figure alone. Check HMI mounting/power details against the actual revision.

USB, COM2/COM3 and cables

USB Type-B / COM1 provides the virtual COM connection for PC transfers. Install the TP USB Driver when required, then match Device Manager’s port to TPEditor’s PC COM Port. A working USB transfer does not establish a working field-device connection.

On the documented local-I/O R models, COM2 RS-485 uses PLC mode and COM3 RS-485 uses panel mode. On the shared DB-9, COM2 D+/D− are pins 6/7; COM3 uses 8/9; GND is 5. RM0 instead uses COM2 RS-232 RX 2/TX 3/GND 5 and COM3 RS-485 D+6/D−7. Verify the actual model pin sheet before reusing a cable.

PLC-mode serial settings use the relevant special PLC registers/bits, while panel mode depends on the TPEditor protocol and objects. Distinguish PC↔TP transfer settings from TP↔PLC field communication. Select programming cables and communication peripherals by electrical interface, pinout and protocol.

The documented TP70P interfaces are USB and serial. Do not transfer DOP-100 Ethernet, editor or remote-access features to TP70P. Match station, baud, parity, data/stop bits and register addresses when connecting an external DVP PLC or drive.

Separate TPEditor screens and PLC programs

The official TPEditor record checked on 15 November 2026 is V1.98.08 and lists TP70P among its supported devices. Use the official TPEditor download and check release/OS details on the TPEditor page.

The TP70P guide uses TPEditor for the screen and WPLSoft/ISPSoft for the applicable PLC project. Obtain WPLSoft and ISPSoft from Delta. COMMGR channels used by ISPSoft are separate from the TP USB driver and should not be imposed as a universal TPEditor connection layer.

Select the TP model, device driver, station and Refer Device addresses correctly. Match bit/word format, signedness, scaling and data length to the PLC. The bit written by a screen button is separate from the PLC logic controlling a physical output.

Keep the original screen source, PLC source, recipes/retained data, serial settings and software/firmware versions together. PC saves, device downloads and persistent-data operations are distinct. A firmware update or factory reset should not be the first communication test without a recoverable backup.

TP70P PDF documents

These five PDFs are prepared for the TP70P section of the shared Delta HMI PDF page. The Quick Start is the 2020 edition; the official 2022 manual record is linked separately. The RM0 sheet includes Turkish. TP panel files provides related PLC/panel archive navigation.

TP70P Quick Start — 2020-01-10 — English; 73 pages; 2.44 MB. 73 pages. R and RM0/1/2 models: I/O, cutout, serial ports, TPEditor and PLC projects. Not the central 2022 edition. PDF 11–14 hardware; PDF 22–24 ports; PDF 40/43/56 project/USB distinctions.

TP70P-RM0 installation and port sheet — includes Turkish — Multilingual; includes Turkish; 2 pages; 0.87 MB. 2 pages; English, Turkish and Chinese, plus a French warning. RM0 mounting and RS-232/RS-485 pinout. Not equated with the central 2022 installation record.

TPEditor user manual — 2016-05-03 — English; 164 pages; 4.80 MB. 164 pages. TP screen projects, objects, PC↔TP versus TP↔PLC, transfers and USB drivers. Not a new V1.98.08-specific manual.

TP70P-211LC1T / TP04P-20EXL1T weighing manual — English; 86 pages; 3.26 MB. 86 pages. TP70P-211LC1T:17 DI/24 DO, NPN,4 AO,2 analogue/RTD and 1 LC; calibration,4/6-wire sensors, registers and wiring. PDF 9–10/20/25/28–36. TP04P data is not transferred to TP70P.

TP70P EU declaration Rev.03 — historical — English; 2 pages; 0.16 MB. 2 pages. Historical appendix names R models, RM0/RM1/RM2,21 EX 1 T and 211 LC 1 T. Not a technical I/O/software compatibility table or an exhaustive list of later variants.

Editor’s note

Record the complete model first. 16TP,32TP,22XA,21EX,RM and 211 LC have different terminal arrangements. Relay R and transistor T versions are not automatic wiring replacements.

Collect screen and PLC sources separately while the panel still works. Save recipes, tare/calibration and serial parameters under the machine name. Opening a file does not prove a complete recovery backup.

Separate PC USB transfer from field communication. Check the correct COM channel and station, then read one known address. Two healthy devices on the wrong channel can still time out.

RM0 has no local X/Y terminals.22XA analogue modes,21EX Pt100 wiring and 211 LC excitation/calibration require their respective diagrams and settings.

For intermittent display or inaccurate touch, check 24 V under load, connectors, contamination/moisture and mounting pressure before erasing software.

Zero/tare and span calibration are separate weighing operations. Use a known load and correct sensor data, and inspect vibration, mechanical friction and shielding. Preserve the working source and change one item at a time.

Related topics

Delta TP70P-16TP1R · Delta TP70P-32TP1R · Delta TP70P-22XA1R · Delta TP70P-21EX1R

Delta TP70P-RM0 · Delta TP panels and remote I/O · Delta TPEditor · Delta WPLSoft

Delta ISPSoft · Delta COMMGR · Delta PLC software · Delta HMI Files

Delta DOP-100 · Delta TP Text Panels · Delta HMI Mounting and Power Connections · Delta HMI Programming and HMC Cables

Delta HMI Shared Power Supplies · Delta HMI Communication Peripheral Units · Delta TP panel files · Delta HMI PDF files

Delta DVP PLC series

External references

Delta TP70P · Official download centre · Manufacturer DVP/TP catalogue copy


Refine Search