Delta DVP48ES300R

Delta DVP48ES300R – ES3 PLC with 24 Inputs and 24 Relay Outputs

The Delta DVP48ES300R is a Delta DVP-ES3 PLC base unit with a 100–240 V AC supply, 24 digital inputs and 24 relay outputs. Delta specifies a 64K-step program capacity, removable terminal blocks and support for up to 256 total I/O points with suitable DVP expansion modules.

24 V DC inputs and relay outputs

X0–X27 use octal addressing. The 24 V DC sink/source inputs use the S/S0 and S/S1 common terminals according to the PNP or NPN sensor wiring. The relay outputs Y0–Y27 use C0, C1 and C2 as common terminals. Delta’s hardware manual specifies 2 A per output and 5 A per common for resistive loads. The contact voltage range is 10–250 V AC or 5–30 V DC. Use the same load voltage throughout each common group.

When relay contacts switch valve or contactor coils, check transient suppression and contact life for the inductive load. For a pulse/direction servo drive, assess the transistor-output DVP48ES300T and the electrical requirements of the drive input.

Communications and panel applications

The CPU has one 10/100 Mbps Ethernet port, two RS-485 ports, a CAN interface and a microSD slot. The Ethernet port supports Modbus TCP and EtherNet/IP. Use RS-485 Modbus for serial drives or instruments, and CANopen for compatible devices. For example, an operator panel can display production counts over Ethernet while the PLC reads drive status over a separate RS-485 bus.

Programming software and cable

Use ISPSoft or DIADesigner to program the DVP48ES300R. Delta specifies ISPSoft 3.08 or later for ES3. Select the ES3 CPU in the project. For the initial connection, use a USB data cable with a USB Mini-B connector at the PLC. For ISPSoft, select the Windows-assigned COM port in COMMGR. When transferring an existing ladder program, verify the hardware configuration, X/Y addresses and network parameters as well.

Editor’s Note

Check for the 48ES300R suffix on the nameplate. The 48ES300T has the same I/O counts with different output hardware.

With the power disconnected, inspect the removable terminals and C0–C2 commons for loose screws or heat damage.

Test inputs through their assigned S/S group. Check that each relay contact switches a suitable test load as well as checking the output LED.

After plugging in the Mini-B cable, check the COM port that Windows assigns. Select that port in COMMGR when using ISPSoft.

Before replacement, back up the program, expansion layout, IP and serial settings. Check what the microSD card contains and how the machine uses it.

Related models and topics

The DVP48ES300T has the same I/O counts with transistor outputs. The DVP32ES300R has 16 inputs and 16 relay outputs. The DVP64ES300R provides 32 inputs and 32 relay outputs, while the DVP80ES300R provides 40 inputs and 40 relay outputs. For new panels, assess Derell Series B PLCs against the project’s I/O and software requirements.

Used Delta automation equipment · Delta PLC · Delta DVP PLC series · Delta DVP PLC files

External references

Delta ES3 instruction sheet (2024, EN/TR) · Delta ES3 hardware and operation manual (2023, EN) · Delta ES3 programming manual (2024, EN)