Delta DVP80EH00R3

Delta DVP80EH00R3 | 80-Point Relay Output PLC

The Delta DVP80EH00R3 is a 100–240 V AC PLC main unit from the Delta DVP-EH3 series. It has 40 digital inputs rated at 24 V DC and 40 relay outputs. It suits packaging machines, assembly stations and conveyor panels with numerous sensors, valves and contactors.

Inputs, relay outputs and high-speed counting

Digital inputs: The onboard inputs use octal addresses X0–X47. The S/S common connection sets the input circuit for sinking or sourcing. Check PNP and NPN signal types against the panel diagram. When replacing an inductive sensor, photoelectric sensor or limit switch, check both the input voltage and the common connection.

Relay outputs: The onboard outputs use addresses Y0–Y47. For resistive loads, Delta specifies 2 A per point and 5 A per common group. The contact operating voltage must be below 250 V AC or at most 30 V DC. Allow for inrush current and contact life when switching coils. Use a suitably rated interposing relay and load suppression where needed. A suitable flyback diode helps limit the voltage spike when a DC coil switches off.

High-speed counting: Delta specifies a 200 kHz input bandwidth for X0, X1, X4, X5, X10, X11, X14 and X15. Before connecting an incremental encoder, check the high-speed counter mode, assigned input pair and frequency limit for that mode. The R3 Y outputs are for relay switching. For a drive that requires a high-speed pulse command, see the T3 model below.

Programming software and cable

WPLSoft and ISPSoft: Program the DVP80EH00R3 with Delta WPLSoft or Delta ISPSoft. On an existing machine, identify the original project software and CPU firmware first. Select the DVP-EH3 target. For an ISPSoft serial connection, configure and start the channel in COMMGR and select the same channel in ISPSoft. See the guides to ladder diagrams and PLC programming for program structure.

COM1 and programming cable: The PLC uses an 8-pin mini-DIN COM1 / RS-232 connection. Use Delta UC-PRG020-12A for a USB-equipped PC or UC-MS020-01A for a PC with a physical RS-232 port. Install the USB converter driver and select the COM number assigned by Windows. See Delta PLC cables and the guide to serial interface standards to identify the connection type.

Communication and expansion

COM2 / RS-485 is available for field communication. When connecting an HMI or drive, match station addresses, baud rate, parity and frame format. See the guides to Modbus and RS-485, Modbus ASCII and Modbus RTU for these settings. For Ethernet, the CPU can use the optional DVP-FEN01 card. Its manual specifies EH3 firmware 1.12 or later.

Program capacity is 30 k steps. Compatible expansion modules raise total capacity to 512 I/O points. Check the module order and current budget. For a measurement signal from a device such as a pressure transmitter, use a suitable analog input module such as DVP04AD-H3. See the guide to analog and digital inputs when selecting the signal interface.

Editor’s Note

Check the label. When buying used, ask for photos of the full model code, terminals and any fitted communication card. Different output types share the same housing.

Test relays with a load. An output LED can light even when contact resistance is too high. Isolate the machine loads and check each required output with a suitable test load.

Measure the common. If several Y outputs fail together, check the feed and terminal at that group’s C common. A single common connection fault can affect a whole group.

Back up first if BAT.LOW is lit. Save the program, retained data and communication settings before switching off. Check Delta’s procedure before changing the battery.

Test the two ports separately. A successful program read confirms the COM1 programming connection. Test the machine’s COM2 field link with its actual communication settings.

Internal References | Related Delta Models

The DVP80EH00T3 has the same 40 inputs and 40 outputs with transistor switching. The DVP64EH00R3 has 32 inputs and 32 relay outputs. The DVP48EH00R3 has 24 inputs and 24 relay outputs.

The DVP80EH00R2 is the 80-point relay model from the earlier EH2 generation. When migrating from EH2 to EH3, compare the program instructions, expansion modules, terminal layout and serial settings.