The Delta DVP48EH00R2 is a PLC main unit from the Delta DVP-EH2 series. It runs on 100–240 V AC and has 24 digital inputs rated at 24 V DC and 24 relay outputs. It reads sensors and sequences valves, contactors and indicators in packaging machines, conveyors and assembly stations.
Digital inputs and encoder wiring
The inputs use octal addresses X0–X27. The S/S common connection sets the input circuit for sinking or sourcing. Check PNP or NPN wiring against the panel diagram. When replacing an inductive sensor, photoelectric sensor or limit switch, check both the input voltage and the common connection.
The EH2 hardware sheet specifies 200 kHz input bandwidth for X0, X1, X4 and X5, and 20 kHz for X10, X11, X14 and X15 on this model. When connecting an incremental encoder, verify the A/B signal type, input pair and frequency limit of the selected high-speed counter mode. These ratings apply to the X inputs. The Y outputs are for relay switching.
Relay outputs and load selection
The onboard outputs use addresses Y0–Y27. For resistive loads, Delta specifies 2 A per point and 5 A per common group. Contact operating voltage must be below 250 V AC or at most 30 V DC. Allow for inrush current and switching frequency when driving coils. Use a suitably rated interposing relay and load suppression where needed. A suitable flyback diode limits the voltage spike when a DC coil switches off.
Programming software and cable
Program the DVP48EH00R2 with WPLSoft or ISPSoft. Select the DVP-EH2 CPU target. For an ISPSoft serial connection, configure and start the channel in COMMGR and select the same channel in ISPSoft. Keep the original project file when servicing an existing machine. See the guides to ladder diagrams and PLC programming for help reading the program.
The PC connects through the PLC’s 8-pin mini-DIN COM1 / RS-232 port. Use Delta’s DVPACAB215 (1.5 m) or DVPACAB230 (3 m) serial cable. On a USB-equipped PC, use a suitable USB-to-RS-232 adapter with the serial cable. Install the adapter driver and select the COM number assigned by Windows. See Delta PLC cables and the guide to serial interface standards when selecting the connection.
Field communication and expansion
COM2 / RS-485 can communicate with HMIs and drives. For Modbus over RS-485, match the station address, baud rate, parity and frame format at both ends. Check the existing project to determine whether it uses Modbus ASCII or Modbus RTU.
Program capacity is 16 k steps. Compatible expansion modules can bring the EH2 system to 512 total I/O points. Check module compatibility, order and the power budget. For 0–10 V or 4–20 mA measurements, consider a suitable module such as DVP04AD-H2. See the guide to analog and digital inputs when selecting an interface.
Editor’s Note
Get a close-up of the label. When buying used, ask for photos showing the 00R2 suffix and the output terminals. Record the codes of any fitted expansion or communication cards.
Test the relays under load. A worn contact can drop voltage even while the output LED is lit. Isolate the machine loads and check the required Y channels with a suitable test load.
Check the common when a group fails. If several outputs stop together, inspect the feed and connection at that group’s C terminal first.
Back up first if BAT.LOW is lit. Save the program, retained data and serial settings before switching off. Follow Delta’s battery replacement procedure.
Test both ports separately. A successful program read verifies COM1. Test the COM2 field link separately with the machine’s device and serial settings.
Internal References | Related Delta Models
The DVP48EH00T2 is the EH2 transistor-output model with the same 24 inputs and 24 outputs. The DVP40EH00R2 has 24 inputs and 16 relay outputs. The DVP64EH00R2 has 32 inputs and 32 relay outputs.
The DVP48EH00R3 has the same 24/24 I/O split and belongs to the EH3 generation. Compare program instructions, expansion modules, terminal layouts and serial settings before migrating.
Related Topics
See grounding and fuses for the panel supply, and NO and NC contacts for field signals. See safety relays for emergency-stop and guard-door circuits.